| Date |
Text |
| 2006-09-24 00:00:00 | *** UNSAT 3RD REVIEW *** |
| | |
| | ** PLEASE SEE NOTES FROM THE TWO |
| | PREVIOUS REVIEW AS FOLLOWS. |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT THE |
| | MANUFACTURES/SPEC CUT SHEETS FOR THE |
| | GENERATOR, ATS, AND WP HOUSING. |
| | PLEASE SEE THAT THIS 3RD REVIEW IS FIRST |
| | TIME ANY PAPER WORK WAS SUBMITTED, |
| | HOWEVER THERE IS PAPERWORK SUBMITTED |
| | WHICH DO NOT APPLY AT ALL TO THIS GEN |
| | ETC. |
| | PLEASE SEE "PARTS LIST" BOOK FOR |
| | GASOLINE ENGINES FORM FORD MOTOR CORP? |
| | PLEASE SEE WARRANTY BOOKS, PLEASE SEE |
| | MULTIPLE ATS BOOKS AND SHEETS AND SOME |
| | ARE NOT THE SAME EQUIPMENT??? |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS, WITH |
| | ONLY PERTINENT SHEETS RELEVANT TO THIS INSTALLATION. |
| | PLEASE PLACE THIS SHEETS |
| | INTO SETS BOUND TOGETHER IN A NEAT AND |
| | ODERLY FASHION WITH LABELS OR TABS FOR |
| | REVIEW AND STAMPING. |
| | |
| | FBC 106.1, 106.1.2, 110.3, 90.7 ETC. |
| | |
| | 2) NOTE: PLEASE SEE THE "S" SHEETS STILL |
| | DO NOT CONTAIN THE CORRECT INFORMATION |
| | AS REQUIRED UNDER THE FLORIDA |
| | ADMINSTRATIVE CODE 61G15-23.002, FLORIDA |
| | STATUES 471.023. |
| | THIS IS THE 3RD REVIEW FOR THIS NOTE. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. PLEASE KNOW, "S" |
| | SHEETS MAY BE RETAINED BY THIS OFFICE |
| | AND FORWARDED TO THE FBPE'S. |
| | |
| | 3) NOTE: PLEASE SEE MISSING CALCULATIONS |
| | FOR LIGHTING POWER DENSITIES, PER FBC |
| | 2004, 13-.AB.1, 13-415.2,13-415.2.ABC.1, |
| | TABLES 415.2.C.1/415.2.B.1. IT WAS |
| | THOUGHT THESE WERE SUBMITTED FOR |
| | COMPLIACNE WITH THE PREVIOUS REVIEW |
| | COMMENTS FOR CHAPTER 13, HOWEVER THESE |
| | COULD NOT BE LOCATED IN PACKAGE. IN |
| | EIHTER CASE , PLEASE SUBMIT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |