Plan Review Notes
Plan Review Notes For Permit 06010008
Permit Number 06010008
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-03 00:00:00DENIED
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 2) FBC-2004424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(ADD TO NOTES, AND DETAILS
 REQUIRED)
 3) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL REQUIRED,
 NOTE: PRINT DRAWING ONLYINDCATES
 REINFORCED CONC. SLAB IT MUST
 INDICATE THE 4" THICKNESS)
 4) FBC-2004 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95 BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
 5) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6) FBC-2004 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLBG. SEC. 605.21
 PURPLE PRIMER REQUIRED ON PVC PIPING
 (ADD TO NOTES)
  
 END OF COMMENTS
  