| 2006-03-09 00:00:00 | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO ROUGH INSPECTIION. | | | | | | 1} PLEASE SEE CIRCUIT #22 HAS THE WRONG | | | OCP LISTED @ 30AMPS. | | | | | | 2} VERIFY LOCATION OF PANEL "A", | | | INDICATED AS METER. ALSO PANEL "B" IS | | | INDICATED AS A METER. INDICATE THE | | | LOCATION OF ALL SERVICE EQUIPMENT ON THE | | | PLAN, AND CORRECTLY LABEL THEM. | | | | | | 3} THE DISCONNECTS AT THE A/C UNITS NEED | | | TO COMPLY WITH 110.26 CLEARANCE. | | | | | | 4} IF THE GENERATOR LOCATED BEHIND THE | | | GARAGE IS TO BE PART OF THIS PERMIT IT | | | MUST BE PROPERLY LOCATED IN THE RISER, | | | AND ALL NECESSARY PAPERWORK MUST BE | | | SUBMITTED. SEE ATTACHED APPLICATION | | | REQUIREMENTS | | | | | | IF THER ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|