| 2006-01-30 00:00:00 | *** DENIED *** |
| | 1)ENERGY CALCULATIONS NEED TO BE ON FORM |
| | 600A-04 (2004) PER FBC 13-600.3.A . |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| | BY OWNER/AGENT. |
| | |
| | 3) 2ND. FLOOR RAG 18X8, IF THIS IS A |
| | TRANSFER GRILL IT IS TO SMALL FOR THE |
| | AMOUNT OF SUPPLY AIR TO THE ROOM SEE |
| | NOTE #4. |
| | |
| | BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 5) PLEASE SHOW ON MECHANICAL PLANS HOW |
| | RETURN AIR IS BEING PROVIDE FOR 1 ST. |
| | FLOOR EXISTING HOUSE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |