Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-30 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET M-2.01-AB, PLEASE PROVIDE
 THE DISTANCE FROM PROPERTY LINES,
 STREETS, ALLEYS, PARKING LOTS AND
 LOADING DOCKS FOR THE FRESH AIR INTAKES
 INTERIOR AND EXTERIOR OF THE BUILDING.
 SHOW COMPLIANCE WITH 2004 FMC 401.5 &
 401.5.1.
  
 2.PLAN SHEET M-2.01-AB, 12 X 12 O.A.
 INTAKE AT THE PARKING MAIN ENTRANCE,
 SHOW COMPLIANCE WITH FMC 401.5, 401.5.1.
  
 3.PLAN SHEET M-2.01-AB, PLEASE CLARIFY
 THE FOLLOWING; R1-SSF-1 IS A SUPPLY FAN
 FOR THE PURPOSE OF SMOKE CONTROL TO THE
 RETAIL SPACE 1 & COORIDOR?ON PLAN
 SHEET THE SYMBOL FOR RETURN DUCT IS
 INDICATED.PLEASE CLARIFY ALSO FIRE
 DAMPERS INDICATED INSTEAD FO FIRE/SMOKE
 DAMPERS.
  
 4.R1-SSF-1 IS ALSO DUCTED TO UNIT 3-3
 (WHICH IS NOT INDICATED ON THE EQUIPMENT
 SCHEDULE),PLEASE CLARIFY WHAT THIS
 EQUIPMENT FUCTION IS, (AHU, RTU, ETC.)?
  
 5.PLAN SHEET M-2.01-AB, PLEASE
 INDICATE THE ELEVATIONS & DISTANCES FROM
 PROPERTY LINES ADJACENT BUILDING ETC.
 FOR THE EXHAUST TERMIANTIONS.SHOW
 COMPLIANCE WITH 2004 FMC 401.5.1,
 401.5.2, & 501.2.
  
 6.PLAN SHEET M-2.01-AB, PLEASE CLARFY
 THE TOILET & SMOKE EXHAUST TO RETAIL 2
 IN RELATION TO THE DOUBLE DOOR,
 SIDEWALK, AND PROPERTY LINES.
  
 7.PLAN SHEET M-2.01-BC, GENERATOR
 ROOM.PLEASE ADDRESS THE FOLLOWING
 ITEMS:
 A) EXHAUST LOUVER TERMINATES IN A 2HR
 RATEDWALL WITHOUT PROTECTION.PLEASE
 NOTE, FIRE DAMPER TO MANUFACTURER
 APPROVAL AT THIS TERMIANTION.
 B) PLAN DOES NOT INDICATE TERMINATION OF
 THE MUFFLER EXHAUST TO THE GENERATOR.
 C) AIR MAKE-UP FOR THE GENERATOR ROOM IS
 TAKEN FROM THE LOADING DOCK AREA WHICH
 IS NON-COMPLIANT WITH 2004 FMC 401.5.1.
 D) PLEASE CLARIFY DETAIL OF THE
 GENERATOR INDICATED ON PLAN M-4-04. THIS
 DETAIL ALSO INDICATES A REMOTE FILL
 WHICH IS NOT DEPICTED ON THE PLAN.
 E) DETAIL INDICATES THE SUB-BASE FUEL
 TANK IS A 300 GALLON, WILL THERE BE
 ANOTHER REMOTE FUEL TANK?
  
 8.INSTALLATION OF THE GENERATOR SHALL
 COMPLY WITH THE FOLLOWING NFPA 110
 REQUIREMENTS:
 7.7.2.1 FOR EPS SUPPLYING LEVEL 1 EPSS,
 VENTILATION AIR SHALL BE SUPPLIED
 DIRECTLY FROM A SOURCE OUTSIDE THE
 BUILDING BY AN EXTERIOR WALL OPENING OR
 FROM A SOURCE OUTSIDE THE BUILDING BY A
 2-HOUR FIRE RATED AIR TRANSFER SYSTEM.
  
 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS,
 DISCHARGE AIR SHALL BE DIRECTED OUTSIDE
 THE BUILDING BY AN EXTERIOR WALL OPENING
 OR TO AN EXTERIOR OPENING BY A 2-HOUR
 FIRE RATED AIR TRANSFER SYSTEM.
  
 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER
 SELF-CLOSING DEVICES SHALL NOT BE
 PERMITTED IN VENTILATION OPENINGS OR
 DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE
 AIR TO EPS EQUIPMENT FOR LEVEL 1 EPSS.
  
 7.7.3 VENTILATION AIR SUPPLY SHALL BE
 FROM OUTDOORS OR FROM A SOURCE OUTSIDE
 THE BUILDING BY AN EXTERIOR WALL OPENING
 OR FROM A SOURCE OUTSIDE THE BUILDING BY
 A 2-HOUR FIRE RATED AIR TRANSFER SYSTEM.
  
 9.PLAN SHEET M-2.01-BC, FIRE CONTROL
 ROOM, ARCHITECTURAL PLANS INDICATE THIS
 ROOM IS AS NOT HAVING A FIRE RATING AS
 REQUIRED PER 2004 FBC 911.1.PLEASE
 CLARIFY.ALL PENETRATIONS SHALL COMPLY
 WITH 2004 FBC 712.
  
 10. PLEASE CLARIFY SMOKE CONTROL METHOD
 FOR THE EXIT CORRIDORS FOR THE RESIDANT
 FLOORS (M-2.03-BC THROUGH M-2.09-CD, AND
 M-2,10-BCM-2.13-CD).SMOKE CONTROL
 THROUGH PRESSURIZATION.PLEASE INDICATE
 WHERE THE FLOOR OF INCIDENT WILL THE
 SMOKE BE MIDIGATED TO.SHOW COMPLIANCE
 WTIH 2004 FMC 513.10.3.
  
 11. PLAN SHEET M-3.01 INDICATES R/A
 GRILLE IN THE LAUNDRY ROOM.LAUNDRY
 ROOMS ARE NOT REQUIRED TO HAVE RETURN
 AIR PER 2004 FMC 601.4 EXCEPTION #3.
  
 12. PLAN SHEET P-4.15 INDICATES GAS
 RISER.PLEASE INDICATE IF ANY OF THE
 APPLIANCES LOCATED IN THE CONDO UNITS
 WILL BE GAS (DRYER, WATER HEATER, RANGE,
 ETC.).
  
 13. PLAN SHEET P-1.01, DETAIL FOR THE
 GENERATOR ROOM SHOWS AN EXTERIORFILL
 POINT.THIS LOCATION IS "INSIDE" THE
 GARAGE AREA, AS IS THE MUFFLER EXHAUST.
 PER 2004 FMC 1305.6, FILL PIPE SHALL
 TERMINATE OUTSIDE THE BUILDING AT A
 POINT AT LEAST 2 FEET FROM ANY BUILDING
 OPENING AT THE SAME OR LOWER LEVEL.IT
 SHALL ALSO TERMINATE IN SUCH A MANNER TO
 MINIMIZE SPILLING WHEN FILL HOSE IS
 DISCONNECTED.
  
 14. PLAN SHEET P-5.01 DETAIL FOR THE
 GENERATOR SIMPLEX FUEL PORT.IS THIS A
 DAY TANK?
  
 15. PLEASE PROVIDE SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE DIESEL
 GENERATOR.
  
 16. PLEASE PROVIDE SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE
 "VENTLESS DRYERS" INDICATED ON PLAN
 SHEET M-3.02.
  
 17. PROVIDE SUBMITTAL DATA FOR ALL
 EQUIPMENNT FANS, BOILERS, COOLING
 TOWERS, ETC.
  
 18. PROVIDE ENERGY CALCUALTIONS IN
 ACCORDANCE WITH 2004 FBC CHAPTER 13.
 PROVIDE SIZING CALCS FOR SPACE COOLING
 UNITS AND DUCT SIZING PER 2004 FBC
 13-407.1.ABC.1 & 13-410.1.ABC.1.2.
  
 19. RETAIL SPACE FOR FUTURE BUILD-OUT -
 PLEASE NOTE, ARE ANY PROVISIONS SET IN
 PLACE FOR A GREASE DUCT INSTALLATION &
 TERMINATION SHOULD A RESTAURANT OCCUPY
 ONE OR MORE OF THE RETAIL SPACES.
  
 20. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].