| Date |
Text |
| 2006-02-02 00:00:00 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS ARE MISSING THE |
| | MANUAL J SECTION OF THEM, NEED MANUAL J |
| | SHOWING THE DUCT SIZE. |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| | BY OWNER/AGENT. |
| | |
| | 3) ENERGY CAL'S ARE CALLING FOR TWO |
| | 55,000 TOTAL BTU SYSTEMS, MECHANICAL |
| | PLANS ARE SHOWING TWO 36,000 TOTAL BTU |
| | SYSTEMS PLEASE CORRECT & PROVIDE MANUAL |
| | J. |
| | |
| | 4) MECHANICAL PLANS MUST SHOW JOB |
| | ADDRESS, NAME OF COMPANY THAT DESIGNED |
| | MECH. PLANS, CO. ADDRESS, CO. TELEPHONE |
| | NUMBER, CO. LICENSE NUMBER, AND NAME & |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN ,ON THEM. |
| | |
| | 5) 1ST. FLOOR BATHROOM AND MASTER |
| | BATHROOM WHERE TUB IS, MAY NEED AN |
| | EXHUST FAN PLEASE SEE 2004 FBC/R303.3 . |
| | |
| | 6) NEED TO SHOW CLOTHES DRYER EXHUST |
| | DUCT ON MECH. PLANS. |
| | |
| | 7) AHU #1. NO RETURN AIR PROVIDED FOR |
| | DINING ROOM, KITCHEN, FAMILY ROOM, & |
| | LIVING ROOM DUE TO DOOR IN HALLWAY, SEE |
| | NOTE #11. |
| | |
| | 8) AHU #1 & 2. RETURN AIR GRILL AND DUCT |
| | (FLEX) IS TO SMALL FOR A 3 TON UNIT. |
| | |
| | 9) AHU #2. NO RETURN AIR PROVIDE FOR |
| | MASTER SUITE DUE TO DOORS, SEE NOTE #11. |
| | |
| | 10) RETURN AIR TRANSFER DUCT TO BEDROOM |
| | #1 IS TO SMALL, SEE NOTE #11. |
| | |
| | 11)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |