| 2006-05-30 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET M-2.01-AB, PLEASE PROVIDE |
| | THE DISTANCE FROM PROPERTY LINES, |
| | STREETS, ALLEYS, PARKING LOTS AND |
| | LOADING DOCKS FOR THE FRESH AIR INTAKES |
| | INTERIOR AND EXTERIOR OF THE BUILDING. |
| | SHOW COMPLIANCE WITH 2004 FMC 401.5 & |
| | 401.5.1. |
| | |
| | 2.PLAN SHEET M-2.01-AB, 12 X 12 O.A. |
| | INTAKE AT THE PARKING MAIN ENTRANCE, |
| | SHOW COMPLIANCE WITH FMC 401.5, 401.5.1. |
| | |
| | 3.PLAN SHEET M-2.01-AB, PLEASE CLARIFY |
| | THE FOLLOWING; R1-SSF-1 IS A SUPPLY FAN |
| | FOR THE PURPOSE OF SMOKE CONTROL TO THE |
| | RETAIL SPACE 1 & COORIDOR?ON PLAN |
| | SHEET THE SYMBOL FOR RETURN DUCT IS |
| | INDICATED.PLEASE CLARIFY ALSO FIRE |
| | DAMPERS INDICATED INSTEAD FO FIRE/SMOKE |
| | DAMPERS. |
| | |
| | 4.R1-SSF-1 IS ALSO DUCTED TO UNIT 3-3 |
| | (WHICH IS NOT INDICATED ON THE EQUIPMENT |
| | SCHEDULE),PLEASE CLARIFY WHAT THIS |
| | EQUIPMENT FUCTION IS, (AHU, RTU, ETC.)? |
| | |
| | 5.PLAN SHEET M-2.01-AB, PLEASE |
| | INDICATE THE ELEVATIONS & DISTANCES FROM |
| | PROPERTY LINES ADJACENT BUILDING ETC. |
| | FOR THE EXHAUST TERMIANTIONS.SHOW |
| | COMPLIANCE WITH 2004 FMC 401.5.1, |
| | 401.5.2, & 501.2. |
| | |
| | 6.PLAN SHEET M-2.01-AB, PLEASE CLARFY |
| | THE TOILET & SMOKE EXHAUST TO RETAIL 2 |
| | IN RELATION TO THE DOUBLE DOOR, |
| | SIDEWALK, AND PROPERTY LINES. |
| | |
| | 7.PLAN SHEET M-2.01-BC, GENERATOR |
| | ROOM.PLEASE ADDRESS THE FOLLOWING |
| | ITEMS: |
| | A) EXHAUST LOUVER TERMINATES IN A 2HR |
| | RATEDWALL WITHOUT PROTECTION.PLEASE |
| | NOTE, FIRE DAMPER TO MANUFACTURER |
| | APPROVAL AT THIS TERMIANTION. |
| | B) PLAN DOES NOT INDICATE TERMINATION OF |
| | THE MUFFLER EXHAUST TO THE GENERATOR. |
| | C) AIR MAKE-UP FOR THE GENERATOR ROOM IS |
| | TAKEN FROM THE LOADING DOCK AREA WHICH |
| | IS NON-COMPLIANT WITH 2004 FMC 401.5.1. |
| | D) PLEASE CLARIFY DETAIL OF THE |
| | GENERATOR INDICATED ON PLAN M-4-04. THIS |
| | DETAIL ALSO INDICATES A REMOTE FILL |
| | WHICH IS NOT DEPICTED ON THE PLAN. |
| | E) DETAIL INDICATES THE SUB-BASE FUEL |
| | TANK IS A 300 GALLON, WILL THERE BE |
| | ANOTHER REMOTE FUEL TANK? |
| | |
| | 8.INSTALLATION OF THE GENERATOR SHALL |
| | COMPLY WITH THE FOLLOWING NFPA 110 |
| | REQUIREMENTS: |
| | 7.7.2.1 FOR EPS SUPPLYING LEVEL 1 EPSS, |
| | VENTILATION AIR SHALL BE SUPPLIED |
| | DIRECTLY FROM A SOURCE OUTSIDE THE |
| | BUILDING BY AN EXTERIOR WALL OPENING OR |
| | FROM A SOURCE OUTSIDE THE BUILDING BY A |
| | 2-HOUR FIRE RATED AIR TRANSFER SYSTEM. |
| | |
| | 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS, |
| | DISCHARGE AIR SHALL BE DIRECTED OUTSIDE |
| | THE BUILDING BY AN EXTERIOR WALL OPENING |
| | OR TO AN EXTERIOR OPENING BY A 2-HOUR |
| | FIRE RATED AIR TRANSFER SYSTEM. |
| | |
| | 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER |
| | SELF-CLOSING DEVICES SHALL NOT BE |
| | PERMITTED IN VENTILATION OPENINGS OR |
| | DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE |
| | AIR TO EPS EQUIPMENT FOR LEVEL 1 EPSS. |
| | |
| | 7.7.3 VENTILATION AIR SUPPLY SHALL BE |
| | FROM OUTDOORS OR FROM A SOURCE OUTSIDE |
| | THE BUILDING BY AN EXTERIOR WALL OPENING |
| | OR FROM A SOURCE OUTSIDE THE BUILDING BY |
| | A 2-HOUR FIRE RATED AIR TRANSFER SYSTEM. |
| | |
| | 9.PLAN SHEET M-2.01-BC, FIRE CONTROL |
| | ROOM, ARCHITECTURAL PLANS INDICATE THIS |
| | ROOM IS AS NOT HAVING A FIRE RATING AS |
| | REQUIRED PER 2004 FBC 911.1.PLEASE |
| | CLARIFY.ALL PENETRATIONS SHALL COMPLY |
| | WITH 2004 FBC 712. |
| | |
| | 10. PLEASE CLARIFY SMOKE CONTROL METHOD |
| | FOR THE EXIT CORRIDORS FOR THE RESIDANT |
| | FLOORS (M-2.03-BC THROUGH M-2.09-CD, AND |
| | M-2,10-BCM-2.13-CD).SMOKE CONTROL |
| | THROUGH PRESSURIZATION.PLEASE INDICATE |
| | WHERE THE FLOOR OF INCIDENT WILL THE |
| | SMOKE BE MIDIGATED TO.SHOW COMPLIANCE |
| | WTIH 2004 FMC 513.10.3. |
| | |
| | 11. PLAN SHEET M-3.01 INDICATES R/A |
| | GRILLE IN THE LAUNDRY ROOM.LAUNDRY |
| | ROOMS ARE NOT REQUIRED TO HAVE RETURN |
| | AIR PER 2004 FMC 601.4 EXCEPTION #3. |
| | |
| | 12. PLAN SHEET P-4.15 INDICATES GAS |
| | RISER.PLEASE INDICATE IF ANY OF THE |
| | APPLIANCES LOCATED IN THE CONDO UNITS |
| | WILL BE GAS (DRYER, WATER HEATER, RANGE, |
| | ETC.). |
| | |
| | 13. PLAN SHEET P-1.01, DETAIL FOR THE |
| | GENERATOR ROOM SHOWS AN EXTERIORFILL |
| | POINT.THIS LOCATION IS "INSIDE" THE |
| | GARAGE AREA, AS IS THE MUFFLER EXHAUST. |
| | PER 2004 FMC 1305.6, FILL PIPE SHALL |
| | TERMINATE OUTSIDE THE BUILDING AT A |
| | POINT AT LEAST 2 FEET FROM ANY BUILDING |
| | OPENING AT THE SAME OR LOWER LEVEL.IT |
| | SHALL ALSO TERMINATE IN SUCH A MANNER TO |
| | MINIMIZE SPILLING WHEN FILL HOSE IS |
| | DISCONNECTED. |
| | |
| | 14. PLAN SHEET P-5.01 DETAIL FOR THE |
| | GENERATOR SIMPLEX FUEL PORT.IS THIS A |
| | DAY TANK? |
| | |
| | 15. PLEASE PROVIDE SUBMITTAL DATA & |
| | INSTALLATION INSTRUCTIONS FOR THE DIESEL |
| | GENERATOR. |
| | |
| | 16. PLEASE PROVIDE SUBMITTAL DATA & |
| | INSTALLATION INSTRUCTIONS FOR THE |
| | "VENTLESS DRYERS" INDICATED ON PLAN |
| | SHEET M-3.02. |
| | |
| | 17. PROVIDE SUBMITTAL DATA FOR ALL |
| | EQUIPMENNT FANS, BOILERS, COOLING |
| | TOWERS, ETC. |
| | |
| | 18. PROVIDE ENERGY CALCUALTIONS IN |
| | ACCORDANCE WITH 2004 FBC CHAPTER 13. |
| | PROVIDE SIZING CALCS FOR SPACE COOLING |
| | UNITS AND DUCT SIZING PER 2004 FBC |
| | 13-407.1.ABC.1 & 13-410.1.ABC.1.2. |
| | |
| | 19. RETAIL SPACE FOR FUTURE BUILD-OUT - |
| | PLEASE NOTE, ARE ANY PROVISIONS SET IN |
| | PLACE FOR A GREASE DUCT INSTALLATION & |
| | TERMINATION SHOULD A RESTAURANT OCCUPY |
| | ONE OR MORE OF THE RETAIL SPACES. |
| | |
| | 20. PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| | 403.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719 OR |
| | E-MAIL [email protected]. |