| Plan Review Notes For Permit 06010031 |
| Permit Number |
06010031 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-03 00:00:00 | 1) THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | | | _X__ CONTRACTOR DID NOT PROVIDE THE MEAN | | | ROOF HEIGHT. | | | | | | | | | | | | __X_ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED.PLEASE SELECT A SYSTEM | | | FROM THE NOA PACKAGE FOR REVIEW.THE | | | FIRST FEW PAGES WHICH LIST THE DIFFERENT | | | MATERIALS ARE REQUIRED ALONG WITH ONE OF | | | THE SYSTEMS WHICH WILL BE USED.SUBMIT | | | TWO COPIES OF THE NOA NOT ONE. | | | | | | 2) FBC 1606.2.5.GENERAL LIMITATION | | | #9 PROHIBITS RATIONAL ANALYSIS OR | | | EXTRAPOLATION TO ENHANCE THE UPLIFT | | | PRESSURE AT PERIMETER AND CORNER AREAS | | | BY REDUCING THE FASTENER SPACING IN | | | THESE AREAS.EITHER SELECT AN | | | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) | | | THAT DOES NOT CITE GENERAL LIMITATION | | | #9.ALTERNATIVELY IF THE SELECTED | | | SYSTEM DOES CITE GENERAL LIMITATION #9, | | | IT MUST HAVE A MAXIMUM DESIGN PRESSURE | | | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 | | | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT | | | OF 30 FEET OR LESS). | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | |
|