| 2006-01-17 00:00:00 | DENIED | | | | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRD FOR | | | GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. THE DRAWING SUBMITTED IS | | | NOT AN ISOMETRIC, AND HARD TO UNDERSTAND | | | 2. THE GAS SYSTEM SUBMITTED IS SIZED | | | INCORRECTLY, PLEASE SIZE CORRECTLY AND | | | RESUBMIT. PLEASE READ ATTACHED LETTERS, | | | CORRECTED DRAWINGS, AND CODE TABLES. | | | | | | END OF COMMENTS | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | 2006-01-03 00:00:00 | TO "G" BOX |
|