| Plan Review Notes For Permit 06010171 |
| Permit Number |
06010171 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-10 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A RISER DIAGRAM, SERVICE | | | EQUIPMENT LOCATIONS AND PANEL SCHEDULES | | | PER 215.5. | | | | | | 2}REGARDING THE NOTE REFERRING TO | | | SMOKE DETECTORS, THEY MUST BE ON AN ARC | | | FAULT BREAKER PER 210.12. | | | | | | 3} THE NOTE REGARDING "RECEPTACLES ON | | | ARC FAULT CIRCUITS" SHOULD READ | | | "OUTLETS", SEE PRIOR COMMENT AND SEE | | | 210.12. | | | | | | 4} THERE IS NO ELEVATOR EQUIPMENT IN THE | | | CALCULATIONS, BUT ONE SHOWN ON THE PLAN. | | | SEE ARTICLE 620. | | | | | | 5} PLEASE SHOW THE LOCATION OF ALL | | | EQUIPMENT ON THE PLAN. POOL PUMPS, | | | CONDENSING UNITS ETC. SO THAT DISCONNECT | | | LOCATIONS AND SERVICE RECEPTACLE | | | PLACEMENT CAN BE REVIEWED. | | | | | | 6} THERE ARE SEVERAL ROOMS WHERE THE | | | RECEPTACLE SPACING DOES NOT COMPLY WITH | | | 210.52(A)(1&2). SEE REVIEWED SET OF | | | PLANS FOR APPROXIMATE LOCATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|