| 2006-03-13 00:00:00 | NOTES |
| | ********** UNSAT ********** |
| | |
| | OPERA PLACE. |
| | 419 LAKE VIEW AVE. |
| | |
| | 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED |
| | FOR "PLAN REVIEW" ONLY AND NOT BEEN |
| | SUBMITTED FOR PERMIT. PLEASE KNOW THERE |
| | WAS AN INCREASE IN PALM BEACH COUNTY |
| | IMPACT FEE SCHEDULE WHICH WENT INTO |
| | EFFECT ON JAN 12, 2006 5PM. ALL PROJECTS |
| | WOULD BE REQUIRED TO BE SUBMITTED FOR |
| | "PERMIT" AND PAID FEE BEFORE THAT DATE. |
| | |
| | 2) NOTE: PLEASE SEE COMMENTS FROM OTHER |
| | TRADES WITH RESPECT TO ADDRESSING OF |
| | TOWERS EAST AND WEST. PLEASE SEE |
| | COMMENTS WHICH MAY REQUIRE SOME |
| | ADJUSTMENT IN TITLE BLOCKS FOR SITE |
| | ADDRESS ETC. PLEASE KNOW, SIGNAGE FOR |
| | EACH WILL BE REQUIRED. PLEASE SEE FIRE |
| | REVIEW COMMENTS AS THIS WILL AFFECT THE |
| | 911 RESPONSE ALONG WITH SIGNAGE AT |
| | BUILDINGS, FIRE COMMAND ROOMS AND ALL |
| | ELECTRICAL ROOMS.230.2E, 700.8 ETC. |
| | * PLEASE ALSO KNOW PLANS AND PERMITTING |
| | FOR THE PROJECT IS COMING IN UNDER ONE |
| | PERMIT AND BOTH TOWERS BEING BUILT AND |
| | CONSTRUCTED AT THE SAME TIME. PLEASE |
| | KNOW THIS MAY CREATE AN ISSUE FOR ANY |
| | CO'S OR TCO'S OF THIS ONE PERMIT. SEE |
| | REVIEW COMMENTS FROM BUILDING. |
| | |
| | 3) NOTE: PLEASE SEE MANY TITLE BLOCKS ON |
| | SAID PLANS ARE MISSING ALL INFORMATION |
| | AS REQUIRED UNDER FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.004 FOR ARCHITECTURAL |
| | FIRM(S) AND 61G15-23.002 FOR ENGINEERING |
| | FIRMS. PLEASE SEE ONLY ONE FIRM AS SHOWN |
| | ON TITLE BLOCKS CONTAINS THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. FLORIDA STATUES |
| | 481.219, 471.023 |
| | PLEASE ALSO SEE OTHER INFORMATION |
| | MISSING, THE PRINTED NAME AND LICENSE |
| | NUMBER FOR THE DESIGN PROFESSIONAL. |
| | PLEASE SEE THIS IS SHOWN FOR HNGS. |
| | * PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE BE SURE ALL THE CURRENT |
| | CODES ARE REFERENCED ON PLANS. PLEASE BE |
| | SUE THE FOLLOWING ARE SHOWN AND DESIGNS |
| | ARE SHOWN ACCORDINGLY. |
| | NFPA-20 (2002), NFPA-110 (2002), |
| | NFPA-101 (2003), NFPA-70 (2002), NFPA-72 |
| | (2002). |
| | PLEASE SEE THERE ARE MANY LOCATIONS ON |
| | PLANS WHICH REFERENCES REQUIREMENTS FROM |
| | THE 1996 NATIONAL ELECTRICAL CODE |
| | NFPA-70. |
| | PLEASE SEE NOTES ETC. |
| | |
| | 5) NOTE: PLEASE SEE COLOR CODING OF |
| | 277/480V SYSTEMS SHALL BE "BROWN, |
| | PURPLE, AND YELLOW". ORANGE IS ONLY FOR |
| | HIGH-LEG SYSTEMS AND IS NOT PERMITTED |
| | FOR 277/480V. |
| | 215, 90.4. |
| | |
| | 6) NOTE: PLEASE KNOW, "LIGHTNING |
| | PROTECTION"SYSTEM AS SHOWN IF |
| | INSTALLED BY A SUB CONTRACTOR WILL |
| | REQUIRED THIS TO BE PULLED UNDER A |
| | SEPARATE PERMIT.PLANS INDICATE "BONDED |
| | LIGHTNING" AS THIS SUB. |
| | |
| | 7) NOTE: PLEASE SUBMIT WIND LOAD |
| | CALCULATIONS FOR ALL SITE LIGHTING POLES |
| | INCLUSIVE OF ATTACHED LIGHT FIXTURES. |
| | PLEASE KNOW, THIS SHOULD INCLUDE ANY |
| | POLE FIXTURES ON POOL DECK/ROOF |
| | LEVEL(S). |
| | |
| | 8) NOTE: PLEASE SHOW AND INDICATE ALL |
| | ROOM/AREA DESIGNATIONS ON PLANS. |
| | PLEASE SEE SOME AREAS ARE UNCLEAR FOR |
| | USE. |
| | PLEASE SEE ONE OF THESE AREAS APPEARS TO |
| | SHOW ACCESS TO THE TRASH SHOOT THROUGH |
| | ONE OF THE ELECTRICAL ROOMS ON |
| | MEZZ/FIRST FLR. PLEASE SEE BUILDING |
| | REVIEW COMMENTS FOR THIS. PLEASE KNOW, |
| | ACCESS THROUGH THIS ELECTRICAL ROOM IS |
| | NOT PERMITTED. 110.26, 110.27, 240.4 |
| | ETC. |
| | |
| | 9) NOTE:PLEASE SEE NFPA-110 7.2.3* |
| | WITH RESPECT TO THE LOCATION OF |
| | GENERATORS AND ELEVATION. PLEASE SEE |
| | EXPLANATION OF THIS REQUIREMENT WHICH |
| | REQUIRES THE MIN AS SET PER THE ?SLOSH? |
| | PREDICTION. (SEA, LAKE, OVERLAND, |
| | SURGES, FROM HURRICANES.) |
| | |
| | 10) NOTE: PLEASE KNOW, DOORS FOR |
| | ELECTRICAL ROOMS, GENERATOR ROOM, AND |
| | FIRE PUMPS ROOMS WILL BE REQUIRED TO |
| | OPEN OUTWARD IN THE DIRECTION OF EGRESS. |
| | PLEASE KNOW THE MAIN ELECTRICAL ROOMS |
| | AND GENERATOR ROOM WILL REQUIRED PANIC |
| | HARDWARE ON DOORS. 110.26. |
| | PLEASE BE SURE TO SEE ANY INTERFERENCE |
| | WITH MINIMUM EGRESS WIDTHS IN HALL |
| | OUTSIDE THE MAIN ELECTRICAL ROOMS. |
| | |
| | 11) NOTE: PLEASE LABEL MAINS 1 OF 5, 2 |
| | OF 5 ETC PLEASE SEE MAINS AS SHOWN MAY |
| | LEAD TO SOME CONFUSION IN ORDER TO SHUT |
| | DOWN BLDG IN CASE OF AN EMERGENCY. |
| | PLEASE KNOW, THESE MAINS SHOULD ALSO BE |
| | IDENTIFIED FOR EACH SECTION /USE OF SHUT |
| | DOWN. FLOORS 1-13 , 13-26, HOUSEPOWER, |
| | EM ETC. |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE 110.26 FOR MINIMUM |
| | CLEARANCES REQUIRED FOR ALL ELECTRICAL |
| | EQUIPMENT IN ELECTRICAL ROOMS.PLEASE |
| | SEE ENLARGE ELECTRICAL ROOM PLAN SEEMS |
| | TO NOT SHOW THE MIN. CLEARANCE FOR DPE. |
| | PLEASE ALSO PROVIDE A NOTE ON E-4.01 FOR |
| | ALL CLEARANCES TO MEET 110.26, NO |
| | EXCEPTIONS. |
| | |
| | 13) NOTE: PLEASE SEE SEF PANEL SHALL BE |
| | LABELED AS ONE OF THE EMERGENCY MAINS |
| | FROM GENERATOR. |
| | 215.5, 230.2,230.72 ETC |
| | |
| | 14) NOTE: PLEASE SEE DPE SHALL CONTAIN A |
| | MCB IN THE EVENT OF SHUTTING DOWN OF |
| | POWER ON THE EM SIDE OF GENERATOR. |
| | 230.76, 230.72, 230.79 ETC. |
| | ACCESS TO GENERATOR ROOM TO QUALIFIED |
| | PERSONNEL DURING AN EMERGENCYTO SHUT |
| | DOWN POWER TO DPE DURING THEOPERATION |
| | OF THIS GENERATORPOSES A CONCERN TO |
| | THIS OFFICE AND FIRE MARSHAL'S OFFICE. |
| | "PLEASE KNOW,"SHUNT TRIPS"ARE NOT |
| | PERMITTED AS THE MEANS OF DISCONNECT , |
| | HOWEVER MAY BE INSTALLED AND LABELED |
| | ACCORDINGLY IN MAIN ELECTRICAL ROOM OR |
| | FIRE COMMAND ROOM. |
| | |
| | 15)NOTE:PLEASE PROVIDE A DETAIL FOR |
| | GATES UNDER POWER FAILURE FOR ACCESS |
| | INTO AND EGRESS OUT OF BLDG. THESE MAY |
| | BE PERMITTED SEPARATELY, HOWEVER A NOTE |
| | FOR A MIN SHOULD BE PROVIDED AT THIS |
| | TIME. |
| | |
| | 16) NOTE:PLEASE PROVIDE AN EMERGENCY |
| | BATTERY BACK UP FIXTURE OF SOME TYPE IN |
| | ALL ELEVATOR EQUIPMENT ROOMS. |
| | 700.16, LS101 7.8, 7.9 |
| | |
| | 17) NOTE: PLEASE SEE 620.22, 620.23, AND |
| | 620.24 FOR ALL MINIMUM REQUIRED |
| | DEDICATED BRANCH CIRCUITS. PLEASE SEE |
| | SOME APPEAR TO SHARE WITH OTHER AREAS |
| | BESIDES ONLY THE ELEVATOR EQUIPMENT |
| | ROOMS. |
| | ALL ROOMS SHALL CONTAIN THEIR OWN |
| | DEDICATED CIRCUITS AND MAY NOT FEED |
| | OTHER ROOMS OR OTHER COMMON ARES. |
| | |
| | 18) NOTE: PLEASE CLARIFY AS IT APPEARS |
| | ONLY ONE ELEVATOR PIT INDICATES SUMP |
| | PUMP CIRCUIT? |
| | PLEASE SHOW OTHER PIT CIRCUIT(S). |
| | |
| | 19) NOTE: PLEASE SEE FBC 2004 CHAPTER 13 |
| | FOR MEANS OF CONTROL REQUIRED FOR |
| | EXTERIOR LIGHTING. PLEASE PROVIDE AREA |
| | CALCULATIONS AS SET FORTH. |
| | 13-415.1.ABC.2 |
| | |
| | 20) NOTE: PLEASE SEE 13-415.1.ABC.1.1 & |
| | .2 FOR CONTROL OF INTERIOR LIGHTS. |
| | PLEASE KNOW, ALL ROOMS NOT IN USE FOR |
| | 24HR OPERATION SHALL CONTAIN MEANS OF |
| | BEING AUTOMATICALLY TURNED OFF.PLEASE |
| | KNOW, THIS INCLUDES ANY STORAGE, |
| | MECHANICAL, CLOSETS ETC. |
| | PLEASE SEE OTHER NEW REQUIREMENTS OF |
| | CHAPTER 13. |
| | |
| | 21) NOTE: PLEASE COMPLETE CIRCUITING ON |
| | PLANS, STAIRS ETC. PLEASE SEE SOME STAIR |
| | TOWERS SHOWN FIXTURES, HOWEVER CIRCUIT |
| | IS NOT SHOWN? |
| | 215.5 |
| | |
| | 22) NOTE:PLEASE PROVIDE COMPLETE |
| | PHOTO-METRICS FOR ALL CORRIDORS, EGRESS |
| | PATHS, STAIR TOWERS. |
| | PLEASE SEE 2003 NFPA-101 7.8 AND 7.9, |
| | THIS REQUIRES A MIN OF 10 FT CANDLES |
| | FOR STAIRS UNDER NORMAL POWER AND A |
| | MINIMUM |
| | OF 1 FT CANDLE UNDER EM POWER. |
| | PLEASE ALSO KNOW THAT BATTERY BACK UP |
| | FIXTURE IS ALREADY BEING SHOWN IN STAIR |
| | TOWERS. |
| | PLEASE KNOW THIS MAY BE A "TYPICAL" |
| | DETAIL FOR THESE AREAS. PLEASE SEE THAT |
| | SOME SORT BATTERY BACK UP FIXTURE WILL |
| | BE REQUIRED TO PROVIDE A MIN AMOUNT OF |
| | LIGHT IN HALLWAYS AND GARAGE ARE IN THE |
| | EVENT OF THE TRIPPING OF THE SINGLE |
| | MEANS OF OCP ON THE EM SIDE OF SYSTEM. |
| | PLEASE SEE OTHER AREAS BESIDES STAIRS |
| | SHALL BE PERMITTED TO PROVIDE 1FT CANDLE |
| | (AVERAGE) UNDER NORMAL AND EMERGENCY. |
| | PLEASE SEE 7.9 WHICH REQUIRES THIS |
| | TO ALLEVIATE ANY ONE AREA BEING IN |
| | TOTAL DARKNESS UPON THE TRIPPING OF A |
| | SINGLE DEVICE, SWITCH, BRKR ETC. |
| | |
| | 23) NOTE:PLEASE SEE THAT ANY AFTER |
| | DUSK BEFORE DAWN SWIMMING WILL REQUIRE |
| | PHOTO-METRICS FOR POOL AREA(S). PLEASE |
| | KNOW, ALL PHOTO-METRICS WILL BE REQUIRED |
| | TO BE SUBMITTED TO PALM BEACH COUNTY |
| | HEALTH DEPARTMENT FOR REVIEW AND |
| | STAMPING. ONLY THE STAMPED PLANS/SHEETS |
| | FROM PBCHD SHOULD BE SUBMITTED. |
| | |
| | 24) NOTE: PLEASE SEE NFPA-1107.3.3* |
| | THE INTENSITY OF ILLUMINATION IN THE |
| | ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL |
| | 1 SHALL BE 32.3 LUX (30 FT-CANDLES). |
| | PLEASE SHOW DETAIL. |
| | |
| | 25) NOTE: PLEASE SEE NFPA-110 7.7 FOR |
| | EPS VENTILATION. PLEASE SEE LOADING DOCK |
| | AREA IS BEING SHOWN AS THE AIR INTAKE |
| | FOR THE GENERATOR WHICH SHOWS A DOOR TO |
| | CLOSE OFF THIS ARE TO OUTSIDE AIR. |
| | PLEASE SEE 7.7.2.1 FOR EPS SUPPLYING |
| | LEVEL 1 EPSS, VENTILATION AIR SHALL BE |
| | SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE |
| | OF THE BUILDING BY AN EXTERIOR WALL |
| | OPENING OR FROM A SOURCE OUTSIDE THE |
| | BUILDING BY A 2-HOUR FIRE RATED AIR |
| | TRANSFER SYSTEM. |
| | PLEASE SEE BUILDING REVIEW COMMENTS AS |
| | WALLS/ LOUVERS AS SHOWN SEEM TO CREATE |
| | AN ISSUE FOR THE MIN 2 HR RATING. |
| | |
| | 26) NOTE: PLEASE PROVIDE AIC RATINGS FOR |
| | ALL EPS EQUIPMENT. (ATS). PLEASE SEE |
| | 6.5.2 NFPA-110. |
| | UNABLE TO VERIFY AT THIS TIME. |
| | |
| | 27) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR ALL EQUIPMENT: |
| | ATS?S, GENERATOR, FIRE PUMP FIRE PUMP |
| | CONTROLLER, SUB-BASE FUEL TANK ETC. |
| | PLEASE SEE OTHER COMMENTS AND KNOW THAT |
| | MANY ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE REVIEW AT THIS TIME DUE TO THESE |
| | ITEMS NOT BEING SUBMITTED FOR REVIEW. |
| | |
| | 28) NOTE: PLEASE SEE NFPA-20 9.6.2.2 |
| | WHICH REQUIRES A MIN OF 8HRS RUNNING @ |
| | 100% LOAD FOR FIRE PUMP. PLEASE ALSO |
| | BEAR IN MIND THE MINIMUM 100% LOADS FOR |
| | ALL OTHER LEGALLY REQUIRED STAND-BY |
| | ITEMS. |
| | |
| | 29) NOTE: PLEASE SEE NFPA-20 7.2FOR |
| | LOCATION OF FP CONTROLLER, HEIGHT, NEMA |
| | TYPE 2 ENCLOSURES AND ROOM CONTAINING A |
| | FLOOR DRAIN. |
| | |
| | 30) NOTE:PLEASE NOTE ON PLANS THE |
| | ACCEPTANCE OF THE EPS AS REQUIRED IN |
| | NFPA-110 7.13. |
| | THE SYSTEM SHALL BE TESTED AS REQUIRED |
| | BEFORE CERTIFICATE OF OCCUPANCY OR |
| | TEMPORARY CO. |
| | |
| | 31) NOTE: PLEASE SEE SQUARES LOCATED ON |
| | PLANS SEEM TO REFERENCE NOTES, HOWEVER |
| | PLEASE SEE THESE NOTES SHOULD BE LABELED |
| | AS TYPICAL ON ALL SHEETS WITH THESE |
| | "SQUARES" REFERENCING THESE. |
| | |
| | 32) NOTE: PLEASE SEE PLANS INDICATE A |
| | ?GENERATOR ROOM? FOR GYM/ SPA AREA. THIS |
| | SEEMS IT SHOULD BE LABELED AS ?STEAM |
| | GENERATOR ROOM. |
| | 215.5 |
| | |
| | 33) NOTE:PLEASE COMPLETE FIXTURE |
| | SCHEDULE AND CORRELATE WITH PLANS. |
| | PLEASE SEE SOME FIXTURES ARE NOTED ON |
| | PLANS AS BEING CHOSEN BY ARCHITECT OR |
| | THEY ARE NOT NOTED AT ALL. A FIXTURE |
| | TYPE OF SOME SORT SHOULD BE INDICATED AT |
| | THIS TIME. THIS CAN BE CHANGE OR REVISED |
| | LATER. PLEASE SEE ANY ADJUSTMENT IN |
| | FIXTURE SCHEDULE SHOULD BE UPDATED |
| | PENDING ANY CHANGES IN EM/EXT LTS. |
| | |
| | |
| | |
| | 34) NOTE: PLEASE SEE NOTE TO BE PROVIDED |
| | ON ALL E-2.09AB FOR MINIMUM CLEARANCES |
| | FOR POOL AREA FIXTURES. PLEASE 680.22 |
| | FOR HIGH VOLTAGE FIXTURES (5FT MIN W/ |
| | GFI PROTECTION AND 10FT MIN FOR LOW |
| | VOLTAGE TYPE FIXTURES. 411.4 |
| | |
| | 35) NOTE: PLEASE SEE 680.22 FOR GFI |
| | RECEPTACLES TO BE LOCATED A MIN OF 20? |
| | OF POOL. PLEASE ALSO SEE EXCEPTION WITH |
| | RESPECT PH-L3 UNITS. |
| | |
| | 36) NOTE: PLEASE PROVIDE NOTE ON PLANS |
| | WHICH PROHIBITS THE INSTALLATION OF ANY |
| | ELECTRICAL CONDUITS ETC IN STAIRS UNLESS |
| | SPECIFICALLY DESIGNATED TO THE STAIRS. |
| | PLEASE ALSO PROVIDE NOTE FOR ELEVATOR |
| | EQUIPMENT ROOMS. |
| | 215.5 |
| | |
| | 37) NOTE: PLEASE SEE ENLARGED ELEVATOR |
| | EQUIPMENT ROOMS, SOME ITEMS DO NOT SEEM |
| | TO CORRELATE. |
| | |
| | 38) NOTE: PLEASE PROVIDE ROOM AND AREA |
| | DESIGNATIONS ON ALL UNIT PLANS. |
| | PLEASE BE SURE TO ADDRESS "DINING AREAS" |
| | AS CIRCUITING IS TO BE VERIFIED. PLEASE |
| | SEE OTHER COMMENT WHICH THIS AFFECTS. |
| | |
| | 39) NOTE: PLEASE PROVIDE VOLTAGE DROP |
| | ANALYSIS FOR ALL FEEDERS AND BRANCH |
| | CIRCUITS. THIS MAY BE A WORST CASE |
| | SCENARIO FOR EACH. PLEASE SEE FBC |
| | CHAPTER 13, 13-413.1.ABC.1.1, &.2. |
| | |
| | 40) NOTE: PLEASE SEE FAIR HOUSING ACT |
| | REGULATIONS, 24 CFR 100.205 WITH RESPECT |
| | TO HEIGHTS AND LOCATIONS FOR ALL |
| | ACCESSIBLE DEVICES. |
| | PLEASE SEE SOME ITEMS ON PLANS ARE SHOWN |
| | TO EXCEED THE MAX OF 48?. |
| | |
| | 41) NOTE: PLEASE SEE CODES NOTE #12 WITH |
| | RESPECT TO LOCATIONS OF SMOKE DETECTORS. |
| | PLEASE SEE 2002 NFPA-72 11.5.1.1, |
| | 11.5.8.3.5. |
| | SD'S ARE TO BE LOCATED A MIN OF 3FT FROM |
| | KITCHEN AND BATH DOORS AND A MIN OF 20FT |
| | FROM COOKING APPLIANCES. (WITH |
| | EXCEPTIONS TO THE DISTANCE FROM COOKING |
| | APPLIANCES. |
| | PLEASE ADJUST THIS "CODES NOTE". |
| | |
| | 42) NOTE: PLEASE SEE NFPA-72 WHICH |
| | REQUIRES ALL SD'S TO BE WIRED "IN-LINE". |
| | PLEASE SEE NUMEROUS UNITS WHERE THE SD?S |
| | ARE WIRED UP TO AS MANY AS 7 INDIVIDUAL |
| | CIRCUITS. THIS IS NOT POSSIBLE WHEN THEY |
| | ARE ALL REQUIRED TO BE WIRED INLINE. |
| | PLEASE ADJUST CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES |
| | SUBMITTED. PLEASE ALSO SEE THE FOLLOWING |
| | COMMENT. |
| | |
| | 43) NOTE: PLEASE SEE 210.12 IN THE 2002 |
| | NEC WHICH REQUIRES ARC FAULT PROTECTION |
| | FOR ALL "OUTLETS" ( SD'S, LTS, FANS, |
| | RECEPTS ETC.)IN BEDROOMS. PLEASE SEE |
| | SOME CIRCUITING ON PLANS DOES NOT |
| | INDICATE ARC FAULT PROTECTION FOR SOME |
| | ITEMS SHOWN IN THE SLEEPING ROOMS. |
| | PLEASE SEE SD'S CIRCUITED ON PLANS WHICH |
| | SOME OF THESE CIRCUITS ON PANEL |
| | SCHEDULES, WHICH DO NOT SHOW AFCI BRANCH |
| | CIRCUIT PROTECTION. |
| | |
| | 44) NOTE: PLEASE SEE PLANS SEEM TO |
| | INDICATE ONLY A "J-BOX" FOR DISHWASHER |
| | AND DISPOSAL WHICH LENDS TO THESE |
| | APPLIANCES NOT BEING INSTALLED UNDER THE |
| | PERMIT FOR THIS BUILDING? PLEASE VERIFY, |
| | IF INDEED THESE APPLIANCES ARE BEING |
| | INSTALLED, THEN THE RECEPTACLES WOULD BE |
| | REQUIRED TO BE SHOWN ON PLANS. |
| | |
| | 44) NOTE: PLEASE SEE LV PANEL LOCATIONS |
| | SHOWN IN CLOSETS MAY NOT BE PERMITTED IF |
| | CONTAINING OCP. PLEASE KNOW, THE |
| | RECEPTACLES AS SHOWN ON ELECTRICAL PLANS |
| | IN CLOSETS IN CLOSE PROXIMITY OF |
| | SHELVING AND/OR STORAGE WILL NOT BE |
| | PERMITTED FOR ANY "PLUG-IN" TYPE |
| | TRANSFORMERS. PLEASE KNOW, THIS |
| | JURISDICTION HAS HAD MANY SCENARIO?S |
| | WHERE THE HEATING AND OR MELTING OF THE |
| | PLUG-IN TYPE TRANSFORMER HAS CAUSED |
| | FIRES. PLEASE KNOW THIS IS A LIFE SAFETY |
| | AND PROPERTY HAZARD AND LOCATIONS OF |
| | THESE UNITS/DEVICES WILL NEED TO BE |
| | ADJUSTED. |
| | * PLEASE KNOW, IT IS NOTED THAT MANY OF |
| | THE UNITS DO NOT SHOW THESE LOCATED IN |
| | CLOSETS AND DO NOT NEED TO BE MOVED. |
| | 240.24,110.26 ETC |
| | |
| | 45) NOTE: PLEASE VERIFY UNIT BALCONIES, |
| | AS UNITS DO NOT SHOW ANY LIGHTING OR |
| | RECEPTACLES ALL THE WAY UP TO THE PH |
| | UNITS?? |
| | THIS IS ONLY A NOTE AS UNLESS THESE |
| | BALCONIES CONTAIN DIRECT GRADE LEVEL |
| | ACCESS, LIGHTING IS NOT REQUIRED. PLEASE |
| | REVISE IF ANY OF THESE ARE INDEED GOING |
| | TO CONTAIN LTS ETC. |
| | |
| | 46) NOTE: PLEASE SEE PLANS WHICH |
| | MENTIONS "THEATRE" AND NOTES |
| | ACCORDINGLY. PLEASE SEE NOTES MENTIONS |
| | "STEP-LTS" WHICH COULD NOT BE LOCATED ON |
| | PLANS? |
| | PLANS ALSO INDICATE THIS ARE AS A |
| | "MULTI-PURPOSE" ROOM?PLEASE CLARIFY |
| | USE. |
| | |
| | 47) NOTE: PLEASE PROVIDE EMERGENCY |
| | LIGHTING FOR EGRESS TO THE PUBLIC RIGHT |
| | OF WAY. PLEASE SEE THE BREEZEWAY AREAS/ |
| | DRIVE AREA WHICH MAY BE USED AS AN |
| | EGRESS PATH WAY. |
| | LS 101-7.8,7.9 |
| | |
| | 48) NOTE: PLEASE SEE NFPA-72 11.8.3.5 |
| | WHICH REQUIRES THE UNIT SMOKE DETECTORS |
| | TO BE LOCATED ON THE LOWER LEVEL OF A |
| | MULTI-STORY DWELLING UNIT AND IN CLOSE |
| | PROXIMITY LEADING TO THE FLOOR ABOVE. |
| | PLEASE SEE SOME OF THESE ARE LOCATED |
| | AWAY FROM THIS AREA. |
| | |
| | 48) NOTE: PLEASE SEE MISSING CIRCUITING |
| | ON MANY OF THE SMOKE DETECTORS SHOWN ON |
| | PLANS. |
| | PLEASE COMPLETE. PLEASE ALSO SEE |
| | PREVIOUS NOTES ABOVE WITH RESPECT TO THE |
| | CIRCUITING AND AFCI. |
| | 215.5 |
| | |
| | 49) NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS OUTSIDE SLEEPING ROOMS. |
| | NFPA-72 11.5.1.1 |
| | |
| | 50) NOTE: PLEASE SEE 210.52 FOR |
| | RECEPTACLE SPACING INSIDE DWELLING UNITS |
| | FOR 2 FT, 6FT AND 12 FT RULE. |
| | PLEASE SEE UNIT LAYOUT AS MANY OF THESE |
| | HAVE BEEN REDLINED. |
| | |
| | 51) NOTE: PLEASE SEE MANY UNITS ARE |
| | SHOWING "J-BOXES" FOR THE REQUIRED MEANS |
| | OF EGRESS LIGHT FIXTURE REQUIRED. PLEASE |
| | SEE 210.70, AND LS 101 7.8 |
| | PLEASE SEE A MIN OF ONE FIXTURE OF SOME |
| | TYPE WILL BE REQUIRED FOR THESE AREAS. |
| | HALL, DINING, LIVING AREAS ETC. |
| | |
| | 52) NOTE: PLEASE SEE 210.52C2,4 FOR |
| | ISLANDS AND SEPARATE COUNTER SPACES |
| | WHICH REQUIRED ADDITIONAL GFI RECETPS. |
| | |
| | 53) NOTE: PLEASE SEE 210.52C1 FOR |
| | COUNTER SPACES ALONG WALLS AND |
| | 210.52C3,4 FOR PENINSULA'S. PLEASE SEE |
| | WALL SPACES BELOW SOME OF THESE |
| | PENINSULAR LOCATIONS MAY REQUIRE RECEPTS |
| | AS THESE APPEAR TO BE WALL SPACES. |
| | PLEASE SEE 210.8A6 AS ALL RECEPTACLES |
| | SERVING KITCHEN COUNTER SPACES SHALL BE |
| | GFI/GFI PROTECTED. |
| | |
| | 54) NOTE: PLEASE SEE WHAT APPEARS TO |
| | MISSING "WALLS" IN UNIT 2A-3.05. |
| | |
| | 55) NOTE: PLEASE SEE WHAT APPEARS TO BE |
| | A SHIFT IN PLANS IN UNIT "3A". 3.06 |
| | |
| | 56) NOTE: PLEASE SEE CIRCUITING FOR |
| | DINING ROOMS AND AREAS OF THE LIKE SHALL |
| | BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. PLEASE SEE ALMOST ALL OF THE |
| | DINING AREAS SHOWN CONTAIN CIRCUITS |
| | WHICH ARE 15A AND #14 AWG. 210.52B1 |
| | PLEASE ADJUST CIRCUITS, CONDUCTOR SIZES |
| | AND SEE PREVIOUS NOTE WITH RESPECT TO |
| | ROOM AND AREA DESIGNATIONS. |
| | |
| | 57) NOTE: PLEASE SEE MISSING HALL |
| | RECEPTACLE FOR HALLS CONTAINING 10FT OR |
| | MORE OF CONTINUOUS WALL SPACE. |
| | 210.52H |
| | |
| | 58) NOTE: PLEASE SEE UNIT PANELS WHICH |
| | INDICATE 12KW FOR RANGE LOADS AND LOAD |
| | CALCULATIONS INDICATE 10KW. |
| | PLEASE CORRELATE 215.5 |
| | |
| | 59) NOTE: PLEASE SEE A 60A BREAKER |
| | FEEDING WHAT WOULD BE A 50A RATED DEVICE |
| | FOR RANGE. PLEASE SEE THIS DOES NOT |
| | CORRELATE WITH LOAD CALCULATIONS AS |
| | CALCULATIONS SHOW A LOWER LOAD. PLEASE |
| | SEE NOTE ABOVE AND CORRELATE LOADS AT |
| | 208V. |
| | PLEASE SEE 210.21B3 |
| | |
| | 60) NOTE: PLEASE CORRELATE PANEL FOR |
| | PH-L3 AS SOME AREAS OF PLANS MENTIONS |
| | THIS AS 225A WITH LOADS EXCEEDING THIS |
| | RATING. PLEASE SEE OTHER AREAS OF PLANS |
| | WHICH INDICATE THIS PANEL AS 400A. |
| | PLEASE ALSO INDICATE IF SECTION ONE |
| | CONTAINS FEED-THRU LUGS. |
| | PLEASE SEE METER CENTERRISER ETC. |
| | 215.5, 240.4, 408,310.16 ETC |
| | |
| | 61) NOTE: PLEASE VERIFY LABELING OF |
| | UNITS AND PANELS, AS SOME AREAS SHOW |
| | "A-1" AND OTHER ?1-A?, AND OTHER UNITS |
| | AND PANELS. |
| | |
| | 62) NOTE: PLEASE SEE FEEDERS SHOWN AT |
| | 250MCM FOR WHAT APPEARS TO BE 400A PANEL |
| | AND 400A OCP FOR PH-L3?? |
| | 240.4, 310.16 |
| | |
| | 63) NOTE: PLEASE SEE 4.05 MENTIONS ONE |
| | A/C SYSTEM FOR PH-L3 WITH 70A OCP, YET |
| | PANEL SCHEDULE FOR THIS UNIT SHOWS 2 |
| | SYSTEMS. PLEASE VERIFY THIS AND ADJUST |
| | ACCORDINGLY. |
| | |
| | |
| | 64) NOTE: PLEASE PROVIDE THE PANEL |
| | SCHEDULE FOR EACH UNIT AND CORRELATE |
| | WITH CIRCUITING FOR EACH UNIT AS THE |
| | CIRCUITING SHOWN DOES NOT CORRELATE TO |
| | ALL UNITS AND TYPE OF PANEL FOR EACH |
| | UNIT. |
| | EACH UNIT SHOULD INDICATE LOADS, OCP AND |
| | CIRCUITING. |
| | 215.5 |
| | |
| | 65) NOTE: PLEASE SEE METER CENTER RISER |
| | WHICH INDICATES A 150A BREAKER FEEDING |
| | PH-L3, WHICH IS 400A?S ETC. PLEASE |
| | CORRELATE AND SEE NOTE ABOVE. |
| | 215.5 |
| | |
| | 66) NOTE: PLEASE CORRELATE LOAD FOR WHAT |
| | IS SHOWN AS A POOL HEATER FOR PH-L3 ON |
| | LOAD CALCULATIONS, HOWEVER THIS IS NOT |
| | ON PANEL SCHEDULE? |
| | 215.5 |
| | |
| | 67) NOTE: PLEASE CORRELATE LOADS FOR |
| | OTHER APPLIANCES. PLEASE SEE DISPOSAL |
| | 800VA ON ONE AND 700VA ON THE OTHER. |
| | 215.5 |
| | |
| | 68) NOTE:PLEASE SEE WHAT APPEARS TO BE |
| | A NOTE ON PANEL SCHEDULES FOR ARC FAULT |
| | PROTECTION; HOWEVER THIS SYMBOL DOES NOT |
| | SEEM TO CORRELATE WITH REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. |
| | 210.12 |
| | |
| | 69) NOTE: PLEASE CORRELATE DISHWASHER |
| | LOADS, AS LOAD CALCULATIONS SHOW 800VA |
| | AND PANEL SCHEDULES SHOW 1200VA. |
| | 215.5 |
| | |
| | 70) NOTE: PLEASE CORRELATE WATER HEATER |
| | SHOWN FOR A-3 OR 3A? 4.5KVA OR 6KVA? |
| | |
| | 71) NOTE: PLEASE SEE UNIT PHL2 STAIR |
| | LAYOUTS DO NOT SEEM TO CORRELATE WITH |
| | EACH FLOOR AND LOCATION OF ABOVE 2ND |
| | FLOOR. |
| | 215.5 |
| | |
| | 72) NOTE: PLEASE SEE PHL-1 FOR LIVING |
| | ROOM NEXT TO KITCHEN BAR AREA AND |
| | CIRCUITING. |
| | 210.52B1 |
| | |
| | 73) NOTE: PLEASE SEE PHL-4 AND LAYOUTS |
| | TO CORRELATE. |
| | |
| | 74) NOTE: PLEASE SEE PHL-5 , IT IS |
| | UNCLEAR WHICH SIDE OF STAIR IS UP? |
| | |
| | 75) NOTE: PLEASE SEE UNIT PHL-7 WHICH |
| | APPEARS TO SHOW THE PANEL LOCATED UNDER |
| | STAIRS? PLEASE SEE 110.26, 240.24 ETC |
| | IS THIS ARE OPEN? PLEASE ALSO SEE |
| | PREVIOUS COMMENTS FOR WALL SPACE IN THIS |
| | SAME AREA. |
| | |
| | 76) NOTE: PLEASE SEE MINIMUM CLEARANCE |
| | FOR 277/480V. |
| | PLEASE SEE 110.26 |
| | |
| | 77) NOTE: PLEASE CLARIFY AND CORRELATE |
| | PLANS, RISER AND ELECTRICAL ROOM?S |
| | LAYOUT AS ELECTRICAL ROOM #7 COULD NOT |
| | BE LOCATED ON ?ENLARGED? ELECTRICAL ROOM |
| | LAYOUT. |
| | 215.5 |
| | |
| | 78) NOTE: PLEASE BE SURE TO CORRELATE |
| | ALL UNIT LOADS FOR A/C UNITS AND NEW |
| | PANEL SCHEDULES TO BE PROVIDED. 215.5 |
| | |
| | 79) NOTE: PLEASE SEE SOME FIXTURES IN |
| | COMMON AREAS WHICH SEEM O INDICATE THE |
| | SAME FIXTURE LABEL; HOWEVER THE SYMBOL |
| | IS NOT THE SAME? PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 80) NOTE: PLEASE SEE FIRE ALARM SHEETS |
| | WHICH REFLECT CODES FROM THE SFBC. |
| | PLEASE ADJUST PER 2004 FBC AND NFPA-72 |
| | |
| | 81) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM SHOWS DETAIL AND CODE FROM THE |
| | 1996 NEC/ NFPA-72. PLEASE ADJUST. |
| | |
| | 82) NOTE: PLEASE COMPLETE THE COMMON |
| | GROUNDING ELECTRODE ON RISER DIAGRAM. |
| | THIS MAY BE IN LIGHT GRAY OR DASHED |
| | LINES FOR ALL REQUIRED ATTACHMENTS PER |
| | 250.50, 250.58 |
| | |
| | 83) NOTE: PLEASE COMPLETE ALL |
| | TRANSFORMER ATTACHMENT LOCATIONS. PLEASE |
| | SEE SOME ARE SHOWN BEING CONNECTED TO |
| | THE BUILDINGS GROUNDING ELECTRODE |
| | SYSTEM, OTHERS ARE NOT. |
| | 250.30, 215.5. |
| | |
| | 84) NOTE: PLEASE SEE RISER SHOWS MAINS |
| | ONE , TWO AND SWBD BEING FED FROM |
| | OVERHEAD ON RISER, HOWEVER ELECTRICAL |
| | ROOM LAYOUT/ PLANS INDICATE THESE AS |
| | BEING FED BACK TO BACK WITH FPL VAULT. |
| | (BUS-STAB?). PLEASE KNOW, NOT MORE THAN |
| | 8? OF UNPROTECTED CONDUCTORS OR BUS DUCT |
| | IS PERMITTED INSIDE THE BUILDING.230.70, |
| | 230.71 |
| | |
| | 85) NOTE: PLEASE CORRELATE RISER AND |
| | 6.01. ONE SHOWS SWBD AND THE OTHER |
| | SWGRA? |
| | 215.5 |
| | |
| | 86) NOTE: PLEASE CORRELATE THE NUMBER OF |
| | PANEL AND UNITS ON RISER DIAGRAM WITH |
| | THE NUMBER OF UNITS SHOWN ON METER |
| | CENTER RISER/ SCHEDULE. |
| | PLEASE SEE ALL FLOORS SHOW DIFFERENT |
| | NUMBER OF UNITS FOR EACH. |
| | 215.5 |
| | A) PLEASE SEE MC 16, SHOWS 16 ON RISER |
| | AND 18 ON METER CENTER SCHEDULE. |
| | B) PLEASE SEE MC # 15 SHOWS 13 ON METER |
| | SCHEDULE AND 14 ON RISER. |
| | C) PLEASE SEE MC #14, SHOWS 19 ON RISER |
| | AND 18 ON METER CENTER SCHEDULE. |
| | D) PLEASE SEE MC #13 SHOWS 20 ON RISER |
| | AND 19 ON MC SCHEDULE. |
| | E) PLEASE SEE MC #12, SHOWS 19 ON RISER |
| | AND SHOWS 18 ON SCHEDULE. |
| | |
| | *** PLEASE SEE ALL OTHERS AND CORRELATE |
| | AS MOST OF THESE DO NOT MATCH. |
| | 215.5 |
| | |
| | 87) NOTE: PLEASE SPECIFY ALL AIC RATINGS |
| | FOR ALL EQUIPMENT. PLEASE PROVIDE |
| | RATINGS FOR ANY FUSE AS INDICATED. |
| | PROVIDE RATINGS ON CURRENT LIMITING |
| | FUSES AS NOTED. 110.9, 215.5 |
| | |
| | 88) NOTE:PLEASE KNOW, IF 1000A'S, GFP |
| | SENSING WILL BE REQUIRED ON SECONDARY |
| | SIDE, GFP WILL BE REQUIRED ON MAIN ALSO |
| | AS NOTED |
| | PER 240.13,230.95. |
| | PLEASE SEE 700.7D, 700.26, 701.9D |
| | PLEASE SEE TEXT TAKEN DIRECTLY FROM ASCO |
| | MANUFACTURE WRITTEN DIRECTIVE FOR EPSS |
| | SYSTEMS. WHERE AS A 4-POLE ATS MAY BE |
| | REQUIRED FOR THE |
| | CORRECT COORDINATION OF ELECTRICAL |
| | SYSTEMS. |
| | "WHERE GROUND FAULT PROTECTION IS |
| | TRIGGERED BY THE CODE AND AN ALTERNATE |
| | POWER SUPPLY IS INCLUDED,SWITCHING OF |
| | THE NEUTRAL BECOMES NECESSARY. THE |
| | CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A |
| | CIRCUMSTANCE. THE SERVICE IS LARGER THAN |
| | 1,000 AMPS. CONSEQUENTLY, GROUND FAULT |
| | PROTECTION IS REQUIRED AT THE MAIN |
| | SERVICE DISCONNECT AT A MINIMUM. IF IT |
| | IS INSTALLED THERE AND THE GENERATOR |
| | NEUTRAL GROUNDING WAS THROUGH A SOLID |
| | CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| | A GROUND FAULT WHEN THE GENERATOR IS |
| | FEEDING THE LOAD WILL CAUSE THE MAIN |
| | SERVICE DISCONNECT TO OPEN. THIS WILL |
| | NOT DISCONNECT THE ARCING FAULT FROM THE |
| | GENERATOR. COORDINATION IS THUS LOST." |
| | PLEASE VERIFY AS SYSTEMMAY BE REQUIRED |
| | TO BE SEPARATELY DERIVED GENERATOR AND |
| | THUS A4-POLE SWITCH MAY BE REQUIRED. |
| | |
| | 89) NOTE:PLEASE SEE 695.4B1 FOR OCP |
| | REQUIRED FOR LOCKED ROTOR. PLEASE ALSO |
| | SEE NFPA-20 |
| | FOR ELECTRICAL REQUIREMENTS FOR MEANS OF |
| | DISCONNECT, LOCATION ETC. PLEASE SEE |
| | NFPA-20 AS THE MEANS OF DISCONNECTING IS |
| | REQUIRED ON THE OUTSIDE OF THE FIRE PUMP |
| | CONTROLLER. PLEASE SEE SPECS WERE NOT |
| | SUBMITTED AND UNABLE TO VERIFY THIS AT |
| | THIS TIME. |
| | |
| | 90) NOTE:PLEASE SEE 240.13, 230.95 |
| | WHERE GROUND FAULT PROTECTION IS |
| | REQUIRED FOR MAIN TO GUTTER "RT". THIS |
| | MAIN COULD NOT BE LOCATED AT THIS TIME. |
| | 215.5 |
| | |
| | 91) NOTE: PLEASE SEE THAT ALL GUTTER |
| | SIZES ARE TO BE SHOWN FOR A MIN SIZE |
| | REQUIRED AND DESIGNED BY THE DESIGN |
| | PROFESSIONAL AT THIS TIME. PLANS NOTE |
| | THIS IS TO BE SIZED PER CONTRACTOR; |
| | HOWEVER THIS SHOULD BE ON RECORD SET OF |
| | PLANS FOR MIN. SIZES. THESE CAN ALWAYS |
| | BE REVISED AT A LATER DATE.215.5 |
| | PLEASE ALSO SEE CODE AS REFERENCE IS |
| | FROM THE 1996 NEC. |
| | |
| | 92) NOTE: PLEASE SEE DP WHICH INDICATES |
| | MANY BRANCH BREAKERS WHICH ARE SHOWN AS |
| | 4-POLE? THIS IS UNCLEAR AS PANELS ARE 3 |
| | PHASE. |
| | |
| | 93) NOTE: PLEASE SEE PANEL DPE WHICH |
| | SHOWS 4-POLE BREAKERS FOR MANY |
| | ITEMS/CIRCUITS? PLEASE CLARIFY THIS> |
| | 215.5 |
| | |
| | 94) NOTE: PLEASE SPECIFY PANEL "SEF" IF |
| | CONTAINING FEED-THRU LUGS. |
| | 215.5 |
| | |
| | 95) NOTE: PLEASE SEE SOME PASSENGER |
| | ELEVATORS SHOWN ON RISER COULD NOT BE |
| | LOCATED ON PANEL SCHEDULE AS CIRCUITED. |
| | PLEASE SEE THESE ARE REDLINED. |
| | 215 PLEASE LABEL, AND CORRELATE. |
| | |
| | 96) NOTE: PLEASE LABEL RISER FOR ALL |
| | CIRCUITS FOR ELEVATOR CARS/ LTS ETC AND |
| | CORRELATE WITH PANEL SCHEDULES PROVIDED. |
| | 215.5,620.22, (NOTED ABOVE). |
| | |
| | 97) NOTE: PLEASE CLARIFY PIT SUMP PUMPS, |
| | AS PANEL SCHEDULES ONLY SEEM TO INDICATE |
| | ONE PUMP IN ONE PIT? |
| | PLEASE INDICATE, REVISE, AND ADJUST. |
| | 215.5 |
| | |
| | 98) NOTE: PLEASE PROVIDE LABELING FOR |
| | ALL ELEVATORS AND LABEL ON PANEL |
| | SCHEDULES.?IE? ELEV 1, ELEV 2,,,, ETC. |
| | PLEASE SEE PANEL "HER". |
| | |
| | 99) NOTE: PLEASE SEE "HER" SHOWS A |
| | "SPR", THIS EQUIPMENT COULD NOT BE |
| | LOCATE ON EQUIPMENT SCHEDULE? |
| | PLEASE SHOW, LABEL ? 215.5 |
| | |
| | 100) NOTE: PLEASE SEE TXL1A WHICH IS |
| | LABELED AS #29 FROM RISER. PLEASE |
| | CORRELATE. 215.5 |
| | |
| | 101) NOTE: PLEASE SEE SERVICE ENTRANCE |
| | CONDUCTORS INDICATE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" FROM FPL VAULT TO |
| | THE FIRST MEANS OF DISCONNECT. PLEASE |
| | SEE 250.6 THE GROUNDING OF ELECTRICAL |
| | SYSTEMS, CIRCUIT CONDUCTORS, SURGE |
| | ARRESTERS, AND CONDUCTIVE |
| | NON"CURRENT-CARRYING MATERIALS AND |
| | EQUIPMENT SHALL BE INSTALLED AND |
| | ARRANGED IN A MANNER THAT WILL PREVENT |
| | OBJECTIONABLE CURRENT OVER THE GROUNDING |
| | CONDUCTORS OR GROUNDING PATHS.THE |
| | "EQUIPMENT GROUNDING CONDUCTORS" SHALL |
| | ONLY BE INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 102) NOTE:PLEASE SHOW ALL CONTINUOUS |
| | LOADS AT 125%, PER 215.3,230.42 ETC. |
| | |
| | 103) NOTE: PLEASE SEE COMPLETE LOAD |
| | CALCULATIONS COULD NOT LOCATED FOR |
| | BUILDING, FUTURE ESTIMATED LOADS FOR |
| | RETAIL SPACE ETC. LOAD ANALYSIS AS SHOWN |
| | DOES NOT INDICATE HOW THIS LOAD CAME |
| | ABOUT? 220.3,220.10,220.13,220.11, ETC |
| | *UNIT METER CENTERS LOADS ARE SHOWN. |
| | |
| | 104) NOTE: PLEASE PROVIDE LOADS FOR |
| | GENERATOR AND DIRECT LOAD CALCULATIONS |
| | FOR SHEDDING OF LOADS. |
| | PLEASE SEE THAT PLANS, RISER DID NOT |
| | INCLUDE A LOAD SUMMARY FOR THIS UNIT. |
| | 215.5, 700.5 |
| | |
| | 105) NOTE: PLEASE SEE NOTE #16 ON RISER |
| | NOTES WHICH MENTIONS ONLY TWO MAIN |
| | CIRCUIT BREAKERS FOR STAND-BY SYSTEM, |
| | HOWEVER RISER SHOWS MORE THAN THE TWO |
| | LISTED? PLEASE CORRELATE. ONCE AGAIN THE |
| | GENERATOR SPECS ETC WERE NOT SUBMITTED. |
| | 215.5 |
| | |
| | 106) NOTE: PLEASE CLARIFY WHY SOME |
| | ELEVATORS INDICATE "SHUNT TRIPS" AND |
| | OTHER DOES NOT? |
| | 215.5 |
| | |
| | 107) NOTE: PLEASE VERIFY THE TAPPED |
| | CONDUCTORS SHOWN FROM TXRL TO RL. PLEASE |
| | SEE 240.21 AS THIS INSTALLATION DOES NOT |
| | SEEM TO MEET ANY OF THE EXCEPTIONS |
| | LISTED. |
| | I215.5 |
| | |
| | 108) NOTE: PLEASE SHOW VOLTAGE DROP FOR |
| | PANEL "HER". THIS MAY BE PART OF LOAD |
| | ANALYSIS AS PREVIOUSLY NOTED. |
| | FEEDER SCHEDULE MENTIONS FEEDERS ARE |
| | UPDATED FOR VD, HOWEVER THESE DO NOT |
| | SEEM TO SHOW THIS? |
| | 215.5, 13.413.1.ABC.1 |
| | |
| | 109) NOTE: PLEASE ALSO SUBMIT THE |
| | VOLTAGE DROP FOR PANEL "HR" AS NOTED |
| | ABOVE. |
| | |
| | 110) NOTE:PLEASE SEE MISSING |
| | CONDUCTORS FROM H-3 TO TRANSFORMER AND |
| | TO PANEL L3. 215.5, 240.4,310.16,240.21 |
| | ETC |
| | |
| | 111) NOTE: PLEASE SEE "HE3", MISSING |
| | CONDUCTORS FROM THIS PANEL TO |
| | TRANSFORMER AND TO PANEL |
| | LE3.215.3,240.4,310.16, 240.21 |
| | |
| | 112) NOTE:PLEASE SEE PANEL "HIA" SHOWS |
| | 15 KVA TRANSFORMER, YET RISER SHOWS 75 |
| | KVA. PLEASE CORRELATE> |
| | 215.5 |
| | |
| | 113) NOTE: PLEASEPANEL "LR" WHICH IS |
| | SHOWN WITH A 100A MCB , HOWEVER THE |
| | CONDUCTORS TO THIS PANEL IS RATED FOR |
| | 50A?S. PLEASE VERIFY THE CONDUCTORS AS |
| | THEY DO NOT TERMINATE IN OCP WHICH |
| | LIMITS THE LOADS FOR THE CONDUCTORS. |
| | PLEASE VERIFY WITH240.21C, (1-6) |
| | |
| | 114) NOTE:PLEASE SEE THAT PANEL "LI" |
| | INDICATES FEED-THREE LUGS IF INDEED THIS |
| | IS THE INSTALLATION. 215.5 |
| | |
| | 115) NOTE:PLEASE SEE RETAIL COMMON |
| | "SHELL AREAS" SHALL CONTAIN MINIMUM |
| | LIGHTING AS REQUIRED AND PERFIRE |
| | MARSHAL'S OFFICE, HOWEVER PLEASE SEE |
| | THESE AREAS ARE ALL BEING SHOWN |
| | CIRCUITED TO PANELSWHICH UNDER THE |
| | BASE BUILDING. PLEASE PROVIDE NOTES ON |
| | PLANS, AS ALL OF THIS INTERIOR |
| | CIRCUITING WILL BE REQUIRED TO BE |
| | REMOVED AND RE-CIRCUITED TO THE PANELS |
| | AND SERVICE THESE TENANT SPACES ONCE |
| | PERMITTED. |
| | CROSSING OVER OF SERVICES, COMMON AREA |
| | BRANCH CIRCUITS IS NOT PERMITTED. |
| | 230.70,225.25 ETC |
| | |
| | 116) NOTE: PLEASE SEE 250.104 WHICH |
| | REQUIRES ?ALL OTHER METAL PIPING SYSTEMS |
| | TO BE PART OF THE BUILDINGS GROUNDING?. |
| | PLEASE SHOW ATTACHMENT OR NOTE; |
| | |
| | 117) NOTE: PLEASE KNOW, MANY OF THE |
| | ABOVE ITEMS ARE REDLINED ON ONE SET OF |
| | THE MEP'S FOR MANY OF THE SD'S, RECEPTS, |
| | LTS ETC AND LOCATIONS NEEDED. PLEASE |
| | KNOW, THIS IS IN NO WAY ALL LOCATIONS |
| | WHICH MAY BE NEEDED. PLEASE GO OVER |
| | PLANS FOR ALL ITEMS. |
| | |
| | 118) NOTE: PLEASE KNOW A DETAILED |
| | RESPONSE LETTER ON HOW ALL COMMENTS WERE |
| | ADDRESSED AND CLARIFICATIONS NEEDED. |
| | THIS WILL HELP IN EXPEDITING THE REVIEW |
| | PROCESS. |
| | |
| | 119) NOTE: PLEASE SEE ALL COMMENTS FROM |
| | OTHER REVIEWS WHICH MAY AFFECT |
| | ELECTRICAL PLANS AND DESIGN. |
| | |
| | 120) NOTE:ONCE ALL REVIEWS ARE |
| | COMPLETE AND BEFORE RESUBMITTING PLANS: |
| | "ALL OLD/VOIDED SHEETS SHALL BE REMOVED |
| | AND ONLY THE NEW REVISED SHEETS SHOULD |
| | BE INSERTED INTO THREE COMPLETE SETS FOR |
| | REVIEW AND STAMPING". |
| | ONE SET OF ALL OLD/VOIDED SHEETS WHICH |
| | ARE REMOVED SHOULD BE SUBMITTED FOR |
| | REFERENCE ALONG WITH THE NEW SETS. ALL |
| | VOIDED SHEETS MUST BE REMOVED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-03-10 00:00:00 | *** ELECTRICAL REVIEW COMPLETED *** |
| | NOTES TO BE ENTERED ON MONDAY 3/13/06 |
| | STATUS WILL BE "F". |
| 2006-03-08 00:00:00 | REVIEW STILL IN PROGRESS,NOTES TO |
| | FOLLOW. |
| 2006-03-06 00:00:00 | REVIEW CONTINUED. |
| 2006-03-03 00:00:00 | REVIEW STOPPED. REVIEW TO CONTINUE ON |
| | MONDAY 3/6 |
| 2006-03-02 00:00:00 | ELEC REVIEW STARTED FOR REVIEW, NOTES TO |
| | FOLLOW. REVIEW IN PROGRESS. |
| 2006-02-10 00:00:00 | ONE ROLL OF MEP'S IN ELECTRICALTO |
| | REVIEW. |