| 2006-07-05 00:00:00 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE LOAD CALCULATION @218.5 AMPS |
| | EXCEEDS THE SERVICE SIZE OF 200 AMPS. |
| | 230.31 SIZE AND RATING. |
| | (A) GENERAL. SERVICE-LATERAL CONDUCTORS |
| | SHALL HAVE SUFFICIENT AMPACITY TO CARRY |
| | THE CURRENT FOR THE LOAD AS COMPUTED IN |
| | ACCORDANCE WITH ARTICLE 220 AND SHALL |
| | HAVE ADEQUATE MECHANICAL STRENGTH. |
| | SUGGEST LARGER SERVICE. |
| | |
| | 2} THE 3/0 FEEDERS FOR 250 AMPS DOES NOT |
| | COMPLY WITH 310.15(B)(6). |
| | |
| | 3} THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST BE SIZED PER 250.66, MINIMUM OF A |
| | #2 COPPER FOR 250 AMP OCP. |
| | |
| | 4} THE FEEDER FOR PANEL "B" IS NOT |
| | LISTED IN PANEL "A". |
| | |
| | 5} THE SMALL APPLIANCE CIRCUITS @ 2400 |
| | VA ARE TOO LARGE FOR A 20 AMP CIRCUIT |
| | SEE 220.16 FOR LOAD CALCULATION |
| | REQUIREMENTS, SMALL APPLIANCE. |
| | |
| | 6} THE LAUNDRY CIRCUIT CALCULATION |
| | REQUIRED BY 220.16(B), IS NOT IN THE |
| | LOAD CALCULATION. |
| | |
| | 7} THE A/C CALCULATIONS ON THE |
| | ELECTRICAL PLAN DOES NOT CORRESPOND TO |
| | THE MECHANICAL PLAN. PLEASE CORRELATE |
| | SAME. |
| | |
| | 8} PLEASE SEE THE GFI LOCATED IN THE |
| | SINK IN THE CABANA BATH. |
| | |
| | 9} BEDROOMS 1 AND 3 NEED A RECEPTACLE |
| | ADDED PER 210.52(A)(1). |
| | |
| | 10} PLEASE INSERT ALL NEW PAGES INTO ONE |
| | COMPLETE SET OF PLANS WHEN RESUBMITTING. |
| | ALSO DO NOT RESUBMIT SHEETS FROM OLD |
| | REVIEWS OTHER THAN THE PREVIOUS REVIEW, |
| | REMOVE ALL OTHERS. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |