| 2006-12-20 18:46:26 | *** UNSAT 5TH REVIEW *** |
| | |
| | ** PLEASE SEE NOTES FROM THE FOUR PREVIOUS REVIEWS AS |
| | FOLLOWS. |
| | PLEASE CALL IS THERE ARE ANY QUESTIONS OR COMMENTS. |
| | |
| | |
| | 1) NOTE:PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW |
| | DATED 11/16/06. PLEASE SEE THAT THE MANUFACTURES SPECS |
| | DO NOT CORRELATE WITH THE SAME INFORMATION AS PROVIDED |
| | ON PLANS. PLEASE SEE THE SPECIFIC UNIT IS NOT CHECKED, |
| | MARKED, HIGHLIGHTED OR NOTED FOR THE PARTICULAR UNIT. |
| | PLEASE SEE THE COMMENTS BELOW. |
| | PLEASE SEE SPECS FOR THE ATS WHICH ARE ONLY NOW BEING |
| | SUBMITTED FOR REVIEW WOULD STILL NEED TO INDICATE BEING |
| | 3R LISTED AS WELL AS RISER INDICATING THE SAME. 90.7, |
| | 110.3, |
| | FBC 106.1.2 |
| | |
| | ** PREVIOUS REVIEW NOTES BELOW FROM REVIEW#4 DATED |
| | 11/16/06 ** |
| | NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE SPECS WERE |
| | SUBMITTED, HOWEVER AS REQUESTED IN THE PREVIOUS REVIEWS |
| | PLEASE BE SURE ALL EQUIPMENT CORRELATES FOR USE AND |
| | INSTALLATION ETC. |
| | PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A |
| | FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE |
| | SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL |
| | BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN |
| | SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF |
| | 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES |
| | MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS |
| | ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET |
| | THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE. |
| | PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE |
| | ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT |
| | SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED. |
| | PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS. |
| | PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND |
| | KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS |
| | THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS |
| | INDICATES 42KW, AND THE NEED TO CORRELATE THE |
| | MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF |
| | THE UTMOST IMPORTANCE. |
| | PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83" |
| | LONG, 40" WIDE AND 72" IN HEIGHT. |
| | PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED |
| | WE ARE UNABLE TO VERIFY. |
| | PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF |
| | THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE |
| | UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE |
| | CLEARANCE IF THE UNIT IS 72" HIGH. |
| | PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE |
| | AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON |
| | EQUIPMENT HAVE BEEN SUBMITTED. |
| | PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS. |
| | |
| | ** PLEASE KNOW BASED ON THESE COMMENT FOR THE |
| | GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY |
| | NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE |
| | TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST |
| | ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED |
| | TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL |
| | WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT |
| | AT THIS TIME. |
| | |
| | |
| | ** PREVIOUS REVIEW COMMENT REVIEW #3** |
| | PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT |
| | SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD |
| | REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES |
| | WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR |
| | AND ETC. |
| | PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT, |
| | HOWEVER PLEASE SEE PLEASE SUBMIT THE |
| | MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS, |
| | AND WP HOUSING. |
| | PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME |
| | ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK |
| | SUBMITTED WHICH DO NOT APPLY AT ALL TO GEN ETC. PLEASE |
| | SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM FORD |
| | MOTOR CORP? |
| | PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS |
| | BOOKS AND SHEETS AND SOME ARE NOT THE SAME |
| | EQUIPMENT??? |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT |
| | SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE |
| | THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND |
| | ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND |
| | STAMPING. |
| | |
| | FBC 106.1, 106.1.2, 110.3, 90.7 ETC. |
| | |
| | 2) NOTE: PLEASE SEE REVIEW NOTE #3 FROM THE PREVIOUS |
| | REVIEW. |
| | PLEASE SEE NOT ENERGY CALCULATIONS/LIGHTING POWER |
| | DENSITIES FOR CODE COMPLIANCE WERE SUBMITTED. PLEASE |
| | SEE NOTE BELOW WHICH SPEAKS OF THE "BLOCK" LOCATED ON |
| | PLANS WHICH DID NOT PROVIDE THE INFORMATION AS NEEDED |
| | AND REQUIRED PER 13-415.1.AB.1, 13-415.2. |
| | |
| | *** PREVIOUS REVIEW NOTE REVIEW, REVIEW #4DATED |
| | 11/16/06** |
| | NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED. THIS |
| | WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL |
| | REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE |
| | REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED |
| | WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE |
| | LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE |
| | THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW. |
| | PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH |
| | A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT |
| | ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY |
| | REFERENCED. |
| | PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S) |
| | AND SECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER |
| | DENSITIES, PER FBC |
| | 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES |
| | 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE |
| | SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW |
| | COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE |
| | LOCATED IN PACKAGE. IN EITHER CASE, PLEASE SUBMIT. |
| | |
| | |
| | |
| | ** NEW NOTE FOR REVIEW NUMBER 5*** |
| | |
| | 1) NOTE: PLEASE CORRELATE PLANS AND LAYOUT OF |
| | MAINS/PANELS AND DISCONNECTS ON RISER WITH THAT OF THE |
| | LAYOUT SHOWN ON E-5. |
| | PLEASE SEE THE MAIN DISCONNECT FOR THE SECONDARY SIDE |
| | OF THE TRANSFORMER COULD NOT BE CLEARLY LOCATED. |
| | |
| | 2) NOTE: PLEASE SEE AS PLANS ARE NOW INDICATING THE |
| | LOCATION OF ALL EQUIPMENT BEING MOVED TO THE NEW |
| | LOCATION PLEASE CLARIFY THIS AS THE SUBMITTAL BOOKS FOR |
| | THE NEW STRUCTURAL MEZZANINE LEVEL FROM PREVIOUS |
| | SUBMITTED PLANS ARE STILL BEING SUBMITTED. PLEASE SEE |
| | ANY BUILDING REVIEW COMMENTS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-12-20 06:52:55 | REVIEW IN PROGRESS |