Plan Review Notes
Plan Review Notes For Permit 06010103
Permit Number 06010103
Review Stop M
Sequence Number 4
Notes
Date Text
2006-06-07 00:00:00*** DENIED ***
 (REVISION TO MECH. PLANS PAGE M-2.)
 1) THE RETURN AIR DUCT NEEDS TO BE AS
 LARGE OR LARGER THEN THE TWO SUPPLY AIR
 DUCTS ADDED TOGETHER.
  
 2) ARE YOU INSTALLING A TOTAL OF FOUR
 12"X12" RETURN AIR GRILLS TO AIR HANDLER
 # 2. PLEASE CLARIFY.
  
 3) PLEASE SHOW LOCATION OF AIR HANDLER
 #2 ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.