Plan Review Notes
Plan Review Notes For Permit 06010103
Permit Number 06010103
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE CIRCUIT #22 HAS THE WRONG
 OCP LISTED @ 60AMPS.
  
 2} VERIFY LOCATION OF PANEL "A",
 INDICATED AS METER.THE SERVICE
 DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER
 OUTSIDE OF A BUILDING OR STRUCTURE OR
 INSIDE NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS.230.70(A)(1). A
 DISCONNECT IS REQUIRED OUTSIDE IF THE
 SERVICE IS RAN THROUGH THE RESIDENCE.
  
 3} A SMOKE DETECTOR IS REQUIRED IN THE
 ROOM DESIGNATED AS "OFFICE" AND ALSO
 OUTSIDE PER R313.1 FBC (RESIDENTIAL).
 THIS ROOM IS A BEDROOM BY DEFINITION.
  
 4} BEDROOM#1,2, SITTING AREA, AND THE
 MASTER BEDROOM ALL NEED ADDED
 RECEPTACLES TO COMPLY WITH 210.52.ALSO
 SMOKE DETECTORS PER 313.1 FBC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved