| Date |
Text |
| 2006-03-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS. FIRM LICENSE NUMBER IS |
| | REQUIRED IN THE TITLE BLOCK OF ALL |
| | DESIGN PROFESSIONALS. FAC 61G1-16.004(2) |
| | AND FS 481.219. FAC 61G15-23.002(2) AND |
| | FS 471.025. |
| | 2. SHT A-0.02 APPLICABLE CODES SHALL |
| | READ FBC-2004. |
| | 3. SHT A-2.01 SUBMIT CALCULATIONS FOR |
| | MINIMUM FACILITIES REQUIRED FOR ALL |
| | COMMON AREAS ON THE GROUND FLOOR AND ON |
| | THE 9TH FLOOR. THIS SHALL INCLUDE THE |
| | RETAIL AREAS. SHOW THE SQUARE FOOTAGE |
| | AREA OF EACH COMMON SPACE AND RETAIL |
| | SPACE AND INDICATE COMPLIANCE WITH |
| | SECTIONS 1004.1.2 AND 403.1. SHOW THE |
| | OCCUPANCY FOR COMMON AREAS. |
| | 4. SHT A-2.03 ROOFS OVER SECONDARY |
| | ENTRIES, SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS. SHOW THE |
| | SQUARE FOOTAGE OF ROOF PLUS 1/2 AREA OF |
| | ALL VERTICAL WALLS, INCLUDING PARAPETS. |
| | SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE LOCATION OF |
| | SECONDARY ROOF DRAIN REQUIRED BY |
| | SECTIONS 1107.1 & 1107.2. |
| | 5. SHT A-2.06 UNIT TYPE MISSING FROM |
| | MANY UNITS. PLEASE INDICATE UNIT TYPE |
| | FOR ALL UNITS. SECTION 106.1.1. |
| | 6. SHT A-2.09 SEPARATE POOL PERMITS |
| | REQUIRED. PLANS SHALL BE REVIEWED AND |
| | APPROVED BY THE PALM BEACH COUNTY HEALTH |
| | DEPT. PRIOR TO SUBMITTING FOR REVIEW BY |
| | THE CITY WPB. 3 COPIES REQUIRED. SECTION |
| | 102.2.1. |
| | 7. SHT A-2.09 MORE INFORMATION REQUIED |
| | FOR THIS SHEET. ARE THERE SPA'S ON THIS |
| | SHEET. NO SPAS ARE IDENTIFIED. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | 8. SHTS A-2.09,A-2.10, & A-2.13, |
| | SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE |
| | FOOTAGE FOR EACH AREA BEING DRAINED, |
| | ALONG WITH 1/2 THE AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS ALONG WITH ANY |
| | ROOF AREA THAT DRAINS ONTO A ROOF AREA |
| | FROM ABOVE. SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. THE SIZING OF SCUPPERS CAN |
| | NOT BE DETERMINED WITHOUT REFERENCE TO |
| | THE DEFLECTION OF THE ROOF. PLEASE STATE |
| | ON PLANS CALCULATIONS FOR SCUPPERS WERE |
| | ACCORDING TO SECTIONS 1101.7, 1107.3 AND |
| | TABLE 1106.7. SHOW THE LOCATION OF ALL |
| | PRIMARY AND SECONDARY ROOF DRAINS AND/OR |
| | SCUPPERS. |
| | 9. SHT A-2.13 DETAILS 1, 2, & 3. |
| | SEPARATE SECONDARY ROOF DRAINS ARE |
| | REQUIRED PER SECTIONS 11-7.1 & 1107.2. |
| | 10. SHT A-2.13 DETAIL 4 TABLE 1616.3 IS |
| | FOR HIGH VELOCITY WIND ZONES ONLY. |
| | SIZING OF SCUPPERS SHALL BE PER SECTIONS |
| | 1101.7, 1107.3 AND TABLE 1106.7. (SEE |
| | COMMENT 8). |
| | 11. SHT A-2.13 DETAIL 4 REFERENCES SHT |
| | A-10.03 DETAIL 7. DETAIL 7 IS A |
| | THRESHOLD DETAIL. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | 12. SHT A-3.01 TOILET ROOMS W-108A & |
| | W-108B SHALL BE ACCESSIBLE. PLEASE |
| | PROVIDE A DETAIL SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 |
| | WITH ALL SUBSECTIONS. |
| | 13. SHTS A-3.02BC & A-3.02CD TOILET |
| | ROOMS SHALL BE ACCESSIBLE. PLEASE |
| | PROVIDE A DETAIL SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22 |
| | WITH ALL SUBSECTIONS. |
| | 14. SHTS A-3.02BC & A-3.02CD KITCHEN |
| | LOUNGE SINKS SHALL BE ACCESSIBLE. PLEASE |
| | PROVIDE A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | CLEAR FLOOR SPACE SHALL BE FORWARD |
| | APPROACH AND SHALL EXTEND A MAXIMUM OF |
| | 19" UNDERNEATH THE SINK. |
| | 15. ALL DWELLING UNITS SHALL COMPLY WITH |
| | FHA-98 DESIGN MANUAL REQUIREMENTS 1 THRU |
| | 7. INDICATE SPECIFICATION "A" OR "B" FOR |
| | EACH UNIT/BATHROOM. SHOW THE CLEAR FLOOR |
| | SPACE FOR ALL USABLE FIXTURES IN THE |
| | BATHROOMS AND KITCHEN. SHOW THE BACKING |
| | REQUIRED BY REQUIREMENT 6 FOR THE W/C'S, |
| | TUBS & SHOWERS. |
| | 16. SHTS A-3.09BC & A-3.09AD TOILET |
| | ROOMS SHALL BE ACCESSIBLE. SUBMIT |
| | DETAILS SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | 17. SHTS A-3.09AB & A-3.09DA POOL PUMP |
| | ROOM SHALL COMPLY WITH SECTIONS |
| | 424.1.5.3 THRU 424.1.5.9. SUBMIT |
| | DETAILS. INDICATE WHERE CHEMICALS ARE TO |
| | BE STORED AND IN WHAT QUANTITY. SECTION |
| | 424.1.5.8. |
| | 18. SHTS A-4.01 & A-4.02 POWDER ROOM AT |
| | LOWER LEVELS SHALL COMPLY WITH |
| | REQUIREMENTS 6 AND 7. SEE PAGE 7.33OF |
| | THE FHA-98 DESIGN MANUAL. SHOW CLEAR |
| | FLOOR SPACE FOR THE LAV AND W/C. LAV TO |
| | BE CENTERED ON THE 48" LENGTH IF |
| | PARALLEL APPROACH, OR THE CABINET BASE |
| | SHALL BE REMOVABLE AND THE LAV SHALL BE |
| | MINIMUM 15" OFF THE WALL. THE W/C SHALL |
| | BE 18" OFF THE WALL TO THE CENTER TO THE |
| | FIXTURE AND SHALL HAVE A MINIMUM OPENING |
| | OF 33". INDICATE ON THE FLOOR PLAN. SEE |
| | PAGES 7.43, 7.44, 7.45 & 7.46. THE |
| | KITCHEN SHALL SHOW THE CLEAR FLOOR SPACE |
| | FOR EACH APPLIANCE AND A 5' TURNING |
| | AREA. SEE PAGES 7.3 THRU 7.11. |
| | 19. SHTS A-4.03 THRU A-4.14 CLEAR FLOOR |
| | SPACE FOR ALL REQUIRED FIXTURES SHALL BE |
| | SHOWN ON THE ENLARGED PLANS. FOR W/C'S |
| | SEE PAGE 7.43, ONE OF THREE SHALL BE |
| | PROVIDED. FOR LAVS SEE PAGES 7.47 & |
| | 7.48. LAVS SHALL BE 2'10" MAXIMUM OFF |
| | THE FLOOR. SEE PAGE 7.52. CLEAR FLOOR |
| | SPACE SHALL BE PARALLEL TO THE SHOWER |
| | AND FLUSH WITH THE CONTROL WALL. SEE |
| | PAGE 7.56. FOR KITCHENS SEE REQUIREMENT |
| | 7. |
| | 20. SHTS A-4.03 THRU A-4.14 MINIMUM |
| | OPENING SIZE FOR W/C'S IS 33" AND THE |
| | FIXTURE SHALL BE 18" OFF THE WALL AND |
| | 18" OFF ONE FIXTURE AND MINIMUM 15" OFF |
| | THE OTHER FIXTURE WHEN BETWEEN TWO |
| | FIXTURES. SEE PAGES 7.43 THRU 7.46. |
| | BIDETS SHALL NOT BE IN THE CLEAR FLOOR |
| | SPACE OF THE W/C PER INTERPRETATION OF |
| | THE ARCHITECTURAL BOARD FOR HUD. |
| | 21. SHT A-4.12A PH LOFT 03 ROOF LEVEL |
| | SHOWS A POOL. MORE INFORMATION IS |
| | REQUIRED FOR POOL. INDICATE TYPE OF POOL |
| | AND USE OF POOL. INDICATE IF THERE IS |
| | POOL EQUIPMENT SUCH AS A PUMP, FILTER, |
| | ETC. SECTION 106.1.1. |
| | 22. SHT A-8.03 FINISH SCHEDULE. ROOMS |
| | W-108A & W-108B, INDICATE HOW DRYWALL/PT |
| | IN TOILET ROOMS COMPLY WITH THE |
| | REQUIREMENT OF SECTION 1210.2 WALLS. |
| | WALLS WITHIN 2' OF URINALS AND W/C'S |
| | SHALL BE NONABSORBENT. |
| | 23. SHT P-1.01 COL LINE R.7 SOUTH OF COL |
| | LINE K SHOWS "4 INCH RWL STUBBED UP 36 |
| | INCHES ABOVE FINISHED FLOOR FLR BACKWASH |
| | DISCHARGE." PLEASE INDICATE WHAT IS |
| | DISCHARGING INTO STUB UP. ONLY STORM |
| | WATER SHALL DISCHARGE INTO STORM LINES |
| | PER MUNICIPAL CODE SECTION 90.203. |
| | 24. SHT P-1.01 CODED NOTES (1), 3" |
| | DISCHARGE FROM FIRE PROTECTION DRAIN |
| | RISER TO SANITARY SYSTEM NOT THE STORM |
| | SYSTEM PER MUNICIPAL CODE SECTION |
| | 90.203. |
| | 25. SHT P-1.01 BACKFLOW PREVENTORS AND |
| | GAS METER DO NOT REFLECT THE LOCATION |
| | SHOWN ON THE CIVIL PLANS. THEY APPEAR TO |
| | BE ON THE SIDEWALK. ALSO THE CIVIL |
| | SHEETS INDICATE 3 BACKFLOWS, (1 FOR |
| | IRRIGATION). PLEASE CORRELATE THE |
| | PLUMBING SHEETS WITH THE CIVIL SHEETS. |
| | SECTION 106.1.1. |
| | 26. SHT P-1.01 OFFICE MANAGER PLUMBING |
| | FLOOR PLAN TO SHOW REVENT TO REFLECT |
| | RISER DIAGRAM. SECTION 106.1.1. |
| | 27. SHT P-1.01 SECTION 404.11 FUEL GAS |
| | PIPING UNDERGROUND BENEATH BUILDINGS. |
| | PLEASE INDICATE IF THE GAS PIPING IS |
| | UNDER THE BUILDING OR UNDER A SLAB |
| | OUTSIDE THE BUILDING. SLEEVE SHALL BE |
| | SEALED ON BOTH ENDS TO PREVENT OF WATER |
| | AND INSECTS. SLEEVE SHALL BE VENTED. |
| | 28. SHT P-1.01 OFFICE MANAGER WATER |
| | DISTRIBUTION RISER DIAGRAM, AIR CHAMBERS |
| | ARE NOT APPROVED. DELETE FROM RISER. |
| | SECTION 604.9. |
| | 29. SHT P-1.01 PLEASE SUBMIT THE |
| | INFORMATION FOR THIS SHEET DRAWN TO A |
| | MINIMUM OF 1/8" SCALE AS REQUIRED IN |
| | SECTION 106.1.3. |
| | 30. SHT P-1.02 SALON, KITCHEN AND REST |
| | ROOMS WATER DISTRIBUTION RISER DIAGRAMS, |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | FROM RISER DIAGRAMS. WATER HAMMER |
| | ARRESTOR IS REQUIRED AT THE REFRIGERATOR |
| | PER SECTION 604.9. - THERMAL EXPANSION |
| | CONTROL IS REQUIRED AT THE WATER HEATER |
| | PER SECTION 607.3.2. SHOW ON RISER |
| | DIAGRAM. |
| | 31. SHT P-1.02 4" GAS LINES IN BLOCK |
| | WALL NOT APPROVED. SECTION 1925.3.5(1) - |
| | THIS IS SHOWN AS 6" GAS LINES ON THE |
| | PLUMBING SHEETS. PLEASE CORRELATETHE |
| | FLOOR PLAN WITH THE GAS RISER DIAGRAM. |
| | 32. SHTS P-2.04AB & P-2.04BC HAVE NOT |
| | BEEN SUBMITTED. SECTION 106.1.1. (SEE |
| | PROJECT DRAWING INDEX) |
| | 33. SHT P-2.04CD 6" RWL IS SHOWN AS 4" |
| | RWL ON THE FLOOR ABOVE AND THE FLOOR |
| | BELOW. PLEASE CLARIFY. SECTION 106.1.1. |
| | 34. SHT P-2.05AB PIPING TO W/C'S AND |
| | LAVS DO NOT PIPE TO THE FIXTURES. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | 35. SHT P-2.05DA INDICATE THE LOCATION |
| | OF RISER J/3. SECTION 106.1.1. |
| | 36. SHTS P-2.07AB & P-2.07DA, INDICATE |
| | UNIT TYPES. SECTION 106.1.1. |
| | 37. SHTS P-2.07AB, P-2.07BC, P-2.07CD, |
| | P-2.07DA INDICATE 3"(40SF) "DOWN" WHEN |
| | THEY APPEAR TO BE GOING "UP" TO THE 7TH |
| | FLOOR. PLEASE CLARIFY. SECTION 106.1.1. |
| | 38. SHTP-2.08AB SHOWS RISER K3 VTR IN |
| | TWO LOCATIONS. THIS DOES NOT REFLECT THE |
| | RISER DIAGRAM. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 37. SHT P2.08AB COOLING TOWER |
| | DRAIN/OVERFLOW DETAILS SHOW THE DRAIN |
| | AND OVERFLOW DRAINING TO THE SANITARY. |
| | OVERFLOW SHALL DISCHARGE SEPARATELY TO |
| | THE STORM SYSTEM. MUNICIPAL CODE SECTION |
| | 90-125. |
| | 38. SHT P-2.08AB SHOW THE LOCATION OF |
| | RISERS J/2 & J/1. SECTION 106.1.1. |
| | 39. SHT P-2.08DA COOLING TOWER |
| | DRAIN/OVERFLOW DETAILS SHOW THE DRAIN |
| | AND OVERFLOW DRAINING INTO THE SANITARY. |
| | THE OVERFLOW SHALL DISCHARGE SEPARATELY |
| | INTO THE STORM SYSTEM. MUNICIPAL CODE |
| | SECTION 90-125. |
| | 40. SHTS P-2.09AD, P-2.09BC, P-2.09CD, |
| | P-2.09DA SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS. SUBMIT THE |
| | CALCULATIONS FOR ALL PRIMARY & SECONDARY |
| | DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE SQUARE FOOTAGE |
| | AREA DRAINING INTO EACH DRAIN ALONG WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS, MANSARDS, & BUILDING WALLS |
| | CONTRIBUTING TO THE AREA BEING DRAINED |
| | IN CALCULATIONS. |
| | 41. SHTS P-2.09AB, P-2.09DA 4" RWL |
| | STUBBED UP FOR BACKWASH DISCHARGE SHALL |
| | DRAIN TO SANITARY SYSTEM. MUNICIPAL CODE |
| | SECTION 90-203. |
| | 42. SHTS P-2.09AB, P-2.09DA SHOWS PD |
| | 50SF, BUT DISCHARGE LINE SHOWS 150SF. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | 43. SHTS P-2.10BC, P-2.10CD RISER |
| | DESIGNATIONS L/1, L/2, L/3 SUPERIMPOSED |
| | OVER "FIRE ALARM ROOMS" AND HARD TO |
| | READ. PLEASE FIX TYPE-O. SECTION |
| | 106.1.1. |
| | 44. SHTS P-2.10BC, P-2.10CD, P-2.11BC, |
| | P-2.11CD, P-2.12BC, P-2.12CD INDICATE |
| | UNIT TYPES ON FLOOR PLAN. SECTION |
| | 106.1.1. |
| | 45. SHTS P-2.13BC, P-2.13CD SANITARY |
| | RISER FOR W/M IN PH-LOFT 05 IS NOT SHOWN |
| | ON THE FLOOR BELOW. INDICATE FIXTURE |
| | TYPE ON FLOOR PLAN. SECTION 106.1.1. |
| | 46. SHTS P-2.13BC, P-2.13CD SHOWS 2 |
| | RWL'S BEHIND THE POWDER ROOM W/C IN |
| | PH-LOFT 05 NOT SHOWN ON THE FLOOR ABOVE. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | 47. SHTS P-2.13BC, P-2.13CD SHOW RISER |
| | NUMBERS FOR KITCHEN SINK, POWDER ROOM, |
| | AND BATHROOM RISERS IN PH-LOFT 04. |
| | SECTION 106.1.1. |
| | 48. SHTS P-2.14BC, P-02.14CD4" RWL & |
| | OFFSET NOT SHOWN ON ROOF. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | 49. SHTS P-2.14BC, P-02.14CD 3" REQUIRED |
| | TO WASH MACHINE FOR PH-LOFTS 04 & 07. |
| | SECTION 406.3. |
| | 50. SHTS P-2.15BC, P-2.15CD SEPARATE |
| | SYSTEMS FOR DRAIN & OVERFLOW FROM THE |
| | COOLING TOWER. DRAIN TO SANITARY AND |
| | OVERFLOW TO STORM. MUNICIPAL CODE |
| | SECTION 90-203. |
| | 51. SHTS P-2.15BC, P-2.15CD 4" RWL |
| | STUBBED UP TO 36" FINISHED FLOOR FOR |
| | BACKWASH DISCHARGE SHALL DRAIN TO |
| | SANITARY. MUNICIPAL CODE SECTION 90-203. |
| | 52. SHTS P-2.15BC, P-2.15CD COOLING |
| | TOWER DRAIN/OVERFLOW DETAIL, DRAIN TO |
| | SANT. & OVERFLOW TO STORM. SECTION |
| | 90-203. - INDICATE MATERIAL FOR SYSTEM & |
| | SUPPORTS TO BE SPACED PER TABLE 308.5. |
| | 53. SHT P-2.15CD SHOWS 6" RD(3490SF), |
| | BUT NO ROOF DRAIN SHOWN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | 54. SHTS P-3.01 THRU P-3.14 NOTE: |
| | "DISCHARGE DRYER CONDENSATE INTO W/M |
| | WASTE TRAP". SUBMIT A DETAIL SHOWING |
| | CONNECTIONS TO THE DRYER & WASTE TRAP, |
| | PIPE SIZE, PIPING MATERIAL, AND MANUF. |
| | SPECIFICATION SHEETS ALONG WITH |
| | INSTALLATION INSTRUCTIONS. SECTION |
| | 106.1.1. |
| | 55. SHT P-3.03 UNIT TYPE "1C' STATES |
| | "SEE DWG. P-3.03 FOR CONTINUATION RISER |
| | N/1". CONTINUATION NOT FOUND ON THIS |
| | SHEET. PLEASE CLARIFY. SECTION 106.1.1. |
| | 56. SHT P-3.04 UNIT TYPE "2G" STATES |
| | "SEE DWG. P-3.02 FOR CONTINUATION", |
| | CONTINUATION NOT FOUND ON P-3.02. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | 57. SHT P-3.05 UNIT TYPES "2B" & "2B-1" |
| | SHOW TWO DIFFERENT RISERS FOR RISERS |
| | H/1, H/2, & G/3. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 58. SHT P-3.05 WATER RISER DIAGRAM FOR |
| | UNIT "2B-1", AIR CHAMBERS ARE NOT |
| | APPROVED. DELETE FROM RISER. SECTION |
| | 604.9. SHOW COMPLIANCE WITH SECTION |
| | 607.3.2 FOR THERMAL EXPANSION CONTROL. |
| | 59. SHT P-3, (BETWEEN P-3.06 & P-3.08), |
| | WATER RISER DIAGRAM, AIR CHAMBERS ARE |
| | NOT APPROVED. DELETE FROM RISER DIAGRAM. |
| | SECTION 604.9. - SHOW COMPLIANCE WITH |
| | SECTION 607.3.2 THERMAL EXPANSION |
| | CONTROL. |
| | 60. SHT P3.08 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED, DELETE FROM |
| | RISER DIAGRAM. SECTION 604.9. - SHOW |
| | COMPLIANCE WITH SECTION 6-7.3.2 THERMAL |
| | EXPANSION CONTROL. |
| | 61. SHT P-3.10 PH-LOTS 02, SHOW PIPING |
| | ON FLOOR PLANS. SECTION 106.1.1. - WATER |
| | RISER DIAGRAM, AIR CHAMBERS ARE NOT |
| | APPROVED, DELETE FROM RISER DIAGRAM. - |
| | SHOW COMPLIANCE WITH SECTION 607.3.2 |
| | THERMAL EXPANSION CONTROL. |
| | 62. SHT P-3.12 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER DIAGRAM. SECTION 604.9. - SHOW |
| | COMPLIANCE WITH SECTION 607.3.2 THERMAL |
| | EXPANSION CONTROL. |
| | 63. SHT P-3.14 WATER RISER DIAGRAM, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | RISER DIAGRAM. SECTION 604.9. - SHOW |
| | COMPLIANCE WITH SECTION 607.3.2. THERMAL |
| | EXPANSION CONTROL. |
| | 64. SHT P-4.0 CONDENSATE RISER DIAGRAM, |
| | VENT SHALL NOT TERMINATE INSIDE A WALL, |
| | OR IN A PLENUM. PLEASE INDICATE WHERE |
| | THE VENT WILL TERMINATE TO COMPLY WITH |
| | THIS INFORMATION. SUBMIT A DETAIL |
| | SECTION 106.1.1. |
| | 65. SHT P-4.0 WATER RISER DIAGRAMS, RPZV |
| | BACKFLOWS ARE REQUIRED ON THE WATER |
| | SUPPLYS FOR THE POOL EQUIPMENT ROOM, |
| | (UNLESS AN AIR GAP IS SHOWN ON WATER |
| | MAKEUP), AND AT SUPPLY FOR THE |
| | IRRIGATION. BACKFLOW PREVENTION IS ALSO |
| | REQUIRED FOR THE SUPPLY OF THE TRASH |
| | CHUTE WASHDOWN. PLEASE INDICATE METHOD |
| | OF BACKFLOW PREVENTION. SECTION 608. |
| | 66. SHTS P-4.1, P-4.2, P-4.3, P-4.5 |
| | WATER RISER DIAGRAMS, AIR CHAMBERS ARE |
| | NOT APPROVED. DELETE FROM RISER |
| | DIAGRAMS. SECTION 604.9. SHOW COMPLIANCE |
| | WITH SECTION 607.3.2 THERMAL EXPANSION |
| | CONTROL. |
| | 67. SHTS P-4.5 THRU P-4.12 FIXTURE UNITS |
| | FOR SANITARY RISER DIAGRAMS SHALL BE |
| | RECHECKED. PER TABLE 709.1, A BATHROOM |
| | GROUP IS 5FU AS DEFINED IN SECTION 202, |
| | BUT EXTRA FIXTURES SHALL BE ADDED PER FU |
| | VALUE OF EACH FIXTURE. FLOOR DRAINS ARE |
| | 2FU WITH A 2" TRAP, BUT LARGER TRAPS |
| | SHALL BE SIZED FOR FIXTURE UNITS PER |
| | TABLE 709.2. A POWDER ROOM IS 4FU. SINKS |
| | ARE 2FU AND LAVS ARE 1FU BUT LAVS ARE |
| | ONLY LOCATED IN POWDER ROOMS OR |
| | BATHROOMS. |
| | 68. SHTS P-4.5 THRU P-4.12 ALL SANITARY |
| | RISERS, INDICATE WHERE OR WHAT SHEET THE |
| | CONTINUATIONS FOR EACH RISER UPPER OR |
| | LOWER SECTIONS ARE LOCATED, OR SUBMIT |
| | RISER DIAGRAMS THAT ARE CONTINUOUS FROM |
| | THE BUILDING DRAIN THRU THE VENT THRU |
| | ROOF. (MANY HOURS PLAN REVIEW WERE SPENT |
| | TRYING TO TRACK THE RISER DIAGRAMS AS |
| | SUBMITTED). SHOW ALL OFFSET VENTS PER |
| | SECTION 915.2 & 915.3, SHOW ALL VENT |
| | CONNECTIONS PER SECTION 903.4 FOR ALL |
| | STACKS THAT REQUIRE A VENT STACK PER |
| | SECTION 903.2. |
| | 69. SHT P-4.6 RISER E/2 INDICATES NO |
| | FIXTURES ABOVE THE 23RD FLOOR, BUT THIS |
| | DOES NOT REFLECT THE FLOOR PLAN FOR THE |
| | 24TH FLOOR AS A KITCHEN SINK AND A |
| | POWDER ROOM ARE SHOWN. PLEASE CORRELATE |
| | THE RISER DIAGRAM AND THE FLOOR PLAN. |
| | SECTION 106.1.1. |
| | 70. SHT P-4.6 RISER G/1 IDENTIFY ALL |
| | FIXTURES. SECTION 106.1.1. |
| | 71. SHT P-4.6 RISER H/1 3" BRANCH LINE |
| | REQUIRED TO WASH MACHINE. SECTION 606.3. |
| | - OFFSET VENTS REQUIRED PER SECTIONS |
| | 915.2 AND 915.3. |
| | 72. SHT P-4.6 RISER H/2 INDICATE |
| | FIXTURES FOR 3RD, 4TH, & 6TH FLOORS. |
| | SECTION 106.1.1. |
| | 73. SHT P-4.6 RISER G/3 5TH & 7TH FLOORS |
| | DO NOT REFLECT THE FLOOR PLAN. DOES NOT |
| | SHOW THE OTHER BATHROOM. NOT CHANGED ON |
| | FLOOR PLAN. SECTION 106.1.1. |
| | 74. SHT P-4.7 RISER H/5 INDICATE ON |
| | RISER WHERE 8TH FLOOR PIPING CAN BE |
| | LOCATED. - 3RD THRU 7TH FLOORS DO NOT |
| | REFLECT THE FLOOR PLAN. NO FIXTURES |
| | SHOWN. SECTION 106.1.1. |
| | 75. SHT P-4.7 RISER N/3 DOES NOT REFLECT |
| | THE 24TH FLOOR FIXTURE UNITS. (+2) |
| | SECTION 106.1.1 AND TABLE 710.1(2). |
| | 76. SHT P-4.8 RISER N/3 3" REQUIRED ON |
| | ALL WASH MACHINE BRANCH LINES. SECTION |
| | 406.3. |
| | 77. SHT P-4.8 RISERS J/1, J/2, J/3, K/1, |
| | K/2, 11, 12, 13, & 14 7TH FLOOR, 3" |
| | REQUIRED FOR WASH MACHINE BRANCH LINES. |
| | SECTION 406.3. |
| | 78. SHT P-4.8 4TH LEVEL RISERS K/2, J/3, |
| | 11/12, 14 DO NOT REFLECT THE FLOOR PLAN. |
| | SECTION 106.1.1. |
| | 79. SHT P-4.8 4TH LEVEL TWO J/2 SANT. |
| | RISERS SHOWN. PLEASE CLARIFY. SECTION |
| | 106.2.1. |
| | 80. SHT P-4.8 4TH LEVEL RISER J/3 NOT |
| | SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY |
| | SECTION 106.1.1. |
| | 81. SHT P-4.8 4TH LEVEL RISER 14, 3" |
| | REQUIRED FOR WASH MACHINE BRANCH LINE. |
| | SECTION 406.3. |
| | 82. SHT P-4.8 3RD LEVEL RISERS 11/12 AND |
| | FLOOR PLAN SHOWS RISER 12 TERMINATING AT |
| | THE 3RD LEVEL, BUT 3RD THRU 7TH FLOOR |
| | RISERS ARE SHOWN AS RISERS 11/12. PLEASE |
| | CORRELATE RISERS AND FLOOR PLAN. SECTION |
| | 106.1.1. |
| | 83. SHT P-4.8 2ND FLOOR RISER K/1, J/2, |
| | J/3, 3" REQUIRED FOR WASH MACHINE BRANCH |
| | LINE. SECTION 406.3. |
| | 84. SHT P-4.8 2ND FLOOR RISER 13/12 |
| | SHOWS 4" TO WASH MACHINE & 2" TO RISER |
| | 12. MINIMUM 3" TO WASH MACHINE BRANCH |
| | LINE AND THE SIZE OF DRAINAGE PIPING |
| | SHALL NOT BE REDUCED IN SIZE IN THE |
| | DIRECTION OF FLOW AS SHOWN IN THE 2" |
| | RISER LINE. SECTIONS 406.3 & 704.2. |
| | 85. SHT P-4.9 PH UPPER LEVEL RISER M/1 |
| | OVERFLOW FROM COOLING TOWER NOT |
| | APPORVED. OVERFLOW SHALL DRAIN TO THE |
| | STORM SYSTEM. MUNICIPAL CODE SECTION |
| | 90-125. |
| | 86. SHT P-4.9 PH UPPER LEVEL RISER H/3 |
| | 3" REQUIRED ON WASH MACHINE BRANCH LINE. |
| | SECTION 406.3. |
| | 87. SHT P-4.9 PH UPPER LEVEL RISER G/1 |
| | DOES NOT REFLECT THE FLOOR PLAN. (SHOWS |
| | W/M). 3" REQUIRED ON THE WASH MACHINE |
| | BRANCH LINE. SECTION 406.3. |
| | 88. SHT P-4.9 PH UPPER LEVEL, RISERS |
| | C/1, B/1, 3" REQUIRED ON THE WASH |
| | MACHINE BRANCH LINE. SECTION 406.3 |
| | 89. SHT P-4.9 PH LOWER LEVEL, TWO G/1 |
| | VTR'S SHOWN, AND TWO B/2 VTR'S SHOWN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | 90. SHT P-4.9 PH LOWER LEVEL, RISER D/3, |
| | AND 2" (4FU) FROM ABOVE TO BE THE |
| | MINIMUM OF 3" TO WASH MACHINES. BRANCH |
| | LINE OR STACK. SECTION 406.3. |
| | 91. SHT P-4.10 24TH LEVEL RISER F/3, 3" |
| | REQUIRED FOR WASH MACHINE BRANCH LINE |
| | AND RISER FROM ABOVE. SECTION 406.3. |
| | 92. SHT P-4.10 24TH LEVEL, INDICATE |
| | RISER NUMBER FOR SANT. RISER BY VENT |
| | E/1. SECTION 106.1.1. |
| | 93. SHT P-4.10 24TH LEVEL, RISERS D/1, |
| | C/3, M/2 MINIMUM 3" REQUIRED FOR WASH |
| | MACHINE BRANCH LINES. SECTION 406.3. |
| | 94. SHT P-4.10 9TH LEVEL, RISER L/1, |
| | L/2, L/3, DOES NOT REFLECT THE FLOOR |
| | PLAN ON THE 9TH LEVEL. PLEASE CORRELATE |
| | RISER AND FLOOR PLAN. SECTION 106.1.1. |
| | 95. SHT P-4.10 9TH LEVEL, THE SIZE OF |
| | THE DRAINAGE PIPING SHALL NOT BE REDUCED |
| | IN SIZE IN THE DIRECT OF THE FLOW. |
| | SECTION 704.2. |
| | 96. SHT P-4.10, 9TH LEVEL RISERS |
| | N/3,N/4,O/1 AND M/1,M2,N/1,N/2, MINIMUM |
| | 3" BRANCH LINE TO WASH MACHINE REQUIRED. |
| | SECTION 406.3. |
| | 97. SHT P-4.10 9TH LEVEL RISER |
| | M/1,M/2,N/1,N/2 DOES NOT REFLECT THE |
| | FLOOR PLAN DOWNSTREAM OF RISER M/2. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 106.1.1. |
| | 98. SHT P-4.10 8TH LEVEL RISERS H/1, |
| | H/5, H/2 OFF SET VENTS REQUIRED PER |
| | SECTIONS 915.2 AND 915.3. |
| | 99. SHT P-4.10 8TH LEVEL RISER H/2, |
| | WHERE A HORIZONTAL STACK OFFSET IS |
| | LOCATED MORE THAN FOUR BRANCH INTERVALS |
| | BELOW THE TOP OT THE STACK, A HORIZONTAL |
| | BRANCH SHALL NOT CONNECT WITHIN THE |
| | HOROZONTAL STACK OFFSET OR WITHIN 2FT |
| | ABOVE OR BELOW SUCH OFFSET. SECTION |
| | 711.2. |
| | 100. SHT P-4.10 8TH LEVEL, RISER H/1 |
| | MINIMUM 3" REQUIRED FOR WASH MACHINE |
| | BRANCH LINE. SECTION 406.3. |
| | 101. SHT P-4.11 7TH LEVEL, RISER H/2, |
| | MINIMUM 3" REQUIRED FOR WASH MACHINE |
| | BRANCH LINE. SECTION 406.3 |
| | 102. SHT P-4.11 3RD LEVEL RISERS |
| | M/1,M/2,N/1,N/2,N/3 AND N/4,O/1,O/2 ARE |
| | NOT SHOWN ON THE FLOOR PLANS FROM THE |
| | 7TH THRU 4TH FLOORS. PLEASE CORRELATE |
| | RISERS AND FLOOR PLANS. SECTION 106.1.1. |
| | 103. SHT P-4.11 2ND LEVEL RISERS H/1, |
| | F/2, G/1,G/2,G/3, A/1,A/2,A/3, B/1,B/2, |
| | E/1,E/2,D/3, C/2,C/3,D/1,D/2, MINIMUM 3" |
| | REQUIRED FOR WASH MACHINE BRANCH LINE. |
| | SECTION 406.3. |
| | 104. SHT P-4.11 2ND LEVEL RISERS |
| | L/1,L/2,L/3, ARE NOT SHOWN FROM THE 8TH |
| | FLOOR THRU 3RD FLOOR. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | 105. SHT P-4.11 3RD LEVEL, RISERS |
| | G/1,G/2,G/3, NOT SHOWN FROM 9TH FLOOR |
| | THRU 3RD FLOOR. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | 106. SHT P-4.113RD LEVEL, SHOW THE RISER |
| | DESIGNATION NUMBERS AT THE BOTTOM AND |
| | TOP OF EACH RISER SECTION. (SEE F/2, |
| | B/1,B/2) SECTION 106.1.1. |
| | 107. SHT P-4.12 MEZZANINE LEVEL, RISERS |
| | E/3,E/4, E/2,E/1,D/3, SHOW RISER |
| | DESIGNATION NUMBERS ON BOTH THE TOP AND |
| | BOTTOM OF EACH RISER SECTION. SECTION |
| | 106.1.1. |
| | 108. SHT P-4.12, MEZZANINE LEVEL, TWO |
| | LINES "4IN. SANT. FROM ABOVE COOLING |
| | TOWER OVERFLOW" SHALL BE CONNECTED TO |
| | STORM SYSTEM. MUNICIPAL CODE SECTION |
| | 90-125. |
| | 109. SHT P-4.13, 2 LINES "4IN SANT. FROM |
| | ABOVE COOLING TOWER OVERFLOW" SHALL BE |
| | CONNECTED TO THE STORM SYSTEM. MUNICIPAL |
| | CODE SECTION 90-125. |
| | 110. SHT P-4.13 SHOW ALL PIPE SIZES AND |
| | DFU'S FOR THE CIVIL LINES BETWEEN |
| | MANHOLES. RECHECK ALL DFU'S & PIPE SIZES |
| | AS WELL AS THE SLOPE OF PIPE. TABLES |
| | 704.1 AND 710.1(1). |
| | 111. (SECOND) SHT P-4.13 RECHECK PIPE |
| | SIZE FOR HORIZONTAL8400SF. |
| | 112. SECOND SHT P-4.13 CONTACT LYNN |
| | MASSON, ENVIRONMENTAL COMPLIANCE MGR. |
| | FOR SIZING OF GREASE INTERCEPTORS AND |
| | OIL/GAS/SAND INTECEPTORS. CONTACT HER AT |
| | (561) 822-2271, OR FAX (561) 822-2279, |
| | OR E-MAIL HER [email protected]. PLEASE |
| | SUBMIT DETERMINATION SHEETS WHEN |
| | RESUBMITTING FOR REVIEW BY CITY. WASTE |
| | ORDINANCE #3434. |
| | 113. SHT P-4.14 EACH RWL SHALL HAVE A |
| | RISER DESIGNATION NUMBER SO THE RISERS |
| | CAN BE TRACED FROM ROOF DRAINS TO |
| | BUILDING STORM DRAIN UNDERGROUND IE: |
| | RWL-1, RWL-2, RWL-3 ETC. SHOW RWL NUMBER |
| | ON EACH FLOOR THRU BUILDING. SECTION |
| | 106.1.1. |
| | 114. SHT P-4.14 SOME RWL RISERS, (7), DO |
| | NOT REFLECT THE FLOOR PLAN AT OFFSETS. |
| | PLEASE CORRELATE RISERS AND FLOOR PLANS. |
| | SECTION 106.1.1. |
| | 115. SHT P-4.14 BACKWASH DISCHARGE TO |
| | SANITARY SYSTEM NOT STORM. SECTION |
| | 90.203 MUNICIPAL CODE. |
| | 116. SHT P-4.14 ROOF AREA DRAIN DOES NOT |
| | INDICATE SQUARE FOOTAGE BEING DRAINED. |
| | PLEASE CLARIFY. SECTION 106.1.1 AND |
| | TABLE 1106.3. |
| | 117. SHT P-4.14 ONE RWL RISER INDICATES |
| | 2005SF ON THE RWL BUT 2805SF ON THE ROOF |
| | PLAN. PLEASE CORRELATE RISER AND ROOF |
| | DRAIN ON THE ROOF PLAN. SECTION 106.1.1. |
| | 118. SHT P-4.14 ONE RWL RISER CHANGES |
| | FROM 6" TO 4" DOWNSTREAM. THIS IS NOT |
| | ALLOWED PER SECTION 704.2. |
| | 119. SHT P-4.14 DRAIN FROM THE FIRE |
| | PROTECTION DRAIN RISER SHALL NOT BE |
| | DRAINED TO STORM. FIRE PROTECTION DRAIN |
| | SHALL CONNECT TO SANITARY. SECTION |
| | 90-203 MUNICIPAL CODE. |
| | 120. SHT P-4.14 ONE BUILDING STORM DRAIN |
| | DOES NOT REFLECT THE FLOOR PLAN FOR RWL |
| | RISER CONNECTIONS. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | 121. SHT P-4.15 GAS REQUIREMENTS: |
| | A. SUBMIT MANUFACTURE SPECIFICATION |
| | SHEETS FOR 5PSI TO .5PSI REGULATORS. IF |
| | REGULATORS ARE VENTED, SUBMIT AN |
| | ISOMETRIC PIPING DIAGRAM FOR THE VENTING |
| | AND INDICATE TERMINATION POINT. INDICATE |
| | MATERIAL FOR VENT PIPING. |
| | B. SHUT OFF VALVES ARE REQUIRED |
| | UPSTREAM OF EACH REGULATOR. SECTION |
| | 409.4 |
| | C. SUBMIT AN APPROVED TABLE FOR 5PSI UP |
| | TO 800 FEET TO VERIFY PIPE SIZE IN |
| | SYSTEM. SECTION 402.3(2) |
| | D. INDICATE LENGHTS OF PIPE FOR EACH |
| | CUT SECTION FROM THE METER TO THE FIRST |
| | RISER, AND FOR ALL CUT SECTIONS |
| | DOWNSTREAM OF THE 5PSI TO .5PSI |
| | REGULATOR. FBC-2004 FUEL GAS |
| | E. GALVANIZED PIPING IS NOT APPROVED |
| | FOR UNDERGROUND INSTALLATION. SECTION |
| | 404.8. |
| | F. SLEEVE FOR UNDERGROUND PIPING SHALL |
| | BE INSTALLED PER SECTION 404.11. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | 122. SHT P-5.01 WATER HEATER CLOSET |
| | DETAIL: THERMAL EXPANSION CONTROL IS |
| | REQUIRED PER SECTION 607.3.2. INDICATE |
| | METHOD. - WATER HEATER AND AIR |
| | CONDITIONER DISCONNECTS APPEAR TO BE IN |
| | FRONT OF THE WATER HEATER AND APPEAR TO |
| | BE IMPEDE THE ACCESS TO REPLACEMENT OF |
| | THE WATER HEATER REQUIRED IN SECTION |
| | 501.4. PLEASE CLARIFY. |
| | 123. SHT P-5.01 TYPICAL AIR CHAMBER |
| | DETAIL: AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE DETAIL. SECTION 604.9. |
| | 124. SHT P-5.01 SUBMIT MANUFACTURE |
| | SPECIFICATION SHEETS FOR THE DOMESTIC |
| | WATER PUMPS. PUMPS SHALL BE LISTED. |
| | SECTION 303.4. |
| | 125. SHT P-5.02 PUBLIC WATER HEATER |
| | DETAIL: INDICATE COMPLIANCE WITH SECTION |
| | 607.3.2 THERMAL EXPANSION CONTROL. |
| | 126. SHT P-5.02 TYPICAL CONDENSATE PIPE |
| | SUPPORT ON ROOF: ACCORDING TO TABLE |
| | 308.5 INDICATE MATERIAL FOR CONDENSATE |
| | PIPING. |
| | 127. SHT P-5.02 GENERAL PLUMBING NOTES: |
| | DOMESTIC WATER PIPING C(2), AIR CHAMBERS |
| | ARE NOT APPROVED. DELETE REFERENCE. |
| | SECTION 604.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REMOVE ALL OLD SHEETS AND RESUBMIT THE |
| | SET OF PLUMBING PLANS HIGHLIGHTED AND |
| | MARKED UP FROM THE FIRST REVIEW TO HELP |
| | SPEED UP SECOND REVIEW. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |