| Date |
Text |
| 2006-08-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE ACCESSIBLE. |
| | SUBMIT A DETAIL SHOWING THE FOLLOWING: |
| | FOR THE W/C |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | E. 11-4.16.6 DISPENSERS |
| | FOR THE LAV |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | FOR THE TOILET ROOM |
| | A. 11-4.22.3 A 5' TURNING AREA IS |
| | REQUIRED. |
| | ****RESPONSE NOTED, BUT ELEVATIONS |
| | INDICATED ON SHEET A1, (A7 44, 45), ARE |
| | NOT ON SHEET A7. PLEASE CLARIFY. |
| | |
| | 2. SHT A4 SUBMIT INFORMATION ON THE |
| | VINYL WALL PAPER SHOWING COMPLIANCE WITH |
| | SECTION 1210.2. WALLS SHALL BE |
| | NONABSORBENT. |
| | ****RESPONSE NOTED, BUT CODE SECTION |
| | 1210.2 STATES "WALLS WITHIN 2FT OF |
| | URINALS AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT SURFACE, TO A |
| | HEIGHT OF 4 FEET ABOVE THE FLOOR. THE |
| | INTENT OF THE CODE IS ALSO FOR CLEAN UP |
| | OF THE WALLS. PLEASE SUBMIT A SAMPLE OF |
| | THE WALL COVERING SO COMPLIANCE CAN BE DETERMINED. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. P3 NATURAL GAS RISER. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT: |
| | A. OK |
| | B. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ****RESPONSE NOTED, BUT GENERATOR SHALL |
| | VENT OUT OF THE STRUCTURE AND ABOVE THE |
| | ROOF LEVEL. |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO MANUF. SPECIFICATION SHEETS |
| | SUBMITTED. |
| | |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | |
| | **************NEW COMMENT************** |
| | |
| | 1B. FROM LOOKING AT THE MSDS SHEETS, A |
| | EYE WASH/EMERGENCY SHOWER WILL BE |
| | REQUIRED. SECTION 411. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |