Plan Review Notes
Plan Review Notes For Permit 06010021
Permit Number 06010021
Review Stop G
Sequence Number 3
Notes
Date Text
2006-08-08 00:00:00RESTAMP: CONTRACTOR LOST PERMIT SET.
  
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON