Plan Review Notes
Plan Review Notes For Permit 06010103
Permit Number 06010103
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-02 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE MISSING THE
 MANUAL J SECTION OF THEM, NEED MANUAL J
 SHOWING THE DUCT SIZE.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) ENERGY CAL'S ARE CALLING FOR TWO
 55,000 TOTAL BTU SYSTEMS, MECHANICAL
 PLANS ARE SHOWING TWO 36,000 TOTAL BTU
 SYSTEMS PLEASE CORRECT & PROVIDE MANUAL
 J.
  
 4) MECHANICAL PLANS MUST SHOW JOB
 ADDRESS, NAME OF COMPANY THAT DESIGNED
 MECH. PLANS, CO. ADDRESS, CO. TELEPHONE
 NUMBER, CO. LICENSE NUMBER, AND NAME &
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN ,ON THEM.
  
 5) 1ST. FLOOR BATHROOM AND MASTER
 BATHROOM WHERE TUB IS, MAY NEED AN
 EXHUST FAN PLEASE SEE 2004 FBC/R303.3 .
  
 6) NEED TO SHOW CLOTHES DRYER EXHUST
 DUCT ON MECH. PLANS.
  
 7) AHU #1. NO RETURN AIR PROVIDED FOR
 DINING ROOM, KITCHEN, FAMILY ROOM, &
 LIVING ROOM DUE TO DOOR IN HALLWAY, SEE
 NOTE #11.
  
 8) AHU #1 & 2. RETURN AIR GRILL AND DUCT
 (FLEX) IS TO SMALL FOR A 3 TON UNIT.
  
 9) AHU #2. NO RETURN AIR PROVIDE FOR
 MASTER SUITE DUE TO DOORS, SEE NOTE #11.
  
 10) RETURN AIR TRANSFER DUCT TO BEDROOM
 #1 IS TO SMALL, SEE NOTE #11.
  
 11)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  