| 2006-02-16 00:00:00 | 1. ELECTRONIC SWITCHES, CHAIN AND LOCK |
| | REQUIRED ON FIRE LINE BACKFLOW DEVICE. |
| | |
| | 2. DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 3. EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 4. TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE STORIES |
| | OR THIRTY FEET IN HEIGHT. |
| | |
| | 5. DEBRIS SHALL BE REMOVED THE BUILDING |
| | DAILY. |
| | |
| | 6. NO CUTTING OR WELDINGALLOWED |
| | WITHOUT APPROVAL OF THE BUREAU OF FIRE |
| | PREVENTION AND COMPLIANCE WITH NFPA 51B. |
| | |
| | 7. PLEASE EXPLAIN "PROP. 6" FIRE |
| | SERVICE" SHOWN IN DETAIL B ON PAGE |
| | C-2.0. |
| | |
| | 8. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 9. KNOX-BOXES WILL BE REQUIRED FOR THE |
| | PROJECT. |
| | |
| | 10. LANDSCAPE AREAS SHALL NOT INTERFERE |
| | WITH ANY ACCESS TO AND FIRE HYDRANTS OR |
| | FIRE PROTECTION DEVICES LIKE FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 11. BUILDING ADDRESS REQUIRED. A MINIMUM |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 12. WHAT WILL THE 24 FOOT DRIVEWAY BE |
| | USED FOR. |
| | |
| | 13. ARE ANY STEPS LOCATED NEAR WATER |
| | FEATURES SLIP RESISTANT. |
| | |
| | 14. ALL NEW STAIRS AND RAMPS SHALL BE |
| | PROVIDED HANDRAILS ON BOTH SIDES. |
| | |
| | 15. ELEVATOR WARNING SIGNS REQUIRED. |
| | |
| | 16. TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOOR LOCATIONS. |
| | |
| | 17. ALL MECHANICAL, ELECTRICAL, AND |
| | STORAGE ROOMS SHALL BE IDENTIFIED WITH |
| | SIGNAGE. |
| | |
| | 18.WRONG LIFE SAFETY CODE REFERENCED ON |
| | PAGE A-0.02.SHOULD READ THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONSISTS OF 2003 |
| | EDITION OF THE LIFE SAFETY CODE AND NFPA |
| | 1, 2003 EDITION. |
| | |
| | 19. DUE TO THE SIZE OF THE PROJECT, A |
| | FIRE AND EMERGENCY SAFETY PLAN WILL BE |
| | REQUIRED. THIS COMPREHENSIVE PLAN SHALL |
| | BE SUBMITTED TO THE CHIEF FIRE |
| | PREVENTION OFFICER OF THE BUREAU OF FIRE |
| | PREVENTION AND A COPY WILL BE PROVIDED |
| | TO THE DIRECTOR OF CONSTRUCTION |
| | SERVICES. |
| | |
| | 20. THIS PROJECT WILL BE REVIEWED UNDER |
| | THE MULTIPLE OCCUPANCY CONCEPT SINCE |
| | SEVERAL DIFFERENT OCCUPANCY TYPES WILL |
| | EXIST. |
| | |
| | 21. HOW WILL THE THEATRE DROP OFF AREA |
| | WORK ON QUADRILLE, PAGE A-1.02. |
| | |
| | 22. ALL PROPOSED RETAIL SPACES SHALL BE |
| | EQUIPPED WITH FIRE SPRINKLER AND FIRE |
| | ALARM PROTECTION PRIOR TO THE |
| | BUILDING(S) RECEIVING A CERTIFICATE OF |
| | OCCUPANCY. THE RETAIL SPACES MAY NOT BE |
| | COMPLETE OR LEASED AT THAT TIME. |
| | |
| | 23. EXIT SIGNS SHALL NOT EXCEED 100 FEET |
| | APART. |
| | |
| | 24. EXIT SIGNS APPEAR TO DIRECT PERSONS |
| | OUT OF THE STORAGE ROOM ON PAGE LS-2.03 |
| | INTO THE PARKING GARAGE. THIS DOES NOT |
| | APPEAR TO BE CORRECT. |
| | |
| | 25. NO EXIT SIGNS SHOWN IN STORAGE ROOMS |
| | ON PAGES LS-2.05, LS-2.06, LS-2.07. |
| | |
| | 26. PLEASE EXPLAIN GENERATOR ROOMS |
| | LOCATED ON THE FLOOR LEVEL EIGHT. |
| | |
| | 27. HOW WILL THE BUILDINGS BE SEPARATELY |
| | IDENTIFIED SHOULD AN EMERGENCY CONDITION |
| | OCCUR. |
| | |
| | 28. SIAMESE CONNECTIONS NOTED ON PAGE |
| | LS-2.13. THESE SHOULD BE CALLED OUT ON |
| | THE PLANS AS ROOF MANIFOLDS. |
| | |
| | 29. AFTER PERSONS EXIT STAIRS 4 & 4A, |
| | WHAT PREVENTS THEM FROM BEING HIT BY |
| | VEHICLES. |
| | |
| | 30. ALL MEZZANINES ILLUSTRATED ON THE |
| | PLANS SHALL COMPLY WITH ALL APPLICABLE |
| | BUILDING AND FIRE CODE REQUIREMENTS. |
| | |
| | 31. THERE APPEARS TO BE COLUMNS NEAR THE |
| | OPENINGS OF THE PARKING GARAGE EXITS |
| | SHOWN ON PAGE A-2.03. |
| | |
| | 32. PLEASE VERIFY THAT ALL DOORS THAT |
| | OPEN ONTO EXIT CORRIDORS (ELECTRICAL |
| | ROOM) DO NOT REDUCE THE CORRIDORS DWON |
| | TO THE REQUIRED WIDTH. |
| | |
| | 33. STAIRWELL IDENTIFICATION SIGNS WILL |
| | BE REQUIRED INDICATING STAIR NUMBER, |
| | FLOOR LEVEL, TERMINATION POINTS TOP AND |
| | BOTTOM. |
| | |
| | 34. ELECTRICAL ROOM AND TRASH ROOM DOORS |
| | OPPOSE ONE ANOTHER ON PAGE A-2.09. |
| | SIMILAR CONDITIONS EXIST ON OTHER PAGES. |
| | |
| | 35. BOTH FIRE COMMAND ROOMS SHALL COMPLY |
| | WITH THE FLORIDA FIRE PREVENTION CODE |
| | AND THE FLORIDA BUILDING CODE AND SHALL |
| | CONTAIN ALL OF THE REQUIRED OUTLINED |
| | WITHIN THESE CODES. |
| | |
| | 36. STRETCHER ACCESSIBLE ELEVATORS SHALL |
| | BE IDENTIFIED BY APPROPRIATE SIGNAGE. |
| | |
| | 37. FOUR CIRCLES SHOWN IN KITCHEN ON |
| | PAGE A-3.02-BC. DOES THIS INDICATE A |
| | STOVE. PLEASE EXPLAIN. PAGE A-3.02CD. |
| | |
| | 38. HOW DOES THE PROPOSED SLIDE GATE ON |
| | PAGE A-3.03BC RESTICT MOVEMENT. DOES IT |
| | RESTRICT MOVEMENT OR TRAVEL TO ANY |
| | EXITS. |
| | |
| | 39. SAME SITUATION EXISTS ON PAGE |
| | A-3.03CD. |
| | |
| | 40. ROOM BEHIND ELECTRICAL ROOM E329 IS |
| | NOT LABELED ON PAGE A-3.04BC. PLEASE |
| | IDENTIFY. |
| | |
| | 41. SIMILAR CONDITION EXISTS ON OTHER |
| | PAGES. |
| | |
| | 42. ON SEVERAL SHEETS IT IS PRESUMED |
| | THAT A PARKING SPACE THAT IS CALLED OUT |
| | AS EJ IS NEXT TO A COLUMN THAT IS IN THE |
| | VICINITY OF AN EXIT DOOR. |
| | |
| | 43. PLEASE EXPLAIN STORAGE ROOM E535 ON |
| | PAGE A-3.06 AB. PLEASE INDICATE INGRESS/ |
| | EGRESS INTO AREA. |
| | |
| | 44. FIRE ALARM CIRCUITS ARE REQUIRED TO |
| | MEET SURVIVABILITY REQUIREMENTS OF THE |
| | APPLICABLE CODES. |
| | |
| | 45. SMOKE DETECTORS SHALL BE MOUNTED A |
| | MINIMUM OF AT LEAST THREE FEET FROM AC |
| | DIFFUSERS. |
| | |
| | 46. MORE DETAILS REQUIRED FOR POOL |
| | CABANAS SHOWN ON PAGE A-3.09AB. |
| | |
| | 47. SMOKE DETECTORS ARE REQUIRED ON |
| | EVERY LEVEL OF THE LOFTS. |
| | |
| | 48. ALL FIRE RATED DOORS AND WINDOWS |
| | SHALL COMPLY WITH NFPA 80 FIRE DOORS AND |
| | WINDOWS. |
| | |
| | 49. FIRE RATED WALLS AND DOORS SHALL BE |
| | GIVEN PRIORITY DURING CONSTRUCTION. |
| | |
| | 50. ON PAGE A-4.15, SEVERAL ELEMENTS |
| | APPEAR TO HANG OVER THE PROPERTY LINE. |
| | |
| | 51. PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | ALL FIRE RATED AWNINGS. |
| | |
| | 52. MECHANICAL GRILLS SHOWN IN CLOSE |
| | PROXIMITY TO OTHER BUILDING OPENINGS ON |
| | PAGE A-5.01. |
| | |
| | 53. THE FIRE SPRINKLER HEADS PLANNED FOR |
| | USE SHALL BE QUICK RESPONSE OR BE |
| | RESIDENTIAL TYPE. |
| | |
| | 54. MORE DETAILS NEEDED FOR ORNAMENTAL |
| | GRILL ON PAGE A-5.06. |
| | |
| | 55. ALL RETAIL SPACES SHALL BE SEPERATED |
| | FROM PARKING AREAS BY A MINIMUM OF AT |
| | LEAST TWO HOUR CONSTRUCTION. |
| | |
| | 56. ANY DECORATIVE SOFFITS PLANNED TO BE |
| | USED SHALL NOT INTERFERE WITH THE |
| | OPERATION OF ANY REQUIRED FIRE |
| | SPRINKLERS. |
| | |
| | 57. PLEASE PROVIDE RATING OF TRASH CHUTE |
| | DOORS ON PAGES A-6.10-A-6.13. |
| | |
| | 58. NOTE # 1 ON PAGE A-7.01 IS NOT |
| | CORRECT. DESIGN ISSUES WITH PIPES SHALL |
| | BE AVOIDED. |
| | |
| | 59. PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS SHALL BE |
| | SHOWN ON PAGE A-7.06. |
| | |
| | 60. ELEVATOR MACHINE ROOMS MUST BE |
| | PROVIDED WITH VENTILATION AND AIR |
| | CONDITIONING. |
| | |
| | 61. EMERGENCY GENERATORS PROPOSED FOR |
| | THIS PROJECT SHALL COMPLY WITH NFPA 110. |
| | |
| | 62. DOOR SCHEDULE LEGEND ON A-8.05 DOES |
| | NOT INDICATE WHAT ELEC. OPER |
| | MEANS ON DOOR SCHEDULE. PLEASE PROVIDE |
| | DETAILS. |
| | |
| | 63. ON PAGE A-10.05 "BREAK GLASS" NOTE |
| | FOR (1) A-10.5. HOW IS THIS TO BE |
| | ACCOMPLISHED IS A HANDLE OR HAMMER |
| | PROVIDED. |
| | |
| | 64. PLEASE VERIFY THAT ALL MATERIAL SUCH |
| | AS UPOSTERED MATERIAL AND DRAPERY |
| | MATERIAL DISPLAYED ON ID-5.06. DOES THIS |
| | PROPOSED MATERIAL MEET FLAME SPREAD |
| | REQUIREMENTS. |
| | |
| | 65. EXIT SIGN APPEARS TO BE MISSING IN |
| | RETAIL SPACE # 4 ON PAGE E-2.01-BC. |
| | |
| | 66. EXIT SIGN LOCATED OUTSIDE OF PUMP |
| | ROOM ON PAGE E-2.01-BC LEADS WHERE. |
| | |
| | 67. SOME EXIT DOORS IN RETAIL SPACE # 9 |
| | ON PAGE E-2.01-DA. VERIFY OCCUPANCY |
| | TYPE. |
| | |
| | 68. ON SHEETS E-2.02 BC AND E-2.20 CD |
| | EXIT SIGNS ARE DIRECTING PERSONS TO EXIT |
| | INTO THE GARAGE. PLEASE EXPLAIN. |
| | |
| | 69. SOME EXIT SIGNS APPEAR TO BE MISSING |
| | ON PAGE E-2.05-AB. |
| | |
| | 70. NO EXIT SIGNS SHOWN IN GYM ON PAGE |
| | E-2.09-BC. |
| | |
| | 71. EXIT SIGNS APPEAR TO BE MISSING ON |
| | PAGE E-2.08-AB. |
| | |
| | 72. ADDITIONAL EXIT SIGN NEEDED NEAR |
| | BATHROOMS ON PAGE E-2.09-BC TO DIRECT |
| | PERSONS TO STAIRWAY. |
| | |
| | 73. THE EMERGENCY LIGHTING AND GENERATOR |
| | SHALL COMPLY WITH NFPA 101, SECTION |
| | 11.8.4. |
| | |
| | 74. THE REQUIRED FIRE ALARM SYSTEM SHALL |
| | BE MONITORED BY A UL LISTED CENTRAL |
| | STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. SEPERATE PLANS AND PERMITS |
| | REQUIRED FOR FIRE ALARM SYSTEM. |
| | |
| | 75. THE FIRE COOMAND ROOM SHOWN ON PAGE |
| | E-5.01C MUST CONTAIN ALL OF THE REQUIRED |
| | EQUIPMENT AS PER SECTION 11-8 OF THE |
| | LIFE SAFETY CODE. |
| | |
| | 76. THE ENTIRE BUILDING WILL BE REQUIRED |
| | TO BE FIRE SPRINKLER PROTECTED. SEPERATE |
| | PLANS AND PERMITS REQUIRED. |
| | |
| | 77. THE 2 1/2 FIRE DEPARTMENT HOSE VALVE |
| | CONNECTIONS SHOWN ON THE FP PAGES SHALL |
| | BE REDUCED WITH 1 1/2 REDUCERS. |
| | |
| | 78. NO COMBUSTIBLES ALLOWED IN ANY AREAS |
| | USED AS RETURN AIR PLENUMS. ALTHOUGH |
| | THIS INFORMATION IS NOTED IT MAY BE |
| | MISSED. PLEASE CLEARLY ILLUSTRATE THIS |
| | ON THE APPROPRIATE SHEETS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |