| Plan Review Notes For Permit 06010171 |
| Permit Number |
06010171 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-12 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATION @254 AMPS | | | EXCEEDS THE SERVICE SIZE OF 200 AMPS. | | | 230.31 SIZE AND RATING. | | | (A) GENERAL. SERVICE-LATERAL CONDUCTORS | | | SHALL HAVE SUFFICIENT AMPACITY TO CARRY | | | THE CURRENT FOR THE LOAD AS COMPUTED IN | | | ACCORDANCE WITH ARTICLE 220 AND SHALL | | | HAVE ADEQUATE MECHANICAL STRENGTH.. | | | | | | 2} PROVIDE PANEL SCHEDULES FOR PANELS | | | "A" AND "C". 408.4 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561) 805-6718 |
|