Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-13 00:00:00NOTES
 ********** UNSAT **********
  
 OPERA PLACE.
 419 LAKE VIEW AVE.
  
 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED
 FOR "PLAN REVIEW" ONLY AND NOT BEEN
 SUBMITTED FOR PERMIT. PLEASE KNOW THERE
 WAS AN INCREASE IN PALM BEACH COUNTY
 IMPACT FEE SCHEDULE WHICH WENT INTO
 EFFECT ON JAN 12, 2006 5PM. ALL PROJECTS
 WOULD BE REQUIRED TO BE SUBMITTED FOR
 "PERMIT" AND PAID FEE BEFORE THAT DATE.
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER
 TRADES WITH RESPECT TO ADDRESSING OF
 TOWERS EAST AND WEST. PLEASE SEE
 COMMENTS WHICH MAY REQUIRE SOME
 ADJUSTMENT IN TITLE BLOCKS FOR SITE
 ADDRESS ETC. PLEASE KNOW, SIGNAGE FOR
 EACH WILL BE REQUIRED. PLEASE SEE FIRE
 REVIEW COMMENTS AS THIS WILL AFFECT THE
 911 RESPONSE ALONG WITH SIGNAGE AT
 BUILDINGS, FIRE COMMAND ROOMS AND ALL
 ELECTRICAL ROOMS.230.2E, 700.8 ETC.
 * PLEASE ALSO KNOW PLANS AND PERMITTING
 FOR THE PROJECT IS COMING IN UNDER ONE
 PERMIT AND BOTH TOWERS BEING BUILT AND
 CONSTRUCTED AT THE SAME TIME. PLEASE
 KNOW THIS MAY CREATE AN ISSUE FOR ANY
 CO'S OR TCO'S OF THIS ONE PERMIT. SEE
 REVIEW COMMENTS FROM BUILDING.
  
 3) NOTE: PLEASE SEE MANY TITLE BLOCKS ON
 SAID PLANS ARE MISSING ALL INFORMATION
 AS REQUIRED UNDER FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 FOR ARCHITECTURAL
 FIRM(S) AND 61G15-23.002 FOR ENGINEERING
 FIRMS. PLEASE SEE ONLY ONE FIRM AS SHOWN
 ON TITLE BLOCKS CONTAINS THE CERTIFICATE
 OF AUTHORIZATION NUMBER. FLORIDA STATUES
 481.219, 471.023
 PLEASE ALSO SEE OTHER INFORMATION
 MISSING, THE PRINTED NAME AND LICENSE
 NUMBER FOR THE DESIGN PROFESSIONAL.
 PLEASE SEE THIS IS SHOWN FOR HNGS.
 * PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE ALL THE CURRENT
 CODES ARE REFERENCED ON PLANS. PLEASE BE
 SUE THE FOLLOWING ARE SHOWN AND DESIGNS
 ARE SHOWN ACCORDINGLY.
 NFPA-20 (2002), NFPA-110 (2002),
 NFPA-101 (2003), NFPA-70 (2002), NFPA-72
 (2002).
 PLEASE SEE THERE ARE MANY LOCATIONS ON
 PLANS WHICH REFERENCES REQUIREMENTS FROM
 THE 1996 NATIONAL ELECTRICAL CODE
 NFPA-70.
 PLEASE SEE NOTES ETC.
  
 5) NOTE: PLEASE SEE COLOR CODING OF
 277/480V SYSTEMS SHALL BE "BROWN,
 PURPLE, AND YELLOW". ORANGE IS ONLY FOR
 HIGH-LEG SYSTEMS AND IS NOT PERMITTED
 FOR 277/480V.
 215, 90.4.
  
 6) NOTE: PLEASE KNOW, "LIGHTNING
 PROTECTION"SYSTEM AS SHOWN IF
 INSTALLED BY A SUB CONTRACTOR WILL
 REQUIRED THIS TO BE PULLED UNDER A
 SEPARATE PERMIT.PLANS INDICATE "BONDED
 LIGHTNING" AS THIS SUB.
  
 7) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR ALL SITE LIGHTING POLES
 INCLUSIVE OF ATTACHED LIGHT FIXTURES.
 PLEASE KNOW, THIS SHOULD INCLUDE ANY
 POLE FIXTURES ON POOL DECK/ROOF
 LEVEL(S).
  
 8) NOTE: PLEASE SHOW AND INDICATE ALL
 ROOM/AREA DESIGNATIONS ON PLANS.
 PLEASE SEE SOME AREAS ARE UNCLEAR FOR
 USE.
 PLEASE SEE ONE OF THESE AREAS APPEARS TO
 SHOW ACCESS TO THE TRASH SHOOT THROUGH
 ONE OF THE ELECTRICAL ROOMS ON
 MEZZ/FIRST FLR. PLEASE SEE BUILDING
 REVIEW COMMENTS FOR THIS. PLEASE KNOW,
 ACCESS THROUGH THIS ELECTRICAL ROOM IS
 NOT PERMITTED. 110.26, 110.27, 240.4
 ETC.
  
 9) NOTE:PLEASE SEE NFPA-110 7.2.3*
 WITH RESPECT TO THE LOCATION OF
 GENERATORS AND ELEVATION. PLEASE SEE
 EXPLANATION OF THIS REQUIREMENT WHICH
 REQUIRES THE MIN AS SET PER THE ?SLOSH?
 PREDICTION. (SEA, LAKE, OVERLAND,
 SURGES, FROM HURRICANES.)
  
 10) NOTE: PLEASE KNOW, DOORS FOR
 ELECTRICAL ROOMS, GENERATOR ROOM, AND
 FIRE PUMPS ROOMS WILL BE REQUIRED TO
 OPEN OUTWARD IN THE DIRECTION OF EGRESS.
 PLEASE KNOW THE MAIN ELECTRICAL ROOMS
 AND GENERATOR ROOM WILL REQUIRED PANIC
 HARDWARE ON DOORS. 110.26.
 PLEASE BE SURE TO SEE ANY INTERFERENCE
 WITH MINIMUM EGRESS WIDTHS IN HALL
 OUTSIDE THE MAIN ELECTRICAL ROOMS.
  
 11) NOTE: PLEASE LABEL MAINS 1 OF 5, 2
 OF 5 ETC PLEASE SEE MAINS AS SHOWN MAY
 LEAD TO SOME CONFUSION IN ORDER TO SHUT
 DOWN BLDG IN CASE OF AN EMERGENCY.
 PLEASE KNOW, THESE MAINS SHOULD ALSO BE
 IDENTIFIED FOR EACH SECTION /USE OF SHUT
 DOWN. FLOORS 1-13 , 13-26, HOUSEPOWER,
 EM ETC.
 215.5
  
 12) NOTE: PLEASE SEE 110.26 FOR MINIMUM
 CLEARANCES REQUIRED FOR ALL ELECTRICAL
 EQUIPMENT IN ELECTRICAL ROOMS.PLEASE
 SEE ENLARGE ELECTRICAL ROOM PLAN SEEMS
 TO NOT SHOW THE MIN. CLEARANCE FOR DPE.
 PLEASE ALSO PROVIDE A NOTE ON E-4.01 FOR
 ALL CLEARANCES TO MEET 110.26, NO
 EXCEPTIONS.
  
 13) NOTE: PLEASE SEE SEF PANEL SHALL BE
 LABELED AS ONE OF THE EMERGENCY MAINS
 FROM GENERATOR.
 215.5, 230.2,230.72 ETC
  
 14) NOTE: PLEASE SEE DPE SHALL CONTAIN A
 MCB IN THE EVENT OF SHUTTING DOWN OF
 POWER ON THE EM SIDE OF GENERATOR.
 230.76, 230.72, 230.79 ETC.
 ACCESS TO GENERATOR ROOM TO QUALIFIED
 PERSONNEL DURING AN EMERGENCYTO SHUT
 DOWN POWER TO DPE DURING THEOPERATION
 OF THIS GENERATORPOSES A CONCERN TO
 THIS OFFICE AND FIRE MARSHAL'S OFFICE.
 "PLEASE KNOW,"SHUNT TRIPS"ARE NOT
 PERMITTED AS THE MEANS OF DISCONNECT ,
 HOWEVER MAY BE INSTALLED AND LABELED
 ACCORDINGLY IN MAIN ELECTRICAL ROOM OR
 FIRE COMMAND ROOM.
  
 15)NOTE:PLEASE PROVIDE A DETAIL FOR
 GATES UNDER POWER FAILURE FOR ACCESS
 INTO AND EGRESS OUT OF BLDG. THESE MAY
 BE PERMITTED SEPARATELY, HOWEVER A NOTE
 FOR A MIN SHOULD BE PROVIDED AT THIS
 TIME.
  
 16) NOTE:PLEASE PROVIDE AN EMERGENCY
 BATTERY BACK UP FIXTURE OF SOME TYPE IN
 ALL ELEVATOR EQUIPMENT ROOMS.
 700.16, LS101 7.8, 7.9
  
 17) NOTE: PLEASE SEE 620.22, 620.23, AND
 620.24 FOR ALL MINIMUM REQUIRED
 DEDICATED BRANCH CIRCUITS. PLEASE SEE
 SOME APPEAR TO SHARE WITH OTHER AREAS
 BESIDES ONLY THE ELEVATOR EQUIPMENT
 ROOMS.
 ALL ROOMS SHALL CONTAIN THEIR OWN
 DEDICATED CIRCUITS AND MAY NOT FEED
 OTHER ROOMS OR OTHER COMMON ARES.
  
 18) NOTE: PLEASE CLARIFY AS IT APPEARS
 ONLY ONE ELEVATOR PIT INDICATES SUMP
 PUMP CIRCUIT?
 PLEASE SHOW OTHER PIT CIRCUIT(S).
  
 19) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MEANS OF CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. PLEASE PROVIDE AREA
 CALCULATIONS AS SET FORTH.
 13-415.1.ABC.2
  
 20) NOTE: PLEASE SEE 13-415.1.ABC.1.1 &
 .2 FOR CONTROL OF INTERIOR LIGHTS.
 PLEASE KNOW, ALL ROOMS NOT IN USE FOR
 24HR OPERATION SHALL CONTAIN MEANS OF
 BEING AUTOMATICALLY TURNED OFF.PLEASE
 KNOW, THIS INCLUDES ANY STORAGE,
 MECHANICAL, CLOSETS ETC.
 PLEASE SEE OTHER NEW REQUIREMENTS OF
 CHAPTER 13.
  
 21) NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS, STAIRS ETC. PLEASE SEE SOME STAIR
 TOWERS SHOWN FIXTURES, HOWEVER CIRCUIT
 IS NOT SHOWN?
 215.5
  
 22) NOTE:PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL CORRIDORS, EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9,
 THIS REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A
 MINIMUM
 OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURE IS ALREADY BEING SHOWN IN STAIR
 TOWERS.
 PLEASE KNOW THIS MAY BE A "TYPICAL"
 DETAIL FOR THESE AREAS. PLEASE SEE THAT
 SOME SORT BATTERY BACK UP FIXTURE WILL
 BE REQUIRED TO PROVIDE A MIN AMOUNT OF
 LIGHT IN HALLWAYS AND GARAGE ARE IN THE
 EVENT OF THE TRIPPING OF THE SINGLE
 MEANS OF OCP ON THE EM SIDE OF SYSTEM.
 PLEASE SEE OTHER AREAS BESIDES STAIRS
 SHALL BE PERMITTED TO PROVIDE 1FT CANDLE
 (AVERAGE) UNDER NORMAL AND EMERGENCY.
 PLEASE SEE 7.9 WHICH REQUIRES THIS
 TO ALLEVIATE ANY ONE AREA BEING IN
 TOTAL DARKNESS UPON THE TRIPPING OF A
 SINGLE DEVICE, SWITCH, BRKR ETC.
  
 23) NOTE:PLEASE SEE THAT ANY AFTER
 DUSK BEFORE DAWN SWIMMING WILL REQUIRE
 PHOTO-METRICS FOR POOL AREA(S). PLEASE
 KNOW, ALL PHOTO-METRICS WILL BE REQUIRED
 TO BE SUBMITTED TO PALM BEACH COUNTY
 HEALTH DEPARTMENT FOR REVIEW AND
 STAMPING. ONLY THE STAMPED PLANS/SHEETS
 FROM PBCHD SHOULD BE SUBMITTED.
  
 24) NOTE: PLEASE SEE NFPA-1107.3.3*
 THE INTENSITY OF ILLUMINATION IN THE
 ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL
 1 SHALL BE 32.3 LUX (30 FT-CANDLES).
 PLEASE SHOW DETAIL.
  
 25) NOTE: PLEASE SEE NFPA-110 7.7 FOR
 EPS VENTILATION. PLEASE SEE LOADING DOCK
 AREA IS BEING SHOWN AS THE AIR INTAKE
 FOR THE GENERATOR WHICH SHOWS A DOOR TO
 CLOSE OFF THIS ARE TO OUTSIDE AIR.
 PLEASE SEE 7.7.2.1 FOR EPS SUPPLYING
 LEVEL 1 EPSS, VENTILATION AIR SHALL BE
 SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE
 OF THE BUILDING BY AN EXTERIOR WALL
 OPENING OR FROM A SOURCE OUTSIDE THE
 BUILDING BY A 2-HOUR FIRE RATED AIR
 TRANSFER SYSTEM.
 PLEASE SEE BUILDING REVIEW COMMENTS AS
 WALLS/ LOUVERS AS SHOWN SEEM TO CREATE
 AN ISSUE FOR THE MIN 2 HR RATING.
  
 26) NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EPS EQUIPMENT. (ATS). PLEASE SEE
 6.5.2 NFPA-110.
 UNABLE TO VERIFY AT THIS TIME.
  
 27) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT:
 ATS?S, GENERATOR, FIRE PUMP FIRE PUMP
 CONTROLLER, SUB-BASE FUEL TANK ETC.
 PLEASE SEE OTHER COMMENTS AND KNOW THAT
 MANY ITEMS FOR CODE COMPLIANCE CAN NOT
 BE REVIEW AT THIS TIME DUE TO THESE
 ITEMS NOT BEING SUBMITTED FOR REVIEW.
  
 28) NOTE: PLEASE SEE NFPA-20 9.6.2.2
 WHICH REQUIRES A MIN OF 8HRS RUNNING @
 100% LOAD FOR FIRE PUMP. PLEASE ALSO
 BEAR IN MIND THE MINIMUM 100% LOADS FOR
 ALL OTHER LEGALLY REQUIRED STAND-BY
 ITEMS.
  
 29) NOTE: PLEASE SEE NFPA-20 7.2FOR
 LOCATION OF FP CONTROLLER, HEIGHT, NEMA
 TYPE 2 ENCLOSURES AND ROOM CONTAINING A
 FLOOR DRAIN.
  
 30) NOTE:PLEASE NOTE ON PLANS THE
 ACCEPTANCE OF THE EPS AS REQUIRED IN
 NFPA-110 7.13.
 THE SYSTEM SHALL BE TESTED AS REQUIRED
 BEFORE CERTIFICATE OF OCCUPANCY OR
 TEMPORARY CO.
  
 31) NOTE: PLEASE SEE SQUARES LOCATED ON
 PLANS SEEM TO REFERENCE NOTES, HOWEVER
 PLEASE SEE THESE NOTES SHOULD BE LABELED
 AS TYPICAL ON ALL SHEETS WITH THESE
 "SQUARES" REFERENCING THESE.
  
 32) NOTE: PLEASE SEE PLANS INDICATE A
 ?GENERATOR ROOM? FOR GYM/ SPA AREA. THIS
 SEEMS IT SHOULD BE LABELED AS ?STEAM
 GENERATOR ROOM.
 215.5
  
 33) NOTE:PLEASE COMPLETE FIXTURE
 SCHEDULE AND CORRELATE WITH PLANS.
 PLEASE SEE SOME FIXTURES ARE NOTED ON
 PLANS AS BEING CHOSEN BY ARCHITECT OR
 THEY ARE NOT NOTED AT ALL. A FIXTURE
 TYPE OF SOME SORT SHOULD BE INDICATED AT
 THIS TIME. THIS CAN BE CHANGE OR REVISED
 LATER. PLEASE SEE ANY ADJUSTMENT IN
 FIXTURE SCHEDULE SHOULD BE UPDATED
 PENDING ANY CHANGES IN EM/EXT LTS.
  
  
  
 34) NOTE: PLEASE SEE NOTE TO BE PROVIDED
 ON ALL E-2.09AB FOR MINIMUM CLEARANCES
 FOR POOL AREA FIXTURES. PLEASE 680.22
 FOR HIGH VOLTAGE FIXTURES (5FT MIN W/
 GFI PROTECTION AND 10FT MIN FOR LOW
 VOLTAGE TYPE FIXTURES. 411.4
  
 35) NOTE: PLEASE SEE 680.22 FOR GFI
 RECEPTACLES TO BE LOCATED A MIN OF 20?
 OF POOL. PLEASE ALSO SEE EXCEPTION WITH
 RESPECT PH-L3 UNITS.
  
 36) NOTE: PLEASE PROVIDE NOTE ON PLANS
 WHICH PROHIBITS THE INSTALLATION OF ANY
 ELECTRICAL CONDUITS ETC IN STAIRS UNLESS
 SPECIFICALLY DESIGNATED TO THE STAIRS.
 PLEASE ALSO PROVIDE NOTE FOR ELEVATOR
 EQUIPMENT ROOMS.
 215.5
  
 37) NOTE: PLEASE SEE ENLARGED ELEVATOR
 EQUIPMENT ROOMS, SOME ITEMS DO NOT SEEM
 TO CORRELATE.
  
 38) NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON ALL UNIT PLANS.
 PLEASE BE SURE TO ADDRESS "DINING AREAS"
 AS CIRCUITING IS TO BE VERIFIED. PLEASE
 SEE OTHER COMMENT WHICH THIS AFFECTS.
  
 39) NOTE: PLEASE PROVIDE VOLTAGE DROP
 ANALYSIS FOR ALL FEEDERS AND BRANCH
 CIRCUITS. THIS MAY BE A WORST CASE
 SCENARIO FOR EACH. PLEASE SEE FBC
 CHAPTER 13, 13-413.1.ABC.1.1, &.2.
  
 40) NOTE: PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT
 TO HEIGHTS AND LOCATIONS FOR ALL
 ACCESSIBLE DEVICES.
 PLEASE SEE SOME ITEMS ON PLANS ARE SHOWN
 TO EXCEED THE MAX OF 48?.
  
 41) NOTE: PLEASE SEE CODES NOTE #12 WITH
 RESPECT TO LOCATIONS OF SMOKE DETECTORS.
 PLEASE SEE 2002 NFPA-72 11.5.1.1,
 11.5.8.3.5.
 SD'S ARE TO BE LOCATED A MIN OF 3FT FROM
 KITCHEN AND BATH DOORS AND A MIN OF 20FT
 FROM COOKING APPLIANCES. (WITH
 EXCEPTIONS TO THE DISTANCE FROM COOKING
 APPLIANCES.
 PLEASE ADJUST THIS "CODES NOTE".
  
 42) NOTE: PLEASE SEE NFPA-72 WHICH
 REQUIRES ALL SD'S TO BE WIRED "IN-LINE".
 PLEASE SEE NUMEROUS UNITS WHERE THE SD?S
 ARE WIRED UP TO AS MANY AS 7 INDIVIDUAL
 CIRCUITS. THIS IS NOT POSSIBLE WHEN THEY
 ARE ALL REQUIRED TO BE WIRED INLINE.
 PLEASE ADJUST CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE ALSO SEE THE FOLLOWING
 COMMENT.
  
 43) NOTE: PLEASE SEE 210.12 IN THE 2002
 NEC WHICH REQUIRES ARC FAULT PROTECTION
 FOR ALL "OUTLETS" ( SD'S, LTS, FANS,
 RECEPTS ETC.)IN BEDROOMS. PLEASE SEE
 SOME CIRCUITING ON PLANS DOES NOT
 INDICATE ARC FAULT PROTECTION FOR SOME
 ITEMS SHOWN IN THE SLEEPING ROOMS.
 PLEASE SEE SD'S CIRCUITED ON PLANS WHICH
 SOME OF THESE CIRCUITS ON PANEL
 SCHEDULES, WHICH DO NOT SHOW AFCI BRANCH
 CIRCUIT PROTECTION.
  
 44) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE ONLY A "J-BOX" FOR DISHWASHER
 AND DISPOSAL WHICH LENDS TO THESE
 APPLIANCES NOT BEING INSTALLED UNDER THE
 PERMIT FOR THIS BUILDING? PLEASE VERIFY,
 IF INDEED THESE APPLIANCES ARE BEING
 INSTALLED, THEN THE RECEPTACLES WOULD BE
 REQUIRED TO BE SHOWN ON PLANS.
  
 44) NOTE: PLEASE SEE LV PANEL LOCATIONS
 SHOWN IN CLOSETS MAY NOT BE PERMITTED IF
 CONTAINING OCP. PLEASE KNOW, THE
 RECEPTACLES AS SHOWN ON ELECTRICAL PLANS
 IN CLOSETS IN CLOSE PROXIMITY OF
 SHELVING AND/OR STORAGE WILL NOT BE
 PERMITTED FOR ANY "PLUG-IN" TYPE
 TRANSFORMERS. PLEASE KNOW, THIS
 JURISDICTION HAS HAD MANY SCENARIO?S
 WHERE THE HEATING AND OR MELTING OF THE
 PLUG-IN TYPE TRANSFORMER HAS CAUSED
 FIRES. PLEASE KNOW THIS IS A LIFE SAFETY
 AND PROPERTY HAZARD AND LOCATIONS OF
 THESE UNITS/DEVICES WILL NEED TO BE
 ADJUSTED.
 * PLEASE KNOW, IT IS NOTED THAT MANY OF
 THE UNITS DO NOT SHOW THESE LOCATED IN
 CLOSETS AND DO NOT NEED TO BE MOVED.
 240.24,110.26 ETC
  
 45) NOTE: PLEASE VERIFY UNIT BALCONIES,
 AS UNITS DO NOT SHOW ANY LIGHTING OR
 RECEPTACLES ALL THE WAY UP TO THE PH
 UNITS??
 THIS IS ONLY A NOTE AS UNLESS THESE
 BALCONIES CONTAIN DIRECT GRADE LEVEL
 ACCESS, LIGHTING IS NOT REQUIRED. PLEASE
 REVISE IF ANY OF THESE ARE INDEED GOING
 TO CONTAIN LTS ETC.
  
 46) NOTE: PLEASE SEE PLANS WHICH
 MENTIONS "THEATRE" AND NOTES
 ACCORDINGLY. PLEASE SEE NOTES MENTIONS
 "STEP-LTS" WHICH COULD NOT BE LOCATED ON
 PLANS?
 PLANS ALSO INDICATE THIS ARE AS A
 "MULTI-PURPOSE" ROOM?PLEASE CLARIFY
 USE.
  
 47) NOTE: PLEASE PROVIDE EMERGENCY
 LIGHTING FOR EGRESS TO THE PUBLIC RIGHT
 OF WAY. PLEASE SEE THE BREEZEWAY AREAS/
 DRIVE AREA WHICH MAY BE USED AS AN
 EGRESS PATH WAY.
 LS 101-7.8,7.9
  
 48) NOTE: PLEASE SEE NFPA-72 11.8.3.5
 WHICH REQUIRES THE UNIT SMOKE DETECTORS
 TO BE LOCATED ON THE LOWER LEVEL OF A
 MULTI-STORY DWELLING UNIT AND IN CLOSE
 PROXIMITY LEADING TO THE FLOOR ABOVE.
 PLEASE SEE SOME OF THESE ARE LOCATED
 AWAY FROM THIS AREA.
  
 48) NOTE: PLEASE SEE MISSING CIRCUITING
 ON MANY OF THE SMOKE DETECTORS SHOWN ON
 PLANS.
 PLEASE COMPLETE. PLEASE ALSO SEE
 PREVIOUS NOTES ABOVE WITH RESPECT TO THE
 CIRCUITING AND AFCI.
 215.5
  
 49) NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS OUTSIDE SLEEPING ROOMS.
 NFPA-72 11.5.1.1
  
 50) NOTE: PLEASE SEE 210.52 FOR
 RECEPTACLE SPACING INSIDE DWELLING UNITS
 FOR 2 FT, 6FT AND 12 FT RULE.
 PLEASE SEE UNIT LAYOUT AS MANY OF THESE
 HAVE BEEN REDLINED.
  
 51) NOTE: PLEASE SEE MANY UNITS ARE
 SHOWING "J-BOXES" FOR THE REQUIRED MEANS
 OF EGRESS LIGHT FIXTURE REQUIRED. PLEASE
 SEE 210.70, AND LS 101 7.8
 PLEASE SEE A MIN OF ONE FIXTURE OF SOME
 TYPE WILL BE REQUIRED FOR THESE AREAS.
 HALL, DINING, LIVING AREAS ETC.
  
 52) NOTE: PLEASE SEE 210.52C2,4 FOR
 ISLANDS AND SEPARATE COUNTER SPACES
 WHICH REQUIRED ADDITIONAL GFI RECETPS.
  
 53) NOTE: PLEASE SEE 210.52C1 FOR
 COUNTER SPACES ALONG WALLS AND
 210.52C3,4 FOR PENINSULA'S. PLEASE SEE
 WALL SPACES BELOW SOME OF THESE
 PENINSULAR LOCATIONS MAY REQUIRE RECEPTS
 AS THESE APPEAR TO BE WALL SPACES.
 PLEASE SEE 210.8A6 AS ALL RECEPTACLES
 SERVING KITCHEN COUNTER SPACES SHALL BE
 GFI/GFI PROTECTED.
  
 54) NOTE: PLEASE SEE WHAT APPEARS TO
 MISSING "WALLS" IN UNIT 2A-3.05.
  
 55) NOTE: PLEASE SEE WHAT APPEARS TO BE
 A SHIFT IN PLANS IN UNIT "3A". 3.06
  
 56) NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOMS AND AREAS OF THE LIKE SHALL
 BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE ALMOST ALL OF THE
 DINING AREAS SHOWN CONTAIN CIRCUITS
 WHICH ARE 15A AND #14 AWG. 210.52B1
 PLEASE ADJUST CIRCUITS, CONDUCTOR SIZES
 AND SEE PREVIOUS NOTE WITH RESPECT TO
 ROOM AND AREA DESIGNATIONS.
  
 57) NOTE: PLEASE SEE MISSING HALL
 RECEPTACLE FOR HALLS CONTAINING 10FT OR
 MORE OF CONTINUOUS WALL SPACE.
 210.52H
  
 58) NOTE: PLEASE SEE UNIT PANELS WHICH
 INDICATE 12KW FOR RANGE LOADS AND LOAD
 CALCULATIONS INDICATE 10KW.
 PLEASE CORRELATE 215.5
  
 59) NOTE: PLEASE SEE A 60A BREAKER
 FEEDING WHAT WOULD BE A 50A RATED DEVICE
 FOR RANGE. PLEASE SEE THIS DOES NOT
 CORRELATE WITH LOAD CALCULATIONS AS
 CALCULATIONS SHOW A LOWER LOAD. PLEASE
 SEE NOTE ABOVE AND CORRELATE LOADS AT
 208V.
 PLEASE SEE 210.21B3
  
 60) NOTE: PLEASE CORRELATE PANEL FOR
 PH-L3 AS SOME AREAS OF PLANS MENTIONS
 THIS AS 225A WITH LOADS EXCEEDING THIS
 RATING. PLEASE SEE OTHER AREAS OF PLANS
 WHICH INDICATE THIS PANEL AS 400A.
 PLEASE ALSO INDICATE IF SECTION ONE
 CONTAINS FEED-THRU LUGS.
 PLEASE SEE METER CENTERRISER ETC.
 215.5, 240.4, 408,310.16 ETC
  
 61) NOTE: PLEASE VERIFY LABELING OF
 UNITS AND PANELS, AS SOME AREAS SHOW
 "A-1" AND OTHER ?1-A?, AND OTHER UNITS
 AND PANELS.
  
 62) NOTE: PLEASE SEE FEEDERS SHOWN AT
 250MCM FOR WHAT APPEARS TO BE 400A PANEL
 AND 400A OCP FOR PH-L3??
 240.4, 310.16
  
 63) NOTE: PLEASE SEE 4.05 MENTIONS ONE
 A/C SYSTEM FOR PH-L3 WITH 70A OCP, YET
 PANEL SCHEDULE FOR THIS UNIT SHOWS 2
 SYSTEMS. PLEASE VERIFY THIS AND ADJUST
 ACCORDINGLY.
  
  
 64) NOTE: PLEASE PROVIDE THE PANEL
 SCHEDULE FOR EACH UNIT AND CORRELATE
 WITH CIRCUITING FOR EACH UNIT AS THE
 CIRCUITING SHOWN DOES NOT CORRELATE TO
 ALL UNITS AND TYPE OF PANEL FOR EACH
 UNIT.
 EACH UNIT SHOULD INDICATE LOADS, OCP AND
 CIRCUITING.
 215.5
  
 65) NOTE: PLEASE SEE METER CENTER RISER
 WHICH INDICATES A 150A BREAKER FEEDING
 PH-L3, WHICH IS 400A?S ETC. PLEASE
 CORRELATE AND SEE NOTE ABOVE.
 215.5
  
 66) NOTE: PLEASE CORRELATE LOAD FOR WHAT
 IS SHOWN AS A POOL HEATER FOR PH-L3 ON
 LOAD CALCULATIONS, HOWEVER THIS IS NOT
 ON PANEL SCHEDULE?
 215.5
  
 67) NOTE: PLEASE CORRELATE LOADS FOR
 OTHER APPLIANCES. PLEASE SEE DISPOSAL
 800VA ON ONE AND 700VA ON THE OTHER.
 215.5
  
 68) NOTE:PLEASE SEE WHAT APPEARS TO BE
 A NOTE ON PANEL SCHEDULES FOR ARC FAULT
 PROTECTION; HOWEVER THIS SYMBOL DOES NOT
 SEEM TO CORRELATE WITH REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE.
 210.12
  
 69) NOTE: PLEASE CORRELATE DISHWASHER
 LOADS, AS LOAD CALCULATIONS SHOW 800VA
 AND PANEL SCHEDULES SHOW 1200VA.
 215.5
  
 70) NOTE: PLEASE CORRELATE WATER HEATER
 SHOWN FOR A-3 OR 3A? 4.5KVA OR 6KVA?
  
 71) NOTE: PLEASE SEE UNIT PHL2 STAIR
 LAYOUTS DO NOT SEEM TO CORRELATE WITH
 EACH FLOOR AND LOCATION OF ABOVE 2ND
 FLOOR.
 215.5
  
 72) NOTE: PLEASE SEE PHL-1 FOR LIVING
 ROOM NEXT TO KITCHEN BAR AREA AND
 CIRCUITING.
 210.52B1
  
 73) NOTE: PLEASE SEE PHL-4 AND LAYOUTS
 TO CORRELATE.
  
 74) NOTE: PLEASE SEE PHL-5 , IT IS
 UNCLEAR WHICH SIDE OF STAIR IS UP?
  
 75) NOTE: PLEASE SEE UNIT PHL-7 WHICH
 APPEARS TO SHOW THE PANEL LOCATED UNDER
 STAIRS? PLEASE SEE 110.26, 240.24 ETC
 IS THIS ARE OPEN? PLEASE ALSO SEE
 PREVIOUS COMMENTS FOR WALL SPACE IN THIS
 SAME AREA.
  
 76) NOTE: PLEASE SEE MINIMUM CLEARANCE
 FOR 277/480V.
 PLEASE SEE 110.26
  
 77) NOTE: PLEASE CLARIFY AND CORRELATE
 PLANS, RISER AND ELECTRICAL ROOM?S
 LAYOUT AS ELECTRICAL ROOM #7 COULD NOT
 BE LOCATED ON ?ENLARGED? ELECTRICAL ROOM
 LAYOUT.
 215.5
  
 78) NOTE: PLEASE BE SURE TO CORRELATE
 ALL UNIT LOADS FOR A/C UNITS AND NEW
 PANEL SCHEDULES TO BE PROVIDED. 215.5
  
 79) NOTE: PLEASE SEE SOME FIXTURES IN
 COMMON AREAS WHICH SEEM O INDICATE THE
 SAME FIXTURE LABEL; HOWEVER THE SYMBOL
 IS NOT THE SAME? PLEASE CORRELATE.
 215.5
  
 80) NOTE: PLEASE SEE FIRE ALARM SHEETS
 WHICH REFLECT CODES FROM THE SFBC.
 PLEASE ADJUST PER 2004 FBC AND NFPA-72
  
 81) NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SHOWS DETAIL AND CODE FROM THE
 1996 NEC/ NFPA-72. PLEASE ADJUST.
  
 82) NOTE: PLEASE COMPLETE THE COMMON
 GROUNDING ELECTRODE ON RISER DIAGRAM.
 THIS MAY BE IN LIGHT GRAY OR DASHED
 LINES FOR ALL REQUIRED ATTACHMENTS PER
 250.50, 250.58
  
 83) NOTE: PLEASE COMPLETE ALL
 TRANSFORMER ATTACHMENT LOCATIONS. PLEASE
 SEE SOME ARE SHOWN BEING CONNECTED TO
 THE BUILDINGS GROUNDING ELECTRODE
 SYSTEM, OTHERS ARE NOT.
 250.30, 215.5.
  
 84) NOTE: PLEASE SEE RISER SHOWS MAINS
 ONE , TWO AND SWBD BEING FED FROM
 OVERHEAD ON RISER, HOWEVER ELECTRICAL
 ROOM LAYOUT/ PLANS INDICATE THESE AS
 BEING FED BACK TO BACK WITH FPL VAULT.
 (BUS-STAB?). PLEASE KNOW, NOT MORE THAN
 8? OF UNPROTECTED CONDUCTORS OR BUS DUCT
 IS PERMITTED INSIDE THE BUILDING.230.70,
 230.71
  
 85) NOTE: PLEASE CORRELATE RISER AND
 6.01. ONE SHOWS SWBD AND THE OTHER
 SWGRA?
 215.5
  
 86) NOTE: PLEASE CORRELATE THE NUMBER OF
 PANEL AND UNITS ON RISER DIAGRAM WITH
 THE NUMBER OF UNITS SHOWN ON METER
 CENTER RISER/ SCHEDULE.
 PLEASE SEE ALL FLOORS SHOW DIFFERENT
 NUMBER OF UNITS FOR EACH.
 215.5
 A) PLEASE SEE MC 16, SHOWS 16 ON RISER
 AND 18 ON METER CENTER SCHEDULE.
 B) PLEASE SEE MC # 15 SHOWS 13 ON METER
 SCHEDULE AND 14 ON RISER.
 C) PLEASE SEE MC #14, SHOWS 19 ON RISER
 AND 18 ON METER CENTER SCHEDULE.
 D) PLEASE SEE MC #13 SHOWS 20 ON RISER
 AND 19 ON MC SCHEDULE.
 E) PLEASE SEE MC #12, SHOWS 19 ON RISER
 AND SHOWS 18 ON SCHEDULE.
  
 *** PLEASE SEE ALL OTHERS AND CORRELATE
 AS MOST OF THESE DO NOT MATCH.
 215.5
  
 87) NOTE: PLEASE SPECIFY ALL AIC RATINGS
 FOR ALL EQUIPMENT. PLEASE PROVIDE
 RATINGS FOR ANY FUSE AS INDICATED.
 PROVIDE RATINGS ON CURRENT LIMITING
 FUSES AS NOTED. 110.9, 215.5
  
 88) NOTE:PLEASE KNOW, IF 1000A'S, GFP
 SENSING WILL BE REQUIRED ON SECONDARY
 SIDE, GFP WILL BE REQUIRED ON MAIN ALSO
 AS NOTED
 PER 240.13,230.95.
 PLEASE SEE 700.7D, 700.26, 701.9D
 PLEASE SEE TEXT TAKEN DIRECTLY FROM ASCO
 MANUFACTURE WRITTEN DIRECTIVE FOR EPSS
 SYSTEMS. WHERE AS A 4-POLE ATS MAY BE
 REQUIRED FOR THE
 CORRECT COORDINATION OF ELECTRICAL
 SYSTEMS.
 "WHERE GROUND FAULT PROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE
 CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A
 CIRCUMSTANCE. THE SERVICE IS LARGER THAN
 1,000 AMPS. CONSEQUENTLY, GROUND FAULT
 PROTECTION IS REQUIRED AT THE MAIN
 SERVICE DISCONNECT AT A MINIMUM. IF IT
 IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOT DISCONNECT THE ARCING FAULT FROM THE
 GENERATOR. COORDINATION IS THUS LOST."
 PLEASE VERIFY AS SYSTEMMAY BE REQUIRED
 TO BE SEPARATELY DERIVED GENERATOR AND
 THUS A4-POLE SWITCH MAY BE REQUIRED.
  
 89) NOTE:PLEASE SEE 695.4B1 FOR OCP
 REQUIRED FOR LOCKED ROTOR. PLEASE ALSO
 SEE NFPA-20
 FOR ELECTRICAL REQUIREMENTS FOR MEANS OF
 DISCONNECT, LOCATION ETC. PLEASE SEE
 NFPA-20 AS THE MEANS OF DISCONNECTING IS
 REQUIRED ON THE OUTSIDE OF THE FIRE PUMP
 CONTROLLER. PLEASE SEE SPECS WERE NOT
 SUBMITTED AND UNABLE TO VERIFY THIS AT
 THIS TIME.
  
 90) NOTE:PLEASE SEE 240.13, 230.95
 WHERE GROUND FAULT PROTECTION IS
 REQUIRED FOR MAIN TO GUTTER "RT". THIS
 MAIN COULD NOT BE LOCATED AT THIS TIME.
 215.5
  
 91) NOTE: PLEASE SEE THAT ALL GUTTER
 SIZES ARE TO BE SHOWN FOR A MIN SIZE
 REQUIRED AND DESIGNED BY THE DESIGN
 PROFESSIONAL AT THIS TIME. PLANS NOTE
 THIS IS TO BE SIZED PER CONTRACTOR;
 HOWEVER THIS SHOULD BE ON RECORD SET OF
 PLANS FOR MIN. SIZES. THESE CAN ALWAYS
 BE REVISED AT A LATER DATE.215.5
 PLEASE ALSO SEE CODE AS REFERENCE IS
 FROM THE 1996 NEC.
  
 92) NOTE: PLEASE SEE DP WHICH INDICATES
 MANY BRANCH BREAKERS WHICH ARE SHOWN AS
 4-POLE? THIS IS UNCLEAR AS PANELS ARE 3
 PHASE.
  
 93) NOTE: PLEASE SEE PANEL DPE WHICH
 SHOWS 4-POLE BREAKERS FOR MANY
 ITEMS/CIRCUITS? PLEASE CLARIFY THIS>
 215.5
  
 94) NOTE: PLEASE SPECIFY PANEL "SEF" IF
 CONTAINING FEED-THRU LUGS.
 215.5
  
 95) NOTE: PLEASE SEE SOME PASSENGER
 ELEVATORS SHOWN ON RISER COULD NOT BE
 LOCATED ON PANEL SCHEDULE AS CIRCUITED.
 PLEASE SEE THESE ARE REDLINED.
 215 PLEASE LABEL, AND CORRELATE.
  
 96) NOTE: PLEASE LABEL RISER FOR ALL
 CIRCUITS FOR ELEVATOR CARS/ LTS ETC AND
 CORRELATE WITH PANEL SCHEDULES PROVIDED.
 215.5,620.22, (NOTED ABOVE).
  
 97) NOTE: PLEASE CLARIFY PIT SUMP PUMPS,
 AS PANEL SCHEDULES ONLY SEEM TO INDICATE
 ONE PUMP IN ONE PIT?
 PLEASE INDICATE, REVISE, AND ADJUST.
 215.5
  
 98) NOTE: PLEASE PROVIDE LABELING FOR
 ALL ELEVATORS AND LABEL ON PANEL
 SCHEDULES.?IE? ELEV 1, ELEV 2,,,, ETC.
 PLEASE SEE PANEL "HER".
  
 99) NOTE: PLEASE SEE "HER" SHOWS A
 "SPR", THIS EQUIPMENT COULD NOT BE
 LOCATE ON EQUIPMENT SCHEDULE?
 PLEASE SHOW, LABEL ? 215.5
  
 100) NOTE: PLEASE SEE TXL1A WHICH IS
 LABELED AS #29 FROM RISER. PLEASE
 CORRELATE. 215.5
  
 101) NOTE: PLEASE SEE SERVICE ENTRANCE
 CONDUCTORS INDICATE AN "EQUIPMENT
 GROUNDING CONDUCTOR" FROM FPL VAULT TO
 THE FIRST MEANS OF DISCONNECT. PLEASE
 SEE 250.6 THE GROUNDING OF ELECTRICAL
 SYSTEMS, CIRCUIT CONDUCTORS, SURGE
 ARRESTERS, AND CONDUCTIVE
 NON"CURRENT-CARRYING MATERIALS AND
 EQUIPMENT SHALL BE INSTALLED AND
 ARRANGED IN A MANNER THAT WILL PREVENT
 OBJECTIONABLE CURRENT OVER THE GROUNDING
 CONDUCTORS OR GROUNDING PATHS.THE
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 ONLY BE INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 102) NOTE:PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%, PER 215.3,230.42 ETC.
  
 103) NOTE: PLEASE SEE COMPLETE LOAD
 CALCULATIONS COULD NOT LOCATED FOR
 BUILDING, FUTURE ESTIMATED LOADS FOR
 RETAIL SPACE ETC. LOAD ANALYSIS AS SHOWN
 DOES NOT INDICATE HOW THIS LOAD CAME
 ABOUT? 220.3,220.10,220.13,220.11, ETC
 *UNIT METER CENTERS LOADS ARE SHOWN.
  
 104) NOTE: PLEASE PROVIDE LOADS FOR
 GENERATOR AND DIRECT LOAD CALCULATIONS
 FOR SHEDDING OF LOADS.
 PLEASE SEE THAT PLANS, RISER DID NOT
 INCLUDE A LOAD SUMMARY FOR THIS UNIT.
 215.5, 700.5
  
 105) NOTE: PLEASE SEE NOTE #16 ON RISER
 NOTES WHICH MENTIONS ONLY TWO MAIN
 CIRCUIT BREAKERS FOR STAND-BY SYSTEM,
 HOWEVER RISER SHOWS MORE THAN THE TWO
 LISTED? PLEASE CORRELATE. ONCE AGAIN THE
 GENERATOR SPECS ETC WERE NOT SUBMITTED.
 215.5
  
 106) NOTE: PLEASE CLARIFY WHY SOME
 ELEVATORS INDICATE "SHUNT TRIPS" AND
 OTHER DOES NOT?
 215.5
  
 107) NOTE: PLEASE VERIFY THE TAPPED
 CONDUCTORS SHOWN FROM TXRL TO RL. PLEASE
 SEE 240.21 AS THIS INSTALLATION DOES NOT
 SEEM TO MEET ANY OF THE EXCEPTIONS
 LISTED.
 I215.5
  
 108) NOTE: PLEASE SHOW VOLTAGE DROP FOR
 PANEL "HER". THIS MAY BE PART OF LOAD
 ANALYSIS AS PREVIOUSLY NOTED.
 FEEDER SCHEDULE MENTIONS FEEDERS ARE
 UPDATED FOR VD, HOWEVER THESE DO NOT
 SEEM TO SHOW THIS?
 215.5, 13.413.1.ABC.1
  
 109) NOTE: PLEASE ALSO SUBMIT THE
 VOLTAGE DROP FOR PANEL "HR" AS NOTED
 ABOVE.
  
 110) NOTE:PLEASE SEE MISSING
 CONDUCTORS FROM H-3 TO TRANSFORMER AND
 TO PANEL L3. 215.5, 240.4,310.16,240.21
 ETC
  
 111) NOTE: PLEASE SEE "HE3", MISSING
 CONDUCTORS FROM THIS PANEL TO
 TRANSFORMER AND TO PANEL
 LE3.215.3,240.4,310.16, 240.21
  
 112) NOTE:PLEASE SEE PANEL "HIA" SHOWS
 15 KVA TRANSFORMER, YET RISER SHOWS 75
 KVA. PLEASE CORRELATE>
 215.5
  
 113) NOTE: PLEASEPANEL "LR" WHICH IS
 SHOWN WITH A 100A MCB , HOWEVER THE
 CONDUCTORS TO THIS PANEL IS RATED FOR
 50A?S. PLEASE VERIFY THE CONDUCTORS AS
 THEY DO NOT TERMINATE IN OCP WHICH
 LIMITS THE LOADS FOR THE CONDUCTORS.
 PLEASE VERIFY WITH240.21C, (1-6)
  
 114) NOTE:PLEASE SEE THAT PANEL "LI"
 INDICATES FEED-THREE LUGS IF INDEED THIS
 IS THE INSTALLATION. 215.5
  
 115) NOTE:PLEASE SEE RETAIL COMMON
 "SHELL AREAS" SHALL CONTAIN MINIMUM
 LIGHTING AS REQUIRED AND PERFIRE
 MARSHAL'S OFFICE, HOWEVER PLEASE SEE
 THESE AREAS ARE ALL BEING SHOWN
 CIRCUITED TO PANELSWHICH UNDER THE
 BASE BUILDING. PLEASE PROVIDE NOTES ON
 PLANS, AS ALL OF THIS INTERIOR
 CIRCUITING WILL BE REQUIRED TO BE
 REMOVED AND RE-CIRCUITED TO THE PANELS
 AND SERVICE THESE TENANT SPACES ONCE
 PERMITTED.
 CROSSING OVER OF SERVICES, COMMON AREA
 BRANCH CIRCUITS IS NOT PERMITTED.
 230.70,225.25 ETC
  
 116) NOTE: PLEASE SEE 250.104 WHICH
 REQUIRES ?ALL OTHER METAL PIPING SYSTEMS
 TO BE PART OF THE BUILDINGS GROUNDING?.
 PLEASE SHOW ATTACHMENT OR NOTE;
  
 117) NOTE: PLEASE KNOW, MANY OF THE
 ABOVE ITEMS ARE REDLINED ON ONE SET OF
 THE MEP'S FOR MANY OF THE SD'S, RECEPTS,
 LTS ETC AND LOCATIONS NEEDED. PLEASE
 KNOW, THIS IS IN NO WAY ALL LOCATIONS
 WHICH MAY BE NEEDED. PLEASE GO OVER
 PLANS FOR ALL ITEMS.
  
 118) NOTE: PLEASE KNOW A DETAILED
 RESPONSE LETTER ON HOW ALL COMMENTS WERE
 ADDRESSED AND CLARIFICATIONS NEEDED.
 THIS WILL HELP IN EXPEDITING THE REVIEW
 PROCESS.
  
 119) NOTE: PLEASE SEE ALL COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 120) NOTE:ONCE ALL REVIEWS ARE
 COMPLETE AND BEFORE RESUBMITTING PLANS:
 "ALL OLD/VOIDED SHEETS SHALL BE REMOVED
 AND ONLY THE NEW REVISED SHEETS SHOULD
 BE INSERTED INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING".
 ONE SET OF ALL OLD/VOIDED SHEETS WHICH
 ARE REMOVED SHOULD BE SUBMITTED FOR
 REFERENCE ALONG WITH THE NEW SETS. ALL
 VOIDED SHEETS MUST BE REMOVED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-10 00:00:00*** ELECTRICAL REVIEW COMPLETED ***
 NOTES TO BE ENTERED ON MONDAY 3/13/06
 STATUS WILL BE "F".
2006-03-08 00:00:00REVIEW STILL IN PROGRESS,NOTES TO
 FOLLOW.
2006-03-06 00:00:00REVIEW CONTINUED.
2006-03-03 00:00:00REVIEW STOPPED. REVIEW TO CONTINUE ON
 MONDAY 3/6
2006-03-02 00:00:00ELEC REVIEW STARTED FOR REVIEW, NOTES TO
 FOLLOW. REVIEW IN PROGRESS.
2006-02-10 00:00:00ONE ROLL OF MEP'S IN ELECTRICALTO
 REVIEW.