| Plan Review Notes For Permit 06010171 |
| Permit Number |
06010171 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-07-05 00:00:00 | *** DENIED *** | | | 1) PLEASE SEE MANUAL J CALCULATIONS PAGE | | | 7 AND CORRECT THE EQUIPMENT LISTING FOR | | | A/C SYSTEM #3 (MASTER SUITE). | | | | | | 2) PLEASE CORRECT THE EQUIPMENT LISTING | | | AS TWO A/C SYSTEMS ARE LISTED AS #2. | | | | | | 3) PLEASE SHOW ON MECHANICAL PLANS AS | | | YOU HAVE ON THE ELECTRICAL PLANS, THAT | | | THE GAS CLOTHES DRYER AND GAS WATER | | | HEATER ARE DIRECT VENTED. | | | | | | 4) PLEASE SEE HIGH-LITED DUCTS ON | | | MECHANICAL PLANS AS SOME ARE NOT SIZED | | | AND SOME ARE RUNNING INTO OTHER DUCTS | | | WITH NO MIXING BOXES AND NO SIZE | | | CHANGES. | | | | | | 5) PLEASE SEE ELECTRICAL REVIEW NOTES #7 | | | AND #10, AND CORRECT. | | | | | | 6) PLEASE REMOVE ALL OLD PLANS AND | | | SUBMIT TWO COMPLETE SETS OF PLANS, THE | | | SETS SHOULD INCLUDE ANY APPROVED STAMPED | | | PAGES FROM PAST REVIEWS (PLUMBING & | | | ZONING). | | | | | | 7) PLEASE BE ADVISED THAT NOTE #6 HAS | | | BEEN REQUESTED NUMEROUS TIMES BY OTHER | | | DEPARTMENTS, AND SEE ATTACHED ADVISORY | | | REGARDING FOUR TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|