Plan Review Notes
Plan Review Notes For Permit 05121248
Permit Number 05121248
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05121248
 ADD: 419 LAKEVIEW
 CONT: ? PLAN REVIEW?
 TEL(305) 322-4105
  
  
 -OPERA PLACE-
  
 ARCHITECT FIRM BERMELLO, AJAMIL &
 PARTNERS
 HECTOR R. VALVERDE
  
 ENGINEERS: PEDRO JOSE DUQUESNE
  
  
 1ST REVIEW
 ACTION DENIED
 CODE: 2004 FL BUILDING CODE
  
 * FL BLD CODE = 2004 WEST PALM BEACH
 ADMINISTRATIVE CODE
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE NEW
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) NOTE THIS IS A THRESHOLD BUILDING
 REQUIRING (3) OF ALL SUBMITTALS,
 PLANS, REPORTS, REVISIONS OR SUBMITTALS
 TO THE BUILDING DEPARTMENT FOR OUR
 RECORD. THESE DOCUMENTS WILL REQUIRE
 ORIGINALS WITH RAISED SEAL, SIGNATURE
 AND DATE.
 PLANS, SPECIFICATIONS,REPORT OR
 OTHER DOCUMENTS PREPARED BY THE
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE
 SEAL OF THE DESIGN PROFESSIONAL
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEER
 FL ATATE STAT: 61G16.003 ARCHITECT
  
 2)FL S S 713.13:
 NOTICE OF COMMENCEMENT, TO BE RECORDED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE:
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) DISCREPANCY BETWEEN THE PERMIT
 APPLICATION AND THE SURVEY. THE
 APPLICATION INDICATES THE STREET
 LAKEVIEW WHEREAS THE SURVEY IN
 THE SOUTH SIDE OF THE PROPERTY
 OKEECHOBEE BLVD. OKEECHOBEE BLVD ISN'T
 DESIGNATED UNTIL AFTER THE WEST BOUND
 TRAFFIC CROSSES OVER THE FEC RAILROAD
 TRACKS.
  
 4)SURVEY ONLY ONE ORIGINAL, SUBMIT (3)
 ORIGINAL SURVEYS WITH RAISED SEAL,
 SIGNATURE W/ DATE.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL S. S. 553.71(7)
 (THRESHOLD BUILDING)
 ANY BUILDING GREATER THAN (3) STORIES OR
 50 FEET IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN FLORIDA BUILDING CODE WHICH
 EXCEEDS 5,000 SQ FT IN AREA AND AN
 OCCUPANT LOAD OF GREATER THAN 500 PEOPLE
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION
 PLAN MUST BE SUBMITTED TO THE
 ENFORCEMENT
 AGENCY PRIOR TO THE ISSUANCE OF A
 PERMIT FOR THE CONSTRUCTION OF THRESHOLD
 BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND STANDARDS
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT
 HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING
 WITH ENGINEERING STANDARDS TO PRESERVE
 THE POSITIVE PATTERNS OF THE AFFECTED
 SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGH WINDS.
 ANY PERSON WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. A OR B.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 12)1609.1.4 PROTECTION OF OPENINGS
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886
 ASTM E 1996, OR MIAMI-DADE TAS 201,202
 AND 203 REFERENCED THEREIN AS FOLLOWING:
  
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 13) PLANS INDICATE THAT THIS PERMIT
 WILL BE PHASED, DOES THIS MEAN
 ENTIRE BUILDING IS UNDER ONE PERMIT OR
 WILL THIS PROJECT BE PERMITTED
 SEPARATELY ?
  
 14) PLEASE CONTACT LILI URSA, MIS
 TECHNICIAN MIS CONTACT FOR ADDRESSING
 ISSUES.
 PLEASE SEE ADDRESSING REQUIREMENT FOR
 TWIN TOWERS UNDER ONE PROPERTY CONTROL
 NUMBER. LILI URSA (561)822-1234
  
 15) VARIOUS SHEETS EXAMPLE A-2.01 OR
 A-3.01 FOR SCALE OF DRAWINGS NOTED IN
 TITLE BLOCK SCALE AS NOTED, BUT NOT ON
 THAT PAGE BUT ON THE PROJECT INDEX PAGE
 THE PROCESS TO GO BACK TO THIS PAGE IS
 VERY TIMELY!!!! PLEASE PUT THE SCALE ON
 THE SAME SHEET!
  
 16) A-2.01 THE ELEVATOR LOBBY E118
 COMMON TO ELE CORE 2 & 3 SHOWS A 2INCHES
 CHANGE IN GRADE? VERTICAL ACCESSIBILITY
 11-4.1.2 VERTICAL ACCESSIBILITY NOTHING
 IN THIS CODE SHALL BE CONSTRUED TO
 RELIEVE THE OWNER OF ANY BUILDING OR
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.
  
 17) A-2.01 UNKNOWN ROOM USAGE BY
 ROOM W125 & W109?
  
 18) RETAIL# 9 AS WELL AS THE MAIN
 LOADING DOCK W142, PLEASE INDICATE A
 TRUCK IN THE LOADING BAY, IT APPEARS
 THOSE 2 TRAFFIC LANES TO THE PARKING
 GARAGE WOULD BE BLOCKED.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THEIR OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 19)A-2.01- A-2.02
 19A)THE MEZZANINE LEVEL,
 PLEASE PROVIDE THE GROSS FLOOR AREA FOR
 EACH TENANT SPACE AND THE FLOOR AREA FOR
 THE MEZZANINE LEVEL IN EACH TENANT SPACE
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
 505.4 OPENNESS. A MEZZANINE SHALL BE
 OPEN
 AND UNOBSTRUCTED TO THE ROOM IN WHICH
 SUCH MEZZANINE IS LOCATED EXCEPT FOR
 WALLS NOT MORE THAN 42 INCHES HIGH,
 COLUMNS AND POSTS. SEE EXAMPLE
  
 19B) PLANS DO NOT SHOW STAIRS TO THE
 MEZZANINE LEVEL, WILL THE MEZZANINE
 LEVEL BE BUILT AS PART OF THE PERMIT
 OR WOULD THIS LEVEL BE BUILT AS PART OF
 A TENANT FIT UP?
  
 19C) ONE CONSIDERATION THAT NEEDS TO BE
 NOTED BY THE DESIGN TEAM.
 ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT),IF THE MEZZANINE
 LEVEL IS BUILT WITH THE SHELL WITH
 STAIRS, IT SHOULD BE NOTED THAT THE AREA
 BENEATH THE MEZZANINE CAN NOT BE
 ENCLOSED SEE 505.2: THE ENCLOSED
 PORTIONS OF ROOMS SHALL NOT BE FIGURED
 IN A DETERMINATION OF THE SIZE
 ROOM IN WHICH THE MEZZANINE IS LOCATED.
 IN DETERMINING THE ALLOWABLE MEZZANINE
 AREA, THE AREA BENEATH THE MEZZANINE CAN
 NOT BE INCLUDED IN THE 1/3RD AREA OF THE
 ROOM.
  
 20) A-2.01 NOTE UPPER RIGHT OF SHEET
 INDICATES THAT MECHANICAL EQUIPMENT
 PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH: VAN ACCESSIBILITY,11-4.1.
 IN PARKING STRUCTURES, ONE IN
 EIGHT ACCESSIBLE SPACES, BUT NOT LESS
 THAN ONE, SHALL BE VAN ACCESSIBLE.
 SHALL BE DESIGNED AS REQUIRED, SEE
 11-4.6.3 . THE VERTICAL CLEARANCE OF
 SUCH SPACES SHALL COMPLY WITH
 11-4.6.5 . ALL SUCH SPACES MAY BE
 GROUPED ON ONE LEVEL OF A PARKING
 STRUCTURE. WHEN SUCH SPACES ARE
 IN A PARKING STRUCTURE AND ONLY
 EIGHT MEET THE HEIGHT REQUIREMENT
 SECTION 11-4.6.5 , THEY SHALL BE
 DESIGNATED AS REQUIRED BY SECTION
 11-4.6.4 .
  
 21) LS-2.09 POOL DECK, THE CALCULATION
 FOR THE GYM TO USE THE 50 OCCUPANT LOAD
 / SQ FT, SEE TABLE 1004.1.2 THIS
 USED WHEN EQUIPMENT IS SHOWN
 PLAN. WHEN NO EQUIPMENT IS SHOWN ON THE
 PLAN
 OCCUPANT LOAD IS FIGURED @ 15 SQ FT/
 OCCUPANT. THIS CALCULATION WILL BE OVER
 THE ALLOWABLE
 STAIRWELLS AND DOORWAYS OCCUPANT LOADS.
  
 22)A-2.01/ A-2.02/ A-3.02CD/
 A7.13 DETAIL# 2THE MAIN LOBBY
 CUTS OFF THE AREA JUST PAST THE ELEVATOR
 BALCONY WITH HANDRAIL OR IF A GLAZED
 ENCLOSURE. THIS INFORMATION IS REQUIRED
 TO
 DETERMINE IF AN ATRIUM WAS CREATED.
 ATRIUM . AN OPENING CONNECTING
 MORE STORIES OTHER THAN ENCLOSED
 STAIRWAYS, ELEVATORS, HOIST WAYS,
 ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT
 WHICH IS CLOSED AT THE TOP AND NOT
 DEFINED AS A MALL. STORIES, AS
 THIS DEFINITION, DO NOT INCLUDE
 BALCONIES WITHIN ASSEMBLY GROUPS
 MEZZANINES THAT COMPLY WITH SECTION 505.
  
 23A) A-3.01AB: SUBMIT STATE APPROVED
 PLANS FOR THE PRE-MANUFACTURED TICKET
 BOOTH, FOR THIS WIND ZONE.
  
 23B) PROVIDE PLANS THAT SHOW VERTICAL
 ACCESSIBILITY FOR BOOTH. PLANS
 SHOW A RAISED CURB, NOT MEETING
 ACCESSIBILITY REQUIREMENTS.
  
 24) A-3.01AB CORRIDOR E140 SHOW
 CHANGE IN ELEVATION REQUIRING
 ON BOTH SIDES OF THE CORRIDOR.
 11.4.8.5. HANDRAILS: IF A RAMP HAS A
 RISE GREATER THAN 6? OR A HORIZONTAL
 PROJECTION GREATER THAN 72INCHESTHEN
 IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 25) STORAGE ROOM E141 PROVIDE WHAT TYPE
 OF MATERIALS ARE TO BE STORED.
 INDICATE IF S1 OR S2 TYPE STORAGE,
 WALL AND DOOR RATINGS ACCORDING TO
 311.2 MODERATE-HAZARD S-13HR
 311.3 LOW-HAZARD S-22HR
 SAME ISSUES WITH STORAGE ROOMS
 E124 & E127.
  
 26) A3.01AB ROOM E109A PROVIDE
 ACCESSIBILITY:11-4.1.2 VERTICAL
 ACCESSIBILITY, NOTHING IN THIS CODE
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, STRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIBLE GRADE LEVEL.
  
 27) A3.01AB ROOM E125 RES # 2 THE
 PLANS INDICATE 2HR RATED WALLS,
 DOOR LISTING OR RATING?
  
 28)A3.01BC RAMPS ON BOTH SIDES OF THE
 TRASH ROOM E119 OVER 30?-0" REQUIRE
 HANDRAILS.11-4.8.2
 THE MAXIMUM RISE FOR ANY RUN SHALL BE 30
 INCHES (760 MM) (SEE FIGURE 11-16)
 CURB RAMPS AND RAMPS TO BE CONSTRUCTED
 ON EXISTING SITES OR IN EXISTING
 BUILDINGS OR FACILITIES MAY HAVE LIMITS.
 11-4.8.5 HANDRAILS.
 IF A RAMP RUN HAS A RISE GREATER THAN 6
 INCHES (150 MM) OR A HORIZONTAL
 PROJECTION GREATER THAN 72 INCHES
 MM), THEN IT SHALL HAVE HANDRAILS
 BOTH SIDES. HANDRAILS ARE NOT REQUIRED
 ON CURB RAMPS OR ADJACENT TO SEATING IN
 ASSEMBLY AREAS. HANDRAILS SHALL COMPLY
 WITH SECTION 11-4.26
  
 29) NOT USED
  
 30) A3.01BC ROOM E103 FIRE COMMAND
 CENTER MISSING 1HR RATED WALLS
 911.1WHERE REQUIRED BY OTHER SECTIONS
 THIS CODE, A FIRE COMMAND CENTER FOR THE
 FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED. THE LOCATION AND ACCESSIBILITY
 OF THE FIRE COMMAND CENTER SHALL
 SEPARATED FROM THE REMAINDEROF THE
 BUILDING BY NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER.
  
 31)SAME COMMENT AS 22, ELEVATOR LOBBY
 IS
 OPEN TO FLOOR ABOVE, IS THIS AN ATRIUM?
  
 32) A3.02BC TRASH ROOM CHUTE #1
 DESIGNATION FOR FIRE RATING? LOCATED IN
 ELECTRIC ROOM?
  
 33) A3.02BC STAIRWELL# 2A AT CORRIDOR
 EM30 WALL DESIGNATION ?D? REQUIRES A
 2 HR RATED WALL. CORRECT SEE 707.4.
  
 34) A3.02BC MESSAGE ROOM VS STAIRWELL
 ALSO REQUIRES A 2HR RATED WALL.707.4
  
 35) A3.02BC MEDIA ROOM EM 33
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIBLE
 GRADE LEVEL.
  
 36) A3.02 BC MEETING ROOM EM23 PLANS
 INDICATE
 A SHAFT NEXT TO THIS ROOM, PLANS DO NOT
 INDICATE THE
 FIRE RATING OF THIS SHAFT. SEE 707.4.
  
 37) A3.02CD SAME COMMENTS AS 27- 36.
  
 38) STAIR TOWER # 1 INDICATES A WALL
 SECTION # 11
 OF A7.01 ON THIS SHEET,SEE NOTE # 1
 ABOUT PIPES
 SHOULD ALSO INCLUDE:
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED, EXCEPT
  
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION
 OPENINGS, WHETHER THE PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 39) A3.02CD PLANS INDICATE ROOM # WM29
 AN ELECTRICAL ROOM AND WITHIN THE ROOM A
 TRASH CHUTE.707.13.3 REFUSE AND LAUNDRY
 REQUIRE ACCESS ROOMS BEFORE ENTERING THE
 REFUSE CHUTE ROOM.
 ACCESS OPENINGS FOR REFUSE AND CHUTES
 SHALL BE LOCATED IN ROOMS, COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION THAT
 HAS A FIRE-RESISTANT
 RATING OF NOT LESS THAN 1 HOUR OPENINGS
 INTO THE ACCESS ROOMS AND PROTECTED BY
 OPENING PROTECTIVE OF A FIRE PROTECTION
 RATING OF NO LESS THAN 3/4 HOUR AND
 SHALL BE SELF-AUTOMATIC-CLOSING UPON THE
 DETECTION OF SMOKE.
 ELECTRICAL ROOMS ARE TO BELOCKED AN
 ONLY
 AUTHORIZED PERSONAL HAVE ACCESS KEYS TO
 THIS
 AREA. THE SECOND ISSUE IS THRASH CHUTES
 HAVE A HIGHER RISK OF FIRE (NFPA 70
 AUTOMATIC FIRE SPRINKLERS), IT
 UNWISE TO PUT SUCH A HIGH RISK AREA
 INTO THE ELECTRICAL ROOMS. SEE
 COMMENTARY 707.13.707.13.1 & 707.13.3.
  
 40) A3.02 DA IT APPEARS THAT THE REFUSE
  
 CHUTE ENCLOSURE HAS A DOOR ON THE CHUTE
 BUT NO ACCESS ROOM.707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS REQUIRED.
  
 41) A3.02DA COMMON WALL BETWEEN THE
 PARKING GARAGE AND RETAIL #9 NO FIRE
 RATING
 DESIGNATION.
  
 42) A3.03AB STAIRWELL 3A & 3,THIS
 COMMENT IS
 TRUE FOR ALL FLOORS WITH THE TWO EGRESS
 DOORS: FL ACCESSIBILITY 11-4.13.7
 TWO DOORS IN SERIES. THE MINIMUM SPACE
 BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES SHALL BE 48 INCHES (1219 MM) PLUS
 THE WIDTH OF ANY DOOR SWINGING INTO THE
 SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY
 FROM THE SPACE BETWEEN THE DOORS FIGURE
 11-26 (A)].
 FAIR HOUSING ANSI A117.1-4
  
 43) A3.03BC SEE STAIR 2A AND 2 , A
 COLUMN (J1/9.3) IS LOCATED IN THE MEANS
 OF EGRESS
 FROM THE GARAGE TO STAIR TOWER.
 ACCESSIBLE ROUTE WILL REQUIRE A 44".
  
 44) A3.03CD SEE STAIR 2A AND 2, A COLUMN
 (J1/9.3) IS LOCATEDIN THE MEANS OF
 EGRESS
 FROM THE GARAGE TO THE STAIR TOWER.
 ACCESSIBLE ROUTE WILL REQUIRE 44 INCHES.
  
 45) A3.03BC PARKING SPACE 96 SHOULD BE
 12 FT WIDE , HANDICAPPED ACCESSIBILITY.
  
  
 46) A3.03BC SHAFT BY STAIRWELL
 COMMON TO ALL FLOORS, IS MISSING THE
 FIRE
 RATING.707.4 FIRE RESISTANCE
  
 47) A3.03AB UNIT 2B EXTERIOR SLIDING
 GLASS DOOR TO THE BALCONY, THROUGH A4.05
 AND ALL SIMILAR DETAILS HAVE THE DOORS
 LABELED OR DIMENSIONED.
  
 48) NOTE PLANS INDICATE USE OF SLIDING
 GLASS DOORS
 FOR VARIOUS UNITS, PROVIDE DETAILS AND
 PRODUCT APPROVAL THAT INDICATEWHEN THE
 UNIT IS OPEN, THERE WILL BE 32 INCHES
 CLEAR SPACE. FAIR HOUSING. THIS WILL
 HOLD TRUE FOR ALL UNITS PROVIDING ACCESS
 TO
 BALCONY THROUGH SLIDING GLASS DOORS.
 PLEASE PROVIDE A SILL DETAIL INDICATING
 COMPLIANCE WITH
 SLIDING GLASS DOOR FOR FAIR HOUSING,
 SLIDING GLASS DOORS ARE SECONDARY DOOR
 LEADING TO BALCONIES OR LANDINGS .FAIR
 HOUSING CHAPTER 4.
  
 49) A3.03BC UNIT 2C MASTER BED, SEE
 SHEET A4.06 ANDB2" A8.05 LISTING. THE
 ACTIVE LEAF OF THE PAIR OF DOORS MUST BE
 32 CLEAR WHEN MEASURE 90 DEGREESTO THE
 DOOR JAMB.
  
 50) SAME SHEET A4.06 UNIT 3A,
 FH 404.2.2 DOUBLE LEAF DOORWAY
 LEAST ONE OF THE ACTIVE LEAVES OF THE
 PAIR OF
 DOORS TO BE 32 INCHES WITH 2 INDEPENDENT
 LEAVES SHALL COMPLY WITH 404.2 WIDTH)
 AND 404.2.4 (MANEUVERING CLEARANCES).
  
 51) A4.07 PH-1 2 PROBLEMS ENTRY DOORS
 WHERE THE DOORWAY IS DIMENSIONED FH
 404.2.2 DOUBLE LEAF DOORWAY LEAST ONE OF
 THE ACTIVE LEAVES 32 INCHES DOORWAYS
 WITH 2 INDEPENDENTLY
 LEAVES SHALL COMPLY WITH 404.2 (WIDTH)
 AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 52) THE SAME DETAIL INDICATES DOUBLE
 DOORS AT
 BEDROOM.
  
  
 53) A4.08 PH-3 THE EXTERIOR SWINGDOORS
 ARE
 MISSING A DESIGNATION. THE SWING DOOR TO
 THE MASTER BEDROOM INDICATES AFIVE
 FOOT SWING WHERE AS THE DOOR SCHEDULE
 INDICATES A PAIR OF DOORS.
 FH 404.2.2 DOUBLE LEAF DOORWAY, LEAST
 ONE OF THE ACTIVE LEAVES TO BE 32INCHES
 WITH 2 INDEPENDENT LEAVES SHALL COMPLY
 WITH 404.2 (WIDTH) AND404.2.4
 (MANEUVERING
 CLEARANCES).
  
 54) SAME SHEET A4.06 UNIT 3A FH 404.2.2
 DOUBLE LEAF DOORWAY LEAST ONE OF THE
 ACTIVE LEAVES
 CLEARANCES).
  
 55) A4.07 PH-1 2 PROBLEMS ENTRY DOORWAY,
 WHERE THE DOORWAY IS DIMENSIONED
 FH 404.2.2 DOUBLE LEAF DOORWAY
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2 WIDTH) AND 404.2.4
 (MANEUVERING
 CLEARANCES).
  
 56) THE SAME DETAIL INDICATES
 BEDROOM.
  
 57) A4.08 PH-3 THE EXTERIOR SWING DOOR
 IS MISSING A DESIGNATION. MASTER BEDROOM
 SWING DOOR VS A PAIR OF DOORS.FH
 404.2.2 DOUBLE LEAF DOORWAY
 LEAST ONE OF THE ACTIVE LEAVES IN
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2
 WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 58) A4.08 PH-3, DOORS TO BALCONY NOT
 LABELED, NO
 DOOR DESIGNATION. SEE NOTE 48 THIS IS
 COMMON TO ALL UNITS!!!
  
  
 60) A4.11 PH LOFT-01 ENTRY DOOR, SEE HOW
 THE ENTRY DOOR IS DIMENSIONED VS THE
 DOOR SCHEDULE.
  
 61) A4.11 PH L-01 BEDROOM DOOR IS A PAIR
 OF DOORS, FH 404.2.2 DOUBLE LEAF DOORWAY
 AT
 LEAST ONE OF THE ACTIVE LEAVES IN
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2
 (WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 62) A4.12 BEDROOM DOOR B1 BEDROOM DOOR
 IS A PAIR OF DOORS, FH 404.2.2 DOUBLE
 LEAF DOORWAY AT LEAST ONE OF THE ACTIVE
 LEAVES IN DOORWAYS WITH 2 INDEPENDENT
 LEAVESSHALL COMPLY WITH 404.2
 (WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 63) A3.04CD SHAFT WALL DETAIL AT LINE
 J.2/6 INDICATES A SECTION OF FLOOR SLAB.
 A10.02 FLOOR SLAB EXPANSION JOINT
 DETAILS INDICATE A SHAFT THROUGH THE
 FLOOR SLAB. THEN NEXT TO IT IS THE 8
 INCH MASONRY WALL WILL ADDITIONAL STEEL
 BE REQUIRED IN THE SLAB FOR REINFORCING
  
 64) A3.09BC/ A3.09CD ROOM E808 THE PLANS
 INDICATE GENERATOR ROOMS WHAT TYPE OF
 GENERATOR THIS WILL BE.
  
 65) A3.09BC/ A3.09CD RESTROOMS E809,
 E810, W809 & W810. PROVIDE DIMENSIONS TO
 PLAN SEE, FAIR HOUSING ANSI
 A117.1/403.5.1
 CLEAR WIDTH AT TURNS.
  
 66) A3.09 BC/ A3.09CD PROVIDE DETAILS
 FOR
 LOBBY E808A/ W808A AND HANDICAPPED
 SHOWER .FAIR HOUSING GUIDELINES
  
 67) A3.09 BC/ A3.09CD IT APPEARS THAT
 NUMBER 2/808 & 1/804 DOES NOT HAVE THE
 REQUIRED 18 INCHES ON THE PULL SIDE OF
 THE LATCH. FAIR HOUSING ANSI A117.1
 404.2 MANEUVERING CLEARANCES AT DOOR
  
 68) A3.09AB/ A3.09DA POOL DECK. L -2.3
 FOR TRELLIS PLANS. THE TRELLIS PLANS
 INDICATE SEE STRUCTURAL PLANS FOR
 DETAILS. THERE IS NO INFORMATION ON THE
 STRUCTURAL PLANS AS TO DESIGN OF THE
 TRELLIS SYSTEMS. SEE NOTE ON SHEET ABOUT
 THE EMBEDDED ELEMENTS AND FASTENING
 ELEMENT AT POST TENSION SLABS AND BEAM.
  
 69) A3.09AB/ A3.09DA TRELLIS SYSTEM IF
 FABRIC IS TO BE APPLIED, SEE 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE
 FABRIC AT WIND VELOCITIES OF 75MPH
 SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF
 WIND GUST 90 MPH
 2.IMPORTANCE FACTOR BASED
 HAZARD TO HUMAN LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR
 DEFINED IN CHAPTER 16 .
 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY
 MEMBRANE COVERED STRUCTURE DESIGN WITH
 A PERMANENT OR NONREMOVABLE FABRIC
 MEMBRANE SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED
 IN CHAPTER 16.
 2.IMPORTANCE FACTOR BASED ON LOW
 HAZARD TO HUMAN LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS
 DEFINED IN CHAPTER 16 .
  
 70) A3.09AB, A3.09DA NOTE ON POOL PATIO
 DRAWINGS FOR ANCHORING TO CONCRETE
 PAVERS.
 STRUCTURAL PLANS DO NOT HAVE
 INFORMATION ON THIS NOTE. WIND AND
 UPLIFT CRITERIA.
 106.1.2 ADDITIONAL DATA.
 BUILDING OFFICIAL MAY REQUIRE ADDITIONAL
 COMPUTATIONS, STRESS DIAGRAMS, DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION
 OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THEIR OF OFFICIAL
 SEAL,SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 71)A3.09AB/ A3.09DA. PLEASE PROVIDE
 THE CHANGE IN GRADE FOR THE POOL DECK.
 INCLUDE STAIR INFORMATION FOR THE TREAD
 & RISER AND THE HANDICAPPED RAMP RISE
 AND LENGTH OF RAMPS, IF AN INTERMEDIATE
 LANDING IS REQUIRED, IF HANDRAILS ARE
 REQUIRED. FAIR HOUSING
  
 72) A3.09AB/ A3.09CD ELEVATOR SHAFT WALL
 CONSTRUCTION FBC 707.4 2HR WALLS WITH1
 1/2 HR PROTECTIVE.
  
 73) A3.09AB/ A3.09BC PLANS INDICATE
 DECORATIVE MANSARD ROOF, PROVIDE A
 SECTION PROVIDING THE BUILDING ELEMENTS.
 (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTSSHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED & SHOW DETAIL THAT IT WILL
 CONFORM TO THE
  
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, AND RULES, REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICIAL.
  
 74) A5.01-A5.04 ELEVATIONS FOR BUILDING
 PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES FOR ALL WINDOW AND DOOR
 OPENINGS. INDICATE THE INTERIOR ZONES
 WELL AS END ZONES. 1609.1.1
 DETERMINATION OF WIND LOADS WIND LOADS
 ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 6 OF ASCE 7 WIND
 SHALL BE ASSUMED TO COME FROM ANY
 HORIZONTAL DIRECTION AND WIND PRESSURES
 SHALL BE ASSUMED TO ACT NORMAL TO THE
 SURFACE CONSIDERED.
  
 75) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE VARIOUS ROOF ZONES
 INTERIOR ROOF ZONE#1, EDGE ZONE # 2 &
 END ZONE S# 3. 1609.1.1.
  
 76) NOTE THIS PROJECT DOES HAVE VARIOUS
 TYPE OF ROOF FINISHES. EACH OF THE ROOF
 FINISHES AND UNDERLAYMENTS WILL REQUIRE
 FL COVERSHEETS WITH THE ASSOCIATED NOA
 OR PRODUCT TESTING REPORT.
 NOTE IF THE PRODUCT APPROVALS HAVE A
 LIMITATION#7 OR LIMITATION #9.
 LIMITATION# 7 ALLOWS FOR THE DESIGN
 PROFESSIONAL TO CALCULATE AND FIGURE
 ENHANCED FASTENING IN THE ZONES 2 & 3.
  
 77)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL
 OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 78) 1609.6.5 COMPONENTS AND CLADDING
 PRESSURE FOR WIND LOADING ACTIONS ON
 COMPONENTS AND CLADDING SHALL BE
 DETERMINED FROM TABLE 1609.6B FOR
 ENCLOSED PORTIONS OF THE BUILDINGS TABLE
 1609.6C FOR OVERHANGS, BASED ON THE
 EFFECTIVE AREA FOR THE ELEMENTS UNDER
 CONSIDERATION. THE PRESSURES IN 1609.6C
 INCLUDE INTERNAL PRESSURE.
 THE PRESSURE SHALL BE APPLIED IN
 ACCORDANCE
 WITH THE LOADING DIAGRAMS IN FIGURE
 1609.6C .
 FL BLD CODE 1609.6.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF
 TESTING REPORTS,MISSING REPORT AS
 FOLLOWS:
 A) WINDOWS FIXED, STOREFRONT
 B) OPERABLE WINDOWS
 C) SPANDREL GLASS
 D) MULLIONS
 E) EXTERIOR SWING METAL DOORS
 F) EXTERIOR SWING GLAZED DOORS
 G) SLIDING GLASS DOORS
 H) WALL LOUVERS
 I) TRUSS ANCHORS
 J) STORM SHUTTERS
 K) PRE-MANUFACTURED A/C STANDS
 L) ROOFING ASSEMBLIES
 M) EFIS SYSTEMS
  
 79) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 80) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBSTRATE.
  
 81) PARKING GARAGE THE BOTTOM FLOORS ARE
 TO BE
 CONSIDERED ENCLOSED AND TO MEET THE
 VENTILATION REQUIREMENTS 406.6.3 AND THE
 F BC MECHANICAL.
  
 82) THE UPPER LEVELS OF THE PARKING
 GARAGE ABOVE
 THE MEZZANINE LEVEL PLEASE PROVIDE
 CALCULATIONS TO SHOW COMPLIANCE WITH
 406.3.3.1 FOR OPEN PARKING GARAGE.
 406.3.3.1 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE
 EXTERIOR SIDE OF THE STRUCTURE SHALL
 HAVE UNIFORMLY DISTRIBUTED OPENINGS ON
 TWO OR MORE SIDES. THE AREA OF SUCH
 OPENINGS IN EXTERIOR WALLS ON A TIER
 MUST BE AT LEAST 20 PERCENT OF THE TOTAL
 PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS
 CONSIDERED TO BE PROVIDING NATURAL
 VENTILATION SHALL CONSTITUTE A MINIMUM
 OF 40 PERCENT OF THE PERIMETER OF THE
 TIER. INTERIOR WALLS SHALL BE AT LEAST
 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 EXCEPTION: OPENINGS ARE NOT REQUIRED TO
 BE DISTRIBUTED OVER 40 PERCENT OF THE
 BUILDING PERIMETER WHERE THE REQUIRED
 OPENINGS ARE UNIFORMLY DISTRIBUTED OVER
 TWO OPPOSING SIDES OF THE BUILDING.
  
 83) VERTICAL EXIT ENCLOSURES IN HIGH
 RISE BUILDINGS
 WILL REQUIRE SMOKE DETECTION AT THE
 ENTRANCE TO THE ENCLOSURES. THE ACCESS
 CORRIDORS SHOW SMOKE DETECTION IN THE
 CORRIDORS BUT NOT DIRECTLY IN FRONT OF
 THE DOORWAY, SEE 909.20.6
  
 84) E SHEETS, HIGHRISE VERTICAL EXIT
 ENCLOSURES THAT OPEN
 DIRECTLY INTOPARKING GARAGES SHOULD
 ALSO HAVE SMOKE DETECTORS IN ACCORDANCE
 WITH 909.20.6
  
 85) REVISIT E SHEETS SOME OF THE UNITS
 ARE MISSING
 THE SMOKE DETECTORS ON THE EXTERIOR OF
 THE BEDROOM SIDE, NOTE LOCATION OF
 SUPPLIES AND RETURN AIR SHOULD BE
 INDICATED FOR LOCATION OF DETECTORS.
  
 COMMENTS 86-105 TO BE FORTH COMING !
 COPYING FROM WORD.