| 2006-03-17 00:00:00 | 1) NOTE: THE PRODUCT APPROVAL FOR THE |
| | GARAGE DOOR IS EXPIRED. PLEASE SUBMIT AN |
| | APPROVED AND UPDATED PRODUCT FOR REVIEW. |
| | SEE MIAMI DADE NOA #01-0323.05 EXIRED |
| | 2/14/06. |
| | THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMMENDMENT TO FBC 106.3.3 |
| | |
| | 2) INDICATE ON THE WHERE EACH FOOTING |
| | DETAIL IS USED ON SHEET A1. DETAILS |
| | F1,F2 AND F3 SHOULD BE SHOWN ON THE |
| | FOUNDATION PLANS. |
| | |
| | 3) THE CONNECTION DETAIL SHOWS TAPCONS |
| | SCREWS. WHY WILL TAPCONS BE USED TO |
| | ATTATCH THE RAILINGAS TO THE WOOD FRAME |
| | INSTEAD OF WOOD SCREWS? PLEASE CLARIFY. |
| | |
| | 4) STATE HOW THE ROOF TILES WILL BE |
| | ATTATCH TO THE DECK. WILL THE TILES BE |
| | NAILED,SCREWED OR FOAM TO THE DECK? |
| | |
| | 5) THE F1 FOOTING DETAIL ON SHEET A1 |
| | INDICATES A CC66.THIS IS A WOOD TO WOOD |
| | COLUM CAP NOT A WOOD TO CONCRETE. SEE |
| | SIMPSON STRONG-TIE CATALOG. SHOW THE |
| | PROPER CONNECTION FOR THIS DETAIL. |
| | |
| | 6) THE ABU66 SHOULD BE USED ON CONCRETE |
| | SO, IF THIS ANCHR IS USED THE BASE SHALL |
| | BE CONCRETE. SEE SHEET A6. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |