Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-30 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. FIRM LICENSE NUMBER IS
 REQUIRED IN THE TITLE BLOCK OF ALL
 DESIGN PROFESSIONALS. FAC 61G1-16.004(2)
 AND FS 481.219. FAC 61G15-23.002(2) AND
 FS 471.025.
 2. SHT A-0.02 APPLICABLE CODES SHALL
 READ FBC-2004.
 3. SHT A-2.01 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES REQUIRED FOR ALL
 COMMON AREAS ON THE GROUND FLOOR AND ON
 THE 9TH FLOOR. THIS SHALL INCLUDE THE
 RETAIL AREAS. SHOW THE SQUARE FOOTAGE
 AREA OF EACH COMMON SPACE AND RETAIL
 SPACE AND INDICATE COMPLIANCE WITH
 SECTIONS 1004.1.2 AND 403.1. SHOW THE
 OCCUPANCY FOR COMMON AREAS.
 4. SHT A-2.03 ROOFS OVER SECONDARY
 ENTRIES, SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW THE
 SQUARE FOOTAGE OF ROOF PLUS 1/2 AREA OF
 ALL VERTICAL WALLS, INCLUDING PARAPETS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE LOCATION OF
 SECONDARY ROOF DRAIN REQUIRED BY
 SECTIONS 1107.1 & 1107.2.
 5. SHT A-2.06 UNIT TYPE MISSING FROM
 MANY UNITS. PLEASE INDICATE UNIT TYPE
 FOR ALL UNITS. SECTION 106.1.1.
 6. SHT A-2.09 SEPARATE POOL PERMITS
 REQUIRED. PLANS SHALL BE REVIEWED AND
 APPROVED BY THE PALM BEACH COUNTY HEALTH
 DEPT. PRIOR TO SUBMITTING FOR REVIEW BY
 THE CITY WPB. 3 COPIES REQUIRED. SECTION
 102.2.1.
 7. SHT A-2.09 MORE INFORMATION REQUIED
 FOR THIS SHEET. ARE THERE SPA'S ON THIS
 SHEET. NO SPAS ARE IDENTIFIED. PLEASE
 CLARIFY. SECTION 106.1.1.
 8. SHTS A-2.09,A-2.10, & A-2.13,
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE FOR EACH AREA BEING DRAINED,
 ALONG WITH 1/2 THE AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ALONG WITH ANY
 ROOF AREA THAT DRAINS ONTO A ROOF AREA
 FROM ABOVE. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. THE SIZING OF SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF. PLEASE STATE
 ON PLANS CALCULATIONS FOR SCUPPERS WERE
 ACCORDING TO SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS AND/OR
 SCUPPERS.
 9. SHT A-2.13 DETAILS 1, 2, & 3.
 SEPARATE SECONDARY ROOF DRAINS ARE
 REQUIRED PER SECTIONS 11-7.1 & 1107.2.
 10. SHT A-2.13 DETAIL 4 TABLE 1616.3 IS
 FOR HIGH VELOCITY WIND ZONES ONLY.
 SIZING OF SCUPPERS SHALL BE PER SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7. (SEE
 COMMENT 8).
 11. SHT A-2.13 DETAIL 4 REFERENCES SHT
 A-10.03 DETAIL 7. DETAIL 7 IS A
 THRESHOLD DETAIL. PLEASE CLARIFY.
 SECTION 106.1.1.
 12. SHT A-3.01 TOILET ROOMS W-108A &
 W-108B SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22
 WITH ALL SUBSECTIONS.
 13. SHTS A-3.02BC & A-3.02CD TOILET
 ROOMS SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22
 WITH ALL SUBSECTIONS.
 14. SHTS A-3.02BC & A-3.02CD KITCHEN
 LOUNGE SINKS SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK.
 15. ALL DWELLING UNITS SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL REQUIREMENTS 1 THRU
 7. INDICATE SPECIFICATION "A" OR "B" FOR
 EACH UNIT/BATHROOM. SHOW THE CLEAR FLOOR
 SPACE FOR ALL USABLE FIXTURES IN THE
 BATHROOMS AND KITCHEN. SHOW THE BACKING
 REQUIRED BY REQUIREMENT 6 FOR THE W/C'S,
 TUBS & SHOWERS.
 16. SHTS A-3.09BC & A-3.09AD TOILET
 ROOMS SHALL BE ACCESSIBLE. SUBMIT
 DETAILS SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 17. SHTS A-3.09AB & A-3.09DA POOL PUMP
 ROOM SHALL COMPLY WITH SECTIONS
 424.1.5.3 THRU 424.1.5.9. SUBMIT
 DETAILS. INDICATE WHERE CHEMICALS ARE TO
 BE STORED AND IN WHAT QUANTITY. SECTION
 424.1.5.8.
 18. SHTS A-4.01 & A-4.02 POWDER ROOM AT
 LOWER LEVELS SHALL COMPLY WITH
 REQUIREMENTS 6 AND 7. SEE PAGE 7.33OF
 THE FHA-98 DESIGN MANUAL. SHOW CLEAR
 FLOOR SPACE FOR THE LAV AND W/C. LAV TO
 BE CENTERED ON THE 48" LENGTH IF
 PARALLEL APPROACH, OR THE CABINET BASE
 SHALL BE REMOVABLE AND THE LAV SHALL BE
 MINIMUM 15" OFF THE WALL. THE W/C SHALL
 BE 18" OFF THE WALL TO THE CENTER TO THE
 FIXTURE AND SHALL HAVE A MINIMUM OPENING
 OF 33". INDICATE ON THE FLOOR PLAN. SEE
 PAGES 7.43, 7.44, 7.45 & 7.46. THE
 KITCHEN SHALL SHOW THE CLEAR FLOOR SPACE
 FOR EACH APPLIANCE AND A 5' TURNING
 AREA. SEE PAGES 7.3 THRU 7.11.
 19. SHTS A-4.03 THRU A-4.14 CLEAR FLOOR
 SPACE FOR ALL REQUIRED FIXTURES SHALL BE
 SHOWN ON THE ENLARGED PLANS. FOR W/C'S
 SEE PAGE 7.43, ONE OF THREE SHALL BE
 PROVIDED. FOR LAVS SEE PAGES 7.47 &
 7.48. LAVS SHALL BE 2'10" MAXIMUM OFF
 THE FLOOR. SEE PAGE 7.52. CLEAR FLOOR
 SPACE SHALL BE PARALLEL TO THE SHOWER
 AND FLUSH WITH THE CONTROL WALL. SEE
 PAGE 7.56. FOR KITCHENS SEE REQUIREMENT
 7.
 20. SHTS A-4.03 THRU A-4.14 MINIMUM
 OPENING SIZE FOR W/C'S IS 33" AND THE
 FIXTURE SHALL BE 18" OFF THE WALL AND
 18" OFF ONE FIXTURE AND MINIMUM 15" OFF
 THE OTHER FIXTURE WHEN BETWEEN TWO
 FIXTURES. SEE PAGES 7.43 THRU 7.46.
 BIDETS SHALL NOT BE IN THE CLEAR FLOOR
 SPACE OF THE W/C PER INTERPRETATION OF
 THE ARCHITECTURAL BOARD FOR HUD.
 21. SHT A-4.12A PH LOFT 03 ROOF LEVEL
 SHOWS A POOL. MORE INFORMATION IS
 REQUIRED FOR POOL. INDICATE TYPE OF POOL
 AND USE OF POOL. INDICATE IF THERE IS
 POOL EQUIPMENT SUCH AS A PUMP, FILTER,
 ETC. SECTION 106.1.1.
 22. SHT A-8.03 FINISH SCHEDULE. ROOMS
 W-108A & W-108B, INDICATE HOW DRYWALL/PT
 IN TOILET ROOMS COMPLY WITH THE
 REQUIREMENT OF SECTION 1210.2 WALLS.
 WALLS WITHIN 2' OF URINALS AND W/C'S
 SHALL BE NONABSORBENT.
 23. SHT P-1.01 COL LINE R.7 SOUTH OF COL
 LINE K SHOWS "4 INCH RWL STUBBED UP 36
 INCHES ABOVE FINISHED FLOOR FLR BACKWASH
 DISCHARGE." PLEASE INDICATE WHAT IS
 DISCHARGING INTO STUB UP. ONLY STORM
 WATER SHALL DISCHARGE INTO STORM LINES
 PER MUNICIPAL CODE SECTION 90.203.
 24. SHT P-1.01 CODED NOTES (1), 3"
 DISCHARGE FROM FIRE PROTECTION DRAIN
 RISER TO SANITARY SYSTEM NOT THE STORM
 SYSTEM PER MUNICIPAL CODE SECTION
 90.203.
 25. SHT P-1.01 BACKFLOW PREVENTORS AND
 GAS METER DO NOT REFLECT THE LOCATION
 SHOWN ON THE CIVIL PLANS. THEY APPEAR TO
 BE ON THE SIDEWALK. ALSO THE CIVIL
 SHEETS INDICATE 3 BACKFLOWS, (1 FOR
 IRRIGATION). PLEASE CORRELATE THE
 PLUMBING SHEETS WITH THE CIVIL SHEETS.
 SECTION 106.1.1.
 26. SHT P-1.01 OFFICE MANAGER PLUMBING
 FLOOR PLAN TO SHOW REVENT TO REFLECT
 RISER DIAGRAM. SECTION 106.1.1.
 27. SHT P-1.01 SECTION 404.11 FUEL GAS
 PIPING UNDERGROUND BENEATH BUILDINGS.
 PLEASE INDICATE IF THE GAS PIPING IS
 UNDER THE BUILDING OR UNDER A SLAB
 OUTSIDE THE BUILDING. SLEEVE SHALL BE
 SEALED ON BOTH ENDS TO PREVENT OF WATER
 AND INSECTS. SLEEVE SHALL BE VENTED.
 28. SHT P-1.01 OFFICE MANAGER WATER
 DISTRIBUTION RISER DIAGRAM, AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM RISER.
 SECTION 604.9.
 29. SHT P-1.01 PLEASE SUBMIT THE
 INFORMATION FOR THIS SHEET DRAWN TO A
 MINIMUM OF 1/8" SCALE AS REQUIRED IN
 SECTION 106.1.3.
 30. SHT P-1.02 SALON, KITCHEN AND REST
 ROOMS WATER DISTRIBUTION RISER DIAGRAMS,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISER DIAGRAMS. WATER HAMMER
 ARRESTOR IS REQUIRED AT THE REFRIGERATOR
 PER SECTION 604.9. - THERMAL EXPANSION
 CONTROL IS REQUIRED AT THE WATER HEATER
 PER SECTION 607.3.2. SHOW ON RISER
 DIAGRAM.
 31. SHT P-1.02 4" GAS LINES IN BLOCK
 WALL NOT APPROVED. SECTION 1925.3.5(1) -
 THIS IS SHOWN AS 6" GAS LINES ON THE
 PLUMBING SHEETS. PLEASE CORRELATETHE
 FLOOR PLAN WITH THE GAS RISER DIAGRAM.
 32. SHTS P-2.04AB & P-2.04BC HAVE NOT
 BEEN SUBMITTED. SECTION 106.1.1. (SEE
 PROJECT DRAWING INDEX)
 33. SHT P-2.04CD 6" RWL IS SHOWN AS 4"
 RWL ON THE FLOOR ABOVE AND THE FLOOR
 BELOW. PLEASE CLARIFY. SECTION 106.1.1.
 34. SHT P-2.05AB PIPING TO W/C'S AND
 LAVS DO NOT PIPE TO THE FIXTURES. PLEASE
 CLARIFY. SECTION 106.1.1.
 35. SHT P-2.05DA INDICATE THE LOCATION
 OF RISER J/3. SECTION 106.1.1.
 36. SHTS P-2.07AB & P-2.07DA, INDICATE
 UNIT TYPES. SECTION 106.1.1.
 37. SHTS P-2.07AB, P-2.07BC, P-2.07CD,
 P-2.07DA INDICATE 3"(40SF) "DOWN" WHEN
 THEY APPEAR TO BE GOING "UP" TO THE 7TH
 FLOOR. PLEASE CLARIFY. SECTION 106.1.1.
 38. SHTP-2.08AB SHOWS RISER K3 VTR IN
 TWO LOCATIONS. THIS DOES NOT REFLECT THE
 RISER DIAGRAM. PLEASE CLARIFY. SECTION
 106.1.1.
 37. SHT P2.08AB COOLING TOWER
 DRAIN/OVERFLOW DETAILS SHOW THE DRAIN
 AND OVERFLOW DRAINING TO THE SANITARY.
 OVERFLOW SHALL DISCHARGE SEPARATELY TO
 THE STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 38. SHT P-2.08AB SHOW THE LOCATION OF
 RISERS J/2 & J/1. SECTION 106.1.1.
 39. SHT P-2.08DA COOLING TOWER
 DRAIN/OVERFLOW DETAILS SHOW THE DRAIN
 AND OVERFLOW DRAINING INTO THE SANITARY.
 THE OVERFLOW SHALL DISCHARGE SEPARATELY
 INTO THE STORM SYSTEM. MUNICIPAL CODE
 SECTION 90-125.
 40. SHTS P-2.09AD, P-2.09BC, P-2.09CD,
 P-2.09DA SHOW THE LOCATION OF ALL
 SECONDARY DRAINS. SUBMIT THE
 CALCULATIONS FOR ALL PRIMARY & SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE
 AREA DRAINING INTO EACH DRAIN ALONG WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, MANSARDS, & BUILDING WALLS
 CONTRIBUTING TO THE AREA BEING DRAINED
 IN CALCULATIONS.
 41. SHTS P-2.09AB, P-2.09DA 4" RWL
 STUBBED UP FOR BACKWASH DISCHARGE SHALL
 DRAIN TO SANITARY SYSTEM. MUNICIPAL CODE
 SECTION 90-203.
 42. SHTS P-2.09AB, P-2.09DA SHOWS PD
 50SF, BUT DISCHARGE LINE SHOWS 150SF.
 PLEASE CLARIFY. SECTION 106.1.1.
 43. SHTS P-2.10BC, P-2.10CD RISER
 DESIGNATIONS L/1, L/2, L/3 SUPERIMPOSED
 OVER "FIRE ALARM ROOMS" AND HARD TO
 READ. PLEASE FIX TYPE-O. SECTION
 106.1.1.
 44. SHTS P-2.10BC, P-2.10CD, P-2.11BC,
 P-2.11CD, P-2.12BC, P-2.12CD INDICATE
 UNIT TYPES ON FLOOR PLAN. SECTION
 106.1.1.
 45. SHTS P-2.13BC, P-2.13CD SANITARY
 RISER FOR W/M IN PH-LOFT 05 IS NOT SHOWN
 ON THE FLOOR BELOW. INDICATE FIXTURE
 TYPE ON FLOOR PLAN. SECTION 106.1.1.
 46. SHTS P-2.13BC, P-2.13CD SHOWS 2
 RWL'S BEHIND THE POWDER ROOM W/C IN
 PH-LOFT 05 NOT SHOWN ON THE FLOOR ABOVE.
 PLEASE CLARIFY. SECTION 106.1.1.
 47. SHTS P-2.13BC, P-2.13CD SHOW RISER
 NUMBERS FOR KITCHEN SINK, POWDER ROOM,
 AND BATHROOM RISERS IN PH-LOFT 04.
 SECTION 106.1.1.
 48. SHTS P-2.14BC, P-02.14CD4" RWL &
 OFFSET NOT SHOWN ON ROOF. PLEASE
 CLARIFY. SECTION 106.1.1.
 49. SHTS P-2.14BC, P-02.14CD 3" REQUIRED
 TO WASH MACHINE FOR PH-LOFTS 04 & 07.
 SECTION 406.3.
 50. SHTS P-2.15BC, P-2.15CD SEPARATE
 SYSTEMS FOR DRAIN & OVERFLOW FROM THE
 COOLING TOWER. DRAIN TO SANITARY AND
 OVERFLOW TO STORM. MUNICIPAL CODE
 SECTION 90-203.
 51. SHTS P-2.15BC, P-2.15CD 4" RWL
 STUBBED UP TO 36" FINISHED FLOOR FOR
 BACKWASH DISCHARGE SHALL DRAIN TO
 SANITARY. MUNICIPAL CODE SECTION 90-203.
 52. SHTS P-2.15BC, P-2.15CD COOLING
 TOWER DRAIN/OVERFLOW DETAIL, DRAIN TO
 SANT. & OVERFLOW TO STORM. SECTION
 90-203. - INDICATE MATERIAL FOR SYSTEM &
 SUPPORTS TO BE SPACED PER TABLE 308.5.
 53. SHT P-2.15CD SHOWS 6" RD(3490SF),
 BUT NO ROOF DRAIN SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1.
 54. SHTS P-3.01 THRU P-3.14 NOTE:
 "DISCHARGE DRYER CONDENSATE INTO W/M
 WASTE TRAP". SUBMIT A DETAIL SHOWING
 CONNECTIONS TO THE DRYER & WASTE TRAP,
 PIPE SIZE, PIPING MATERIAL, AND MANUF.
 SPECIFICATION SHEETS ALONG WITH
 INSTALLATION INSTRUCTIONS. SECTION
 106.1.1.
 55. SHT P-3.03 UNIT TYPE "1C' STATES
 "SEE DWG. P-3.03 FOR CONTINUATION RISER
 N/1". CONTINUATION NOT FOUND ON THIS
 SHEET. PLEASE CLARIFY. SECTION 106.1.1.
 56. SHT P-3.04 UNIT TYPE "2G" STATES
 "SEE DWG. P-3.02 FOR CONTINUATION",
 CONTINUATION NOT FOUND ON P-3.02. PLEASE
 CLARIFY. SECTION 106.1.1.
 57. SHT P-3.05 UNIT TYPES "2B" & "2B-1"
 SHOW TWO DIFFERENT RISERS FOR RISERS
 H/1, H/2, & G/3. PLEASE CLARIFY. SECTION
 106.1.1.
 58. SHT P-3.05 WATER RISER DIAGRAM FOR
 UNIT "2B-1", AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM RISER. SECTION
 604.9. SHOW COMPLIANCE WITH SECTION
 607.3.2 FOR THERMAL EXPANSION CONTROL.
 59. SHT P-3, (BETWEEN P-3.06 & P-3.08),
 WATER RISER DIAGRAM, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM RISER DIAGRAM.
 SECTION 604.9. - SHOW COMPLIANCE WITH
 SECTION 607.3.2 THERMAL EXPANSION
 CONTROL.
 60. SHT P3.08 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED, DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 6-7.3.2 THERMAL
 EXPANSION CONTROL.
 61. SHT P-3.10 PH-LOTS 02, SHOW PIPING
 ON FLOOR PLANS. SECTION 106.1.1. - WATER
 RISER DIAGRAM, AIR CHAMBERS ARE NOT
 APPROVED, DELETE FROM RISER DIAGRAM. -
 SHOW COMPLIANCE WITH SECTION 607.3.2
 THERMAL EXPANSION CONTROL.
 62. SHT P-3.12 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 607.3.2 THERMAL
 EXPANSION CONTROL.
 63. SHT P-3.14 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 607.3.2. THERMAL
 EXPANSION CONTROL.
 64. SHT P-4.0 CONDENSATE RISER DIAGRAM,
 VENT SHALL NOT TERMINATE INSIDE A WALL,
 OR IN A PLENUM. PLEASE INDICATE WHERE
 THE VENT WILL TERMINATE TO COMPLY WITH
 THIS INFORMATION. SUBMIT A DETAIL
 SECTION 106.1.1.
 65. SHT P-4.0 WATER RISER DIAGRAMS, RPZV
 BACKFLOWS ARE REQUIRED ON THE WATER
 SUPPLYS FOR THE POOL EQUIPMENT ROOM,
 (UNLESS AN AIR GAP IS SHOWN ON WATER
 MAKEUP), AND AT SUPPLY FOR THE
 IRRIGATION. BACKFLOW PREVENTION IS ALSO
 REQUIRED FOR THE SUPPLY OF THE TRASH
 CHUTE WASHDOWN. PLEASE INDICATE METHOD
 OF BACKFLOW PREVENTION. SECTION 608.
 66. SHTS P-4.1, P-4.2, P-4.3, P-4.5
 WATER RISER DIAGRAMS, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM RISER
 DIAGRAMS. SECTION 604.9. SHOW COMPLIANCE
 WITH SECTION 607.3.2 THERMAL EXPANSION
 CONTROL.
 67. SHTS P-4.5 THRU P-4.12 FIXTURE UNITS
 FOR SANITARY RISER DIAGRAMS SHALL BE
 RECHECKED. PER TABLE 709.1, A BATHROOM
 GROUP IS 5FU AS DEFINED IN SECTION 202,
 BUT EXTRA FIXTURES SHALL BE ADDED PER FU
 VALUE OF EACH FIXTURE. FLOOR DRAINS ARE
 2FU WITH A 2" TRAP, BUT LARGER TRAPS
 SHALL BE SIZED FOR FIXTURE UNITS PER
 TABLE 709.2. A POWDER ROOM IS 4FU. SINKS
 ARE 2FU AND LAVS ARE 1FU BUT LAVS ARE
 ONLY LOCATED IN POWDER ROOMS OR
 BATHROOMS.
 68. SHTS P-4.5 THRU P-4.12 ALL SANITARY
 RISERS, INDICATE WHERE OR WHAT SHEET THE
 CONTINUATIONS FOR EACH RISER UPPER OR
 LOWER SECTIONS ARE LOCATED, OR SUBMIT
 RISER DIAGRAMS THAT ARE CONTINUOUS FROM
 THE BUILDING DRAIN THRU THE VENT THRU
 ROOF. (MANY HOURS PLAN REVIEW WERE SPENT
 TRYING TO TRACK THE RISER DIAGRAMS AS
 SUBMITTED). SHOW ALL OFFSET VENTS PER
 SECTION 915.2 & 915.3, SHOW ALL VENT
 CONNECTIONS PER SECTION 903.4 FOR ALL
 STACKS THAT REQUIRE A VENT STACK PER
 SECTION 903.2.
 69. SHT P-4.6 RISER E/2 INDICATES NO
 FIXTURES ABOVE THE 23RD FLOOR, BUT THIS
 DOES NOT REFLECT THE FLOOR PLAN FOR THE
 24TH FLOOR AS A KITCHEN SINK AND A
 POWDER ROOM ARE SHOWN. PLEASE CORRELATE
 THE RISER DIAGRAM AND THE FLOOR PLAN.
 SECTION 106.1.1.
 70. SHT P-4.6 RISER G/1 IDENTIFY ALL
 FIXTURES. SECTION 106.1.1.
 71. SHT P-4.6 RISER H/1 3" BRANCH LINE
 REQUIRED TO WASH MACHINE. SECTION 606.3.
 - OFFSET VENTS REQUIRED PER SECTIONS
 915.2 AND 915.3.
 72. SHT P-4.6 RISER H/2 INDICATE
 FIXTURES FOR 3RD, 4TH, & 6TH FLOORS.
 SECTION 106.1.1.
 73. SHT P-4.6 RISER G/3 5TH & 7TH FLOORS
 DO NOT REFLECT THE FLOOR PLAN. DOES NOT
 SHOW THE OTHER BATHROOM. NOT CHANGED ON
 FLOOR PLAN. SECTION 106.1.1.
 74. SHT P-4.7 RISER H/5 INDICATE ON
 RISER WHERE 8TH FLOOR PIPING CAN BE
 LOCATED. - 3RD THRU 7TH FLOORS DO NOT
 REFLECT THE FLOOR PLAN. NO FIXTURES
 SHOWN. SECTION 106.1.1.
 75. SHT P-4.7 RISER N/3 DOES NOT REFLECT
 THE 24TH FLOOR FIXTURE UNITS. (+2)
 SECTION 106.1.1 AND TABLE 710.1(2).
 76. SHT P-4.8 RISER N/3 3" REQUIRED ON
 ALL WASH MACHINE BRANCH LINES. SECTION
 406.3.
 77. SHT P-4.8 RISERS J/1, J/2, J/3, K/1,
 K/2, 11, 12, 13, & 14 7TH FLOOR, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINES.
 SECTION 406.3.
 78. SHT P-4.8 4TH LEVEL RISERS K/2, J/3,
 11/12, 14 DO NOT REFLECT THE FLOOR PLAN.
 SECTION 106.1.1.
 79. SHT P-4.8 4TH LEVEL TWO J/2 SANT.
 RISERS SHOWN. PLEASE CLARIFY. SECTION
 106.2.1.
 80. SHT P-4.8 4TH LEVEL RISER J/3 NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY
 SECTION 106.1.1.
 81. SHT P-4.8 4TH LEVEL RISER 14, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 82. SHT P-4.8 3RD LEVEL RISERS 11/12 AND
 FLOOR PLAN SHOWS RISER 12 TERMINATING AT
 THE 3RD LEVEL, BUT 3RD THRU 7TH FLOOR
 RISERS ARE SHOWN AS RISERS 11/12. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 106.1.1.
 83. SHT P-4.8 2ND FLOOR RISER K/1, J/2,
 J/3, 3" REQUIRED FOR WASH MACHINE BRANCH
 LINE. SECTION 406.3.
 84. SHT P-4.8 2ND FLOOR RISER 13/12
 SHOWS 4" TO WASH MACHINE & 2" TO RISER
 12. MINIMUM 3" TO WASH MACHINE BRANCH
 LINE AND THE SIZE OF DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE
 DIRECTION OF FLOW AS SHOWN IN THE 2"
 RISER LINE. SECTIONS 406.3 & 704.2.
 85. SHT P-4.9 PH UPPER LEVEL RISER M/1
 OVERFLOW FROM COOLING TOWER NOT
 APPORVED. OVERFLOW SHALL DRAIN TO THE
 STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 86. SHT P-4.9 PH UPPER LEVEL RISER H/3
 3" REQUIRED ON WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 87. SHT P-4.9 PH UPPER LEVEL RISER G/1
 DOES NOT REFLECT THE FLOOR PLAN. (SHOWS
 W/M). 3" REQUIRED ON THE WASH MACHINE
 BRANCH LINE. SECTION 406.3.
 88. SHT P-4.9 PH UPPER LEVEL, RISERS
 C/1, B/1, 3" REQUIRED ON THE WASH
 MACHINE BRANCH LINE. SECTION 406.3
 89. SHT P-4.9 PH LOWER LEVEL, TWO G/1
 VTR'S SHOWN, AND TWO B/2 VTR'S SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
 90. SHT P-4.9 PH LOWER LEVEL, RISER D/3,
 AND 2" (4FU) FROM ABOVE TO BE THE
 MINIMUM OF 3" TO WASH MACHINES. BRANCH
 LINE OR STACK. SECTION 406.3.
 91. SHT P-4.10 24TH LEVEL RISER F/3, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE
 AND RISER FROM ABOVE. SECTION 406.3.
 92. SHT P-4.10 24TH LEVEL, INDICATE
 RISER NUMBER FOR SANT. RISER BY VENT
 E/1. SECTION 106.1.1.
 93. SHT P-4.10 24TH LEVEL, RISERS D/1,
 C/3, M/2 MINIMUM 3" REQUIRED FOR WASH
 MACHINE BRANCH LINES. SECTION 406.3.
 94. SHT P-4.10 9TH LEVEL, RISER L/1,
 L/2, L/3, DOES NOT REFLECT THE FLOOR
 PLAN ON THE 9TH LEVEL. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1.
 95. SHT P-4.10 9TH LEVEL, THE SIZE OF
 THE DRAINAGE PIPING SHALL NOT BE REDUCED
 IN SIZE IN THE DIRECT OF THE FLOW.
 SECTION 704.2.
 96. SHT P-4.10, 9TH LEVEL RISERS
 N/3,N/4,O/1 AND M/1,M2,N/1,N/2, MINIMUM
 3" BRANCH LINE TO WASH MACHINE REQUIRED.
 SECTION 406.3.
 97. SHT P-4.10 9TH LEVEL RISER
 M/1,M/2,N/1,N/2 DOES NOT REFLECT THE
 FLOOR PLAN DOWNSTREAM OF RISER M/2.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
 98. SHT P-4.10 8TH LEVEL RISERS H/1,
 H/5, H/2 OFF SET VENTS REQUIRED PER
 SECTIONS 915.2 AND 915.3.
 99. SHT P-4.10 8TH LEVEL RISER H/2,
 WHERE A HORIZONTAL STACK OFFSET IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS
 BELOW THE TOP OT THE STACK, A HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HOROZONTAL STACK OFFSET OR WITHIN 2FT
 ABOVE OR BELOW SUCH OFFSET. SECTION
 711.2.
 100. SHT P-4.10 8TH LEVEL, RISER H/1
 MINIMUM 3" REQUIRED FOR WASH MACHINE
 BRANCH LINE. SECTION 406.3.
 101. SHT P-4.11 7TH LEVEL, RISER H/2,
 MINIMUM 3" REQUIRED FOR WASH MACHINE
 BRANCH LINE. SECTION 406.3
 102. SHT P-4.11 3RD LEVEL RISERS
 M/1,M/2,N/1,N/2,N/3 AND N/4,O/1,O/2 ARE
 NOT SHOWN ON THE FLOOR PLANS FROM THE
 7TH THRU 4TH FLOORS. PLEASE CORRELATE
 RISERS AND FLOOR PLANS. SECTION 106.1.1.
 103. SHT P-4.11 2ND LEVEL RISERS H/1,
 F/2, G/1,G/2,G/3, A/1,A/2,A/3, B/1,B/2,
 E/1,E/2,D/3, C/2,C/3,D/1,D/2, MINIMUM 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 104. SHT P-4.11 2ND LEVEL RISERS
 L/1,L/2,L/3, ARE NOT SHOWN FROM THE 8TH
 FLOOR THRU 3RD FLOOR. PLEASE CLARIFY.
 SECTION 106.1.1.
 105. SHT P-4.11 3RD LEVEL, RISERS
 G/1,G/2,G/3, NOT SHOWN FROM 9TH FLOOR
 THRU 3RD FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
 106. SHT P-4.113RD LEVEL, SHOW THE RISER
 DESIGNATION NUMBERS AT THE BOTTOM AND
 TOP OF EACH RISER SECTION. (SEE F/2,
 B/1,B/2) SECTION 106.1.1.
 107. SHT P-4.12 MEZZANINE LEVEL, RISERS
 E/3,E/4, E/2,E/1,D/3, SHOW RISER
 DESIGNATION NUMBERS ON BOTH THE TOP AND
 BOTTOM OF EACH RISER SECTION. SECTION
 106.1.1.
 108. SHT P-4.12, MEZZANINE LEVEL, TWO
 LINES "4IN. SANT. FROM ABOVE COOLING
 TOWER OVERFLOW" SHALL BE CONNECTED TO
 STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 109. SHT P-4.13, 2 LINES "4IN SANT. FROM
 ABOVE COOLING TOWER OVERFLOW" SHALL BE
 CONNECTED TO THE STORM SYSTEM. MUNICIPAL
 CODE SECTION 90-125.
 110. SHT P-4.13 SHOW ALL PIPE SIZES AND
 DFU'S FOR THE CIVIL LINES BETWEEN
 MANHOLES. RECHECK ALL DFU'S & PIPE SIZES
 AS WELL AS THE SLOPE OF PIPE. TABLES
 704.1 AND 710.1(1).
 111. (SECOND) SHT P-4.13 RECHECK PIPE
 SIZE FOR HORIZONTAL8400SF.
 112. SECOND SHT P-4.13 CONTACT LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MGR.
 FOR SIZING OF GREASE INTERCEPTORS AND
 OIL/GAS/SAND INTECEPTORS. CONTACT HER AT
 (561) 822-2271, OR FAX (561) 822-2279,
 OR E-MAIL HER [email protected]. PLEASE
 SUBMIT DETERMINATION SHEETS WHEN
 RESUBMITTING FOR REVIEW BY CITY. WASTE
 ORDINANCE #3434.
 113. SHT P-4.14 EACH RWL SHALL HAVE A
 RISER DESIGNATION NUMBER SO THE RISERS
 CAN BE TRACED FROM ROOF DRAINS TO
 BUILDING STORM DRAIN UNDERGROUND IE:
 RWL-1, RWL-2, RWL-3 ETC. SHOW RWL NUMBER
 ON EACH FLOOR THRU BUILDING. SECTION
 106.1.1.
 114. SHT P-4.14 SOME RWL RISERS, (7), DO
 NOT REFLECT THE FLOOR PLAN AT OFFSETS.
 PLEASE CORRELATE RISERS AND FLOOR PLANS.
 SECTION 106.1.1.
 115. SHT P-4.14 BACKWASH DISCHARGE TO
 SANITARY SYSTEM NOT STORM. SECTION
 90.203 MUNICIPAL CODE.
 116. SHT P-4.14 ROOF AREA DRAIN DOES NOT
 INDICATE SQUARE FOOTAGE BEING DRAINED.
 PLEASE CLARIFY. SECTION 106.1.1 AND
 TABLE 1106.3.
 117. SHT P-4.14 ONE RWL RISER INDICATES
 2005SF ON THE RWL BUT 2805SF ON THE ROOF
 PLAN. PLEASE CORRELATE RISER AND ROOF
 DRAIN ON THE ROOF PLAN. SECTION 106.1.1.
 118. SHT P-4.14 ONE RWL RISER CHANGES
 FROM 6" TO 4" DOWNSTREAM. THIS IS NOT
 ALLOWED PER SECTION 704.2.
 119. SHT P-4.14 DRAIN FROM THE FIRE
 PROTECTION DRAIN RISER SHALL NOT BE
 DRAINED TO STORM. FIRE PROTECTION DRAIN
 SHALL CONNECT TO SANITARY. SECTION
 90-203 MUNICIPAL CODE.
 120. SHT P-4.14 ONE BUILDING STORM DRAIN
 DOES NOT REFLECT THE FLOOR PLAN FOR RWL
 RISER CONNECTIONS. PLEASE CORRELATE.
 SECTION 106.1.1.
 121. SHT P-4.15 GAS REQUIREMENTS:
 A. SUBMIT MANUFACTURE SPECIFICATION
 SHEETS FOR 5PSI TO .5PSI REGULATORS. IF
 REGULATORS ARE VENTED, SUBMIT AN
 ISOMETRIC PIPING DIAGRAM FOR THE VENTING
 AND INDICATE TERMINATION POINT. INDICATE
 MATERIAL FOR VENT PIPING.
 B. SHUT OFF VALVES ARE REQUIRED
 UPSTREAM OF EACH REGULATOR. SECTION
 409.4
 C. SUBMIT AN APPROVED TABLE FOR 5PSI UP
 TO 800 FEET TO VERIFY PIPE SIZE IN
 SYSTEM. SECTION 402.3(2)
 D. INDICATE LENGHTS OF PIPE FOR EACH
 CUT SECTION FROM THE METER TO THE FIRST
 RISER, AND FOR ALL CUT SECTIONS
 DOWNSTREAM OF THE 5PSI TO .5PSI
 REGULATOR. FBC-2004 FUEL GAS
 E. GALVANIZED PIPING IS NOT APPROVED
 FOR UNDERGROUND INSTALLATION. SECTION
 404.8.
 F. SLEEVE FOR UNDERGROUND PIPING SHALL
 BE INSTALLED PER SECTION 404.11.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 122. SHT P-5.01 WATER HEATER CLOSET
 DETAIL: THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD. - WATER HEATER AND AIR
 CONDITIONER DISCONNECTS APPEAR TO BE IN
 FRONT OF THE WATER HEATER AND APPEAR TO
 BE IMPEDE THE ACCESS TO REPLACEMENT OF
 THE WATER HEATER REQUIRED IN SECTION
 501.4. PLEASE CLARIFY.
 123. SHT P-5.01 TYPICAL AIR CHAMBER
 DETAIL: AIR CHAMBERS ARE NOT APPROVED.
 DELETE DETAIL. SECTION 604.9.
 124. SHT P-5.01 SUBMIT MANUFACTURE
 SPECIFICATION SHEETS FOR THE DOMESTIC
 WATER PUMPS. PUMPS SHALL BE LISTED.
 SECTION 303.4.
 125. SHT P-5.02 PUBLIC WATER HEATER
 DETAIL: INDICATE COMPLIANCE WITH SECTION
 607.3.2 THERMAL EXPANSION CONTROL.
 126. SHT P-5.02 TYPICAL CONDENSATE PIPE
 SUPPORT ON ROOF: ACCORDING TO TABLE
 308.5 INDICATE MATERIAL FOR CONDENSATE
 PIPING.
 127. SHT P-5.02 GENERAL PLUMBING NOTES:
 DOMESTIC WATER PIPING C(2), AIR CHAMBERS
 ARE NOT APPROVED. DELETE REFERENCE.
 SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL OLD SHEETS AND RESUBMIT THE
 SET OF PLUMBING PLANS HIGHLIGHTED AND
 MARKED UP FROM THE FIRST REVIEW TO HELP
 SPEED UP SECOND REVIEW.
  
 REVIEW BY KEN STEVENS