2006-03-17 00:00:001) NOTE: THE PRODUCT APPROVAL FOR THE
 GARAGE DOOR IS EXPIRED. PLEASE SUBMIT AN
 APPROVED AND UPDATED PRODUCT FOR REVIEW.
 SEE MIAMI DADE NOA #01-0323.05 EXIRED
 2/14/06.
 THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 2) INDICATE ON THE WHERE EACH FOOTING
 DETAIL IS USED ON SHEET A1. DETAILS
 F1,F2 AND F3 SHOULD BE SHOWN ON THE
 FOUNDATION PLANS.
  
 3) THE CONNECTION DETAIL SHOWS TAPCONS
 SCREWS. WHY WILL TAPCONS BE USED TO
 ATTATCH THE RAILINGAS TO THE WOOD FRAME
 INSTEAD OF WOOD SCREWS? PLEASE CLARIFY.
  
 4) STATE HOW THE ROOF TILES WILL BE
 ATTATCH TO THE DECK. WILL THE TILES BE
 NAILED,SCREWED OR FOAM TO THE DECK?
  
 5) THE F1 FOOTING DETAIL ON SHEET A1
 INDICATES A CC66.THIS IS A WOOD TO WOOD
 COLUM CAP NOT A WOOD TO CONCRETE. SEE
 SIMPSON STRONG-TIE CATALOG. SHOW THE
 PROPER CONNECTION FOR THIS DETAIL.
  
 6) THE ABU66 SHOULD BE USED ON CONCRETE
 SO, IF THIS ANCHR IS USED THE BASE SHALL
 BE CONCRETE. SEE SHEET A6.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  