| Plan Review Notes For Permit 06010036 |
| Permit Number |
06010036 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-31 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE PROVIDE ROOM AND AREA | | | DESIGNATIONS ON PLANS. | | | PLEASE LABEL ELECTRICAL RM,PLEASE ALSO | | | ADD NOTEWHICH WILL ALSO REQUIRE | | | SIGNAGE ON DOOR FOR | | | "NO STORAGE PER ORDER OF FIRE MARSHAL" | | | | | | 2)NOTE: PLEASE SEE CHAPTER 13 2004 FBC, | | | PLEASE ADJUST AND ADD NOTE FOR ENERGY | | | CODE COMPLIANCE PER 13 COMMERCIAL | | | SPACES. | | | | | | 3)NOTE: PLEASE SHOW THE CONTINUOUS LOADS | | | AT 125%. | | | 215.3,230.42 | | | | | | 4)NOTE: PLEASE SEE ID PLANS SUBMITTED | | | ALSO NOTED AS BEING "ELECTRICAL PLANS"? | | | PLEASE KNOW, IF THESE ID PLANS ARE GOING | | | TO SUBMITTED, PLEASE BE SURE PLASN | | | CORRELATE WITH ELECTRICLA PLANS DONE BY | | | KAMM CONSULTING. | | | 215.5 | | | | | | 5)NOTE: PLEASE REFERENCE CURRENT CODE | | | INS EFFECT FOR NFPA-70 (2002 ) AND | | | NFPA-72(2002). | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] |
|