Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-16 00:00:001. ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 2. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 4. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 5. DEBRIS SHALL BE REMOVED THE BUILDING
 DAILY.
  
 6. NO CUTTING OR WELDINGALLOWED
 WITHOUT APPROVAL OF THE BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA 51B.
  
 7. PLEASE EXPLAIN "PROP. 6" FIRE
 SERVICE" SHOWN IN DETAIL B ON PAGE
 C-2.0.
  
 8. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING, AND AFTER CONSTRUCTION.
  
 9. KNOX-BOXES WILL BE REQUIRED FOR THE
 PROJECT.
  
 10. LANDSCAPE AREAS SHALL NOT INTERFERE
 WITH ANY ACCESS TO AND FIRE HYDRANTS OR
 FIRE PROTECTION DEVICES LIKE FIRE
 DEPARTMENT CONNECTIONS.
  
 11. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 12. WHAT WILL THE 24 FOOT DRIVEWAY BE
 USED FOR.
  
 13. ARE ANY STEPS LOCATED NEAR WATER
 FEATURES SLIP RESISTANT.
  
 14. ALL NEW STAIRS AND RAMPS SHALL BE
 PROVIDED HANDRAILS ON BOTH SIDES.
  
 15. ELEVATOR WARNING SIGNS REQUIRED.
  
 16. TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 17. ALL MECHANICAL, ELECTRICAL, AND
 STORAGE ROOMS SHALL BE IDENTIFIED WITH
 SIGNAGE.
  
 18.WRONG LIFE SAFETY CODE REFERENCED ON
 PAGE A-0.02.SHOULD READ THE FLORIDA FIRE
 PREVENTION CODE WHICH CONSISTS OF 2003
 EDITION OF THE LIFE SAFETY CODE AND NFPA
 1, 2003 EDITION.
  
 19. DUE TO THE SIZE OF THE PROJECT, A
 FIRE AND EMERGENCY SAFETY PLAN WILL BE
 REQUIRED. THIS COMPREHENSIVE PLAN SHALL
 BE SUBMITTED TO THE CHIEF FIRE
 PREVENTION OFFICER OF THE BUREAU OF FIRE
 PREVENTION AND A COPY WILL BE PROVIDED
 TO THE DIRECTOR OF CONSTRUCTION
 SERVICES.
  
 20. THIS PROJECT WILL BE REVIEWED UNDER
 THE MULTIPLE OCCUPANCY CONCEPT SINCE
 SEVERAL DIFFERENT OCCUPANCY TYPES WILL
 EXIST.
  
 21. HOW WILL THE THEATRE DROP OFF AREA
 WORK ON QUADRILLE, PAGE A-1.02.
  
 22. ALL PROPOSED RETAIL SPACES SHALL BE
 EQUIPPED WITH FIRE SPRINKLER AND FIRE
 ALARM PROTECTION PRIOR TO THE
 BUILDING(S) RECEIVING A CERTIFICATE OF
 OCCUPANCY. THE RETAIL SPACES MAY NOT BE
 COMPLETE OR LEASED AT THAT TIME.
  
 23. EXIT SIGNS SHALL NOT EXCEED 100 FEET
 APART.
  
 24. EXIT SIGNS APPEAR TO DIRECT PERSONS
 OUT OF THE STORAGE ROOM ON PAGE LS-2.03
 INTO THE PARKING GARAGE. THIS DOES NOT
 APPEAR TO BE CORRECT.
  
 25. NO EXIT SIGNS SHOWN IN STORAGE ROOMS
 ON PAGES LS-2.05, LS-2.06, LS-2.07.
  
 26. PLEASE EXPLAIN GENERATOR ROOMS
 LOCATED ON THE FLOOR LEVEL EIGHT.
  
 27. HOW WILL THE BUILDINGS BE SEPARATELY
 IDENTIFIED SHOULD AN EMERGENCY CONDITION
 OCCUR.
  
 28. SIAMESE CONNECTIONS NOTED ON PAGE
 LS-2.13. THESE SHOULD BE CALLED OUT ON
 THE PLANS AS ROOF MANIFOLDS.
  
 29. AFTER PERSONS EXIT STAIRS 4 & 4A,
 WHAT PREVENTS THEM FROM BEING HIT BY
 VEHICLES.
  
 30. ALL MEZZANINES ILLUSTRATED ON THE
 PLANS SHALL COMPLY WITH ALL APPLICABLE
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 31. THERE APPEARS TO BE COLUMNS NEAR THE
 OPENINGS OF THE PARKING GARAGE EXITS
 SHOWN ON PAGE A-2.03.
  
 32. PLEASE VERIFY THAT ALL DOORS THAT
 OPEN ONTO EXIT CORRIDORS (ELECTRICAL
 ROOM) DO NOT REDUCE THE CORRIDORS DWON
 TO THE REQUIRED WIDTH.
  
 33. STAIRWELL IDENTIFICATION SIGNS WILL
 BE REQUIRED INDICATING STAIR NUMBER,
 FLOOR LEVEL, TERMINATION POINTS TOP AND
 BOTTOM.
  
 34. ELECTRICAL ROOM AND TRASH ROOM DOORS
 OPPOSE ONE ANOTHER ON PAGE A-2.09.
 SIMILAR CONDITIONS EXIST ON OTHER PAGES.
  
 35. BOTH FIRE COMMAND ROOMS SHALL COMPLY
 WITH THE FLORIDA FIRE PREVENTION CODE
 AND THE FLORIDA BUILDING CODE AND SHALL
 CONTAIN ALL OF THE REQUIRED OUTLINED
 WITHIN THESE CODES.
  
 36. STRETCHER ACCESSIBLE ELEVATORS SHALL
 BE IDENTIFIED BY APPROPRIATE SIGNAGE.
  
 37. FOUR CIRCLES SHOWN IN KITCHEN ON
 PAGE A-3.02-BC. DOES THIS INDICATE A
 STOVE. PLEASE EXPLAIN. PAGE A-3.02CD.
  
 38. HOW DOES THE PROPOSED SLIDE GATE ON
 PAGE A-3.03BC RESTICT MOVEMENT. DOES IT
 RESTRICT MOVEMENT OR TRAVEL TO ANY
 EXITS.
  
 39. SAME SITUATION EXISTS ON PAGE
 A-3.03CD.
  
 40. ROOM BEHIND ELECTRICAL ROOM E329 IS
 NOT LABELED ON PAGE A-3.04BC. PLEASE
 IDENTIFY.
  
 41. SIMILAR CONDITION EXISTS ON OTHER
 PAGES.
  
 42. ON SEVERAL SHEETS IT IS PRESUMED
 THAT A PARKING SPACE THAT IS CALLED OUT
 AS EJ IS NEXT TO A COLUMN THAT IS IN THE
 VICINITY OF AN EXIT DOOR.
  
 43. PLEASE EXPLAIN STORAGE ROOM E535 ON
 PAGE A-3.06 AB. PLEASE INDICATE INGRESS/
 EGRESS INTO AREA.
  
 44. FIRE ALARM CIRCUITS ARE REQUIRED TO
 MEET SURVIVABILITY REQUIREMENTS OF THE
 APPLICABLE CODES.
  
 45. SMOKE DETECTORS SHALL BE MOUNTED A
 MINIMUM OF AT LEAST THREE FEET FROM AC
 DIFFUSERS.
  
 46. MORE DETAILS REQUIRED FOR POOL
 CABANAS SHOWN ON PAGE A-3.09AB.
  
 47. SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL OF THE LOFTS.
  
 48. ALL FIRE RATED DOORS AND WINDOWS
 SHALL COMPLY WITH NFPA 80 FIRE DOORS AND
 WINDOWS.
  
 49. FIRE RATED WALLS AND DOORS SHALL BE
 GIVEN PRIORITY DURING CONSTRUCTION.
  
 50. ON PAGE A-4.15, SEVERAL ELEMENTS
 APPEAR TO HANG OVER THE PROPERTY LINE.
  
 51. PLEASE PROVIDE PRODUCT APPROVALS FOR
 ALL FIRE RATED AWNINGS.
  
 52. MECHANICAL GRILLS SHOWN IN CLOSE
 PROXIMITY TO OTHER BUILDING OPENINGS ON
 PAGE A-5.01.
  
 53. THE FIRE SPRINKLER HEADS PLANNED FOR
 USE SHALL BE QUICK RESPONSE OR BE
 RESIDENTIAL TYPE.
  
 54. MORE DETAILS NEEDED FOR ORNAMENTAL
 GRILL ON PAGE A-5.06.
  
 55. ALL RETAIL SPACES SHALL BE SEPERATED
 FROM PARKING AREAS BY A MINIMUM OF AT
 LEAST TWO HOUR CONSTRUCTION.
  
 56. ANY DECORATIVE SOFFITS PLANNED TO BE
 USED SHALL NOT INTERFERE WITH THE
 OPERATION OF ANY REQUIRED FIRE
 SPRINKLERS.
  
 57. PLEASE PROVIDE RATING OF TRASH CHUTE
 DOORS ON PAGES A-6.10-A-6.13.
  
 58. NOTE # 1 ON PAGE A-7.01 IS NOT
 CORRECT. DESIGN ISSUES WITH PIPES SHALL
 BE AVOIDED.
  
 59. PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS SHALL BE
 SHOWN ON PAGE A-7.06.
  
 60. ELEVATOR MACHINE ROOMS MUST BE
 PROVIDED WITH VENTILATION AND AIR
 CONDITIONING.
  
 61. EMERGENCY GENERATORS PROPOSED FOR
 THIS PROJECT SHALL COMPLY WITH NFPA 110.
  
 62. DOOR SCHEDULE LEGEND ON A-8.05 DOES
 NOT INDICATE WHAT ELEC. OPER
 MEANS ON DOOR SCHEDULE. PLEASE PROVIDE
 DETAILS.
  
 63. ON PAGE A-10.05 "BREAK GLASS" NOTE
 FOR (1) A-10.5. HOW IS THIS TO BE
 ACCOMPLISHED IS A HANDLE OR HAMMER
 PROVIDED.
  
 64. PLEASE VERIFY THAT ALL MATERIAL SUCH
 AS UPOSTERED MATERIAL AND DRAPERY
 MATERIAL DISPLAYED ON ID-5.06. DOES THIS
 PROPOSED MATERIAL MEET FLAME SPREAD
 REQUIREMENTS.
  
 65. EXIT SIGN APPEARS TO BE MISSING IN
 RETAIL SPACE # 4 ON PAGE E-2.01-BC.
  
 66. EXIT SIGN LOCATED OUTSIDE OF PUMP
 ROOM ON PAGE E-2.01-BC LEADS WHERE.
  
 67. SOME EXIT DOORS IN RETAIL SPACE # 9
 ON PAGE E-2.01-DA. VERIFY OCCUPANCY
 TYPE.
  
 68. ON SHEETS E-2.02 BC AND E-2.20 CD
 EXIT SIGNS ARE DIRECTING PERSONS TO EXIT
 INTO THE GARAGE. PLEASE EXPLAIN.
  
 69. SOME EXIT SIGNS APPEAR TO BE MISSING
 ON PAGE E-2.05-AB.
  
 70. NO EXIT SIGNS SHOWN IN GYM ON PAGE
 E-2.09-BC.
  
 71. EXIT SIGNS APPEAR TO BE MISSING ON
 PAGE E-2.08-AB.
  
 72. ADDITIONAL EXIT SIGN NEEDED NEAR
 BATHROOMS ON PAGE E-2.09-BC TO DIRECT
 PERSONS TO STAIRWAY.
  
 73. THE EMERGENCY LIGHTING AND GENERATOR
 SHALL COMPLY WITH NFPA 101, SECTION
 11.8.4.
  
 74. THE REQUIRED FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE. SEPERATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM.
  
 75. THE FIRE COOMAND ROOM SHOWN ON PAGE
 E-5.01C MUST CONTAIN ALL OF THE REQUIRED
 EQUIPMENT AS PER SECTION 11-8 OF THE
 LIFE SAFETY CODE.
  
 76. THE ENTIRE BUILDING WILL BE REQUIRED
 TO BE FIRE SPRINKLER PROTECTED. SEPERATE
 PLANS AND PERMITS REQUIRED.
  
 77. THE 2 1/2 FIRE DEPARTMENT HOSE VALVE
 CONNECTIONS SHOWN ON THE FP PAGES SHALL
 BE REDUCED WITH 1 1/2 REDUCERS.
  
 78. NO COMBUSTIBLES ALLOWED IN ANY AREAS
 USED AS RETURN AIR PLENUMS. ALTHOUGH
 THIS INFORMATION IS NOTED IT MAY BE
 MISSED. PLEASE CLEARLY ILLUSTRATE THIS
 ON THE APPROPRIATE SHEETS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709