Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop G
Sequence Number 1
Notes
Date Text
2006-04-21 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-4.15 GAS REQUIREMENTS:
 A. SUBMIT MANUFACTURE SPECIFICATION
 SHEETS FOR 5PSI TO .5PSI REGULATORS. IF
 REGULATORS ARE VENTED, SUBMIT AN
 ISOMETRIC PIPING DIAGRAM FOR THE VENTING
 AND INDICATE TERMINATION POINT. INDICATE
 MATERIAL FOR VENT PIPING.
 B. SHUT OFF VALVES ARE REQUIRED
 UPSTREAM OF EACH REGULATOR. SECTION
 409.4
 C. SUBMIT AN APPROVED TABLE FOR 5PSI UP
 TO 800 FEET TO VERIFY PIPE SIZE IN
 SYSTEM. SECTION 402.3(2)
 D. INDICATE LENGHTS OF PIPE FOR EACH
 CUT SECTION FROM THE METER TO THE FIRST
 RISER, AND FOR ALL CUT SECTIONS
 DOWNSTREAM OF THE 5PSI TO .5PSI
 REGULATOR. FBC-2004 FUEL GAS
 E. GALVANIZED PIPING IS NOT APPROVED
 FOR UNDERGROUND INSTALLATION. SECTION
 404.8.
 F. SLEEVE FOR UNDERGROUND PIPING SHALL
 BE INSTALLED PER SECTION 404.11.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]