| 2006-02-15 00:00:00 | *********** UNSAT *************** |
| | |
| | ** PLEASE KNOW, PLANS/SUBMITTED |
| | MATERIALS ARE NOT COMPLETE AT THIS TIME |
| | FOR A COMPLETE REVIEW. |
| | |
| | **************************************** |
| | |
| | 1A)NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.001 WHICH |
| | REQUIRED THE RAISED SEAL TO CHANGE FROM |
| | THE WORDING OF "CERTIFICATE" TO |
| | "LICENSE" BY 2/5/04, HOWEVER AN |
| | EXTENSION WAS GRANTED BY THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS TO |
| | DECEMBER 31,2005. |
| | PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE |
| | WORDING ON RAISED SEAL AS REQUIRED. |
| | FS 471.025 |
| | ANY SEALED PLANS SHALL BECOME "VOID". |
| | PLEASE BE SURE THE NEW RAISED SEAL |
| | CONTAINS THE "LICENSE" WORDING. |
| | PLEASE CONTACT THIS OFFICE OR THE FBPE'S |
| | IF THERE ARE ANY QUESTIONS. |
| | |
| | *************************************** |
| | |
| | |
| | 1)NOTE; PLEASE SEE LOCATION OF GENERATOR |
| | LOCATED ON THE 6TH LEVEL IS NOT |
| | PERMITTED BY THIS OFFICE AND FIRE |
| | MARSHAL'S OFFICE. |
| | PLEASE ALSO SEE ELECTRICAL COMMENTS |
| | PERTAINING LOCATION OF DISCONNECTING |
| | ETC. |
| | |
| | 2)NOTE: PLEASE SEE ALL DISCONNECTING |
| | MEANS FOR POWER FEEDERS ETC SHALL BE |
| | GROUPED. |
| | 230.72,225.31. |
| | |
| | 3)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | THE FOLLOWING APPLICABLE CODES, 2002 |
| | NFPA-70, 2003 NFPA-101, 2002 NFPA-72, |
| | 2002 NFPA-110, 1999 NFPA-75 |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL |
| | SPECS/MANFACTURES CUT SHEETS FOR |
| | GENERATOR, ATS ETC. |
| | IF THE EPSS IS GOING TO BE INSTALLED |
| | UNDER THIS PERMIT, PLEASE INCLUDE. |
| | |
| | 5)NOTE: PLEASE SEE 645.10,,300.21 FOR |
| | LOCATION AND SHUT DOWN OF ELECTRICAL |
| | REQUIRED FOR A/C'S AND ALL ALL EQUIPMENT |
| | FEEDING IT ROOM. |
| | PLEASE SEE A/C SYSTEMS. |
| | |
| | 6)NOTE: PLEASE SEE 645.5D FOR SD'S AND |
| | DETAILS REQUIRED FOR REVIEW AND |
| | CONNECTION INTO THE FA SYSTEM. |
| | |
| | 7) NOTE: PLEASE SHOW AND IDENTIFY AL |
| | REQUIREMENTS FOR THE IT ROOM AND |
| | REFERENCE NFPA-75 ON ALL P,M, E, |
| | ARCHITECTUAL AND STRUCTUAL PLANS. |
| | ALL CONTRUCTION, FIRE SPRINKLER |
| | PROTECTION AND OR OTHER EXTINGUISHING |
| | SYSTEMS SHALL BE PROVIDED. |
| | PLEASE MAKE REFERENCE TO THE ROOM |
| | PENETRATIONS AS REQUIRED PER CHAPTER 3. |
| | ETC |
| | |
| | 8)NOTE: PLEASE SEE THAT AN EM BATTERY |
| | BACK LT OF SOME SORT BE PROVIDED IN THE |
| | ELECTRICAL ROOM. |
| | 700.16, 101,7.8,7.9 ETC. |
| | |
| | 9)NOTE: PLEASE PROVIDE GROUNDING |
| | ELECTRODE CONNECTION DETAIL(S) FOR THE |
| | TRANSFORMER(S). 250.30, 250.58. |
| | PLEASE SEE THE CODE SHALL NOT BE |
| | REFERENCED IN WHOLE OR IN PART IN LEIU |
| | OF THE TECHNICAL INFORMATION REQUIRED ON |
| | SAID PLANS. |
| | |
| | 10)NOTE: PLEASE SEE THE FBC 2004 CHAPTER |
| | 13. PLEASE SEE 13-413.1ABC.1 FOR VOLTAGE |
| | DROP OF FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-415.1.ABC.1.1 FOR LIGHTING |
| | CONTROL OF SPCES. |
| | TANDEM WIRING PER 13-415.1.ABC.3, .4 |
| | PLEASE SEE ALL OF CHAPTER 13 FOR |
| | COMMERCIAL SPACES. |
| | |
| | 11)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH TEH SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE MANY WSH UNITS, A/C 1&2 UNITS |
| | ETC. |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE PROVIDE IDENTIFICATION |
| | ON PLANS FOR ALL FIXTURES AND CORRELATE |
| | WITH THE FIXTURE LEGEND SUBMITTED. |
| | |
| | 13)NOTE: PLEASE SEE THAT ALL TITLE |
| | BLOCKS FOR DESIGNERS OF RECORD CONTAIN |
| | ALL LICENSING INFORMATION AS REQUIRED |
| | UNDER FAC 61G15-23.002, FS 471.023, THIS |
| | COMMENT IS NOT FOR STANDROD ENG.\ |
| | PLEASE SEE "S" SHEETS. |
| | |
| | 14)NOTE: PLEASE SEE THE COMPLETE |
| | VALUATION FOR SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR AND MATERIALS, EVEN IF |
| | EQUIPMENT IS OWNER SUPPLIED. PLEASE SEE |
| | ANY SYSTEM PERMANANTLY INSTALLED, |
| | HARDWIRED , FASTENED IN PLACE SHALL BE |
| | INCLUDED. |
| | FBC ADMINISTRATIVE SECTION 108.3. AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWERS WHICH WILL AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. THIS WILL HELP TO ALLEAVIATE |
| | ANY DELAY'S IN PROJECT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |