Plan Review Notes
Plan Review Notes For Permit 06010106
Permit Number 06010106
Review Stop B
Sequence Number 1
Notes
Date Text
2006-01-05 00:00:001) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 AN APPROVED ASSEMBLY IS REQUIRED. SEE
 FL#985-R1 FOR MORE INFORMATION.
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 _X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ CONTRACTOR FAILED TO INDICATE THE
 DECK TYPE FOR THE MODIFIED ROOF. PRODUCT
 APPROVAL IS FOR LIGHRWEIGHT CONCRETE.
  
 _IF__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 2) GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL: (561)805-6726
  
  
  
  
  
  
  
  
  