Date Text
2006-03-09 00:00:00 
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTIION.
  
 1} PLEASE SEE CIRCUIT #22 HAS THE WRONG
 OCP LISTED @ 30AMPS.
  
 2} VERIFY LOCATION OF PANEL "A",
 INDICATED AS METER. ALSO PANEL "B" IS
 INDICATED AS A METER. INDICATE THE
 LOCATION OF ALL SERVICE EQUIPMENT ON THE
 PLAN, AND CORRECTLY LABEL THEM.
  
 3} THE DISCONNECTS AT THE A/C UNITS NEED
 TO COMPLY WITH 110.26 CLEARANCE.
  
 4} IF THE GENERATOR LOCATED BEHIND THE
 GARAGE IS TO BE PART OF THIS PERMIT IT
 MUST BE PROPERLY LOCATED IN THE RISER,
 AND ALL NECESSARY PAPERWORK MUST BE
 SUBMITTED. SEE ATTACHED APPLICATION
 REQUIREMENTS
  
 IF THER ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  