| Plan Review Notes For Permit 06010103 |
| Permit Number |
06010103 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-01 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SEE CIRCUIT #22 HAS THE WRONG | | | OCP LISTED @ 60AMPS. | | | | | | 2} VERIFY LOCATION OF PANEL "A", | | | INDICATED AS METER.THE SERVICE | | | DISCONNECTING MEANS SHALL BE INSTALLED | | | AT A READILY ACCESSIBLE LOCATION EITHER | | | OUTSIDE OF A BUILDING OR STRUCTURE OR | | | INSIDE NEAREST THE POINT OF ENTRANCE OF | | | THE SERVICE CONDUCTORS.230.70(A)(1). A | | | DISCONNECT IS REQUIRED OUTSIDE IF THE | | | SERVICE IS RAN THROUGH THE RESIDENCE. | | | | | | 3} A SMOKE DETECTOR IS REQUIRED IN THE | | | ROOM DESIGNATED AS "OFFICE" AND ALSO | | | OUTSIDE PER R313.1 FBC (RESIDENTIAL). | | | THIS ROOM IS A BEDROOM BY DEFINITION. | | | | | | 4} BEDROOM#1,2, SITTING AREA, AND THE | | | MASTER BEDROOM ALL NEED ADDED | | | RECEPTACLES TO COMPLY WITH 210.52.ALSO | | | SMOKE DETECTORS PER 313.1 FBC | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|