| 2006-03-27 00:00:00 | ****DENIED 2ND TIME**** |
| | REFERENCE:FBC-2004 PLUMBING, AND CITY OF |
| | WESR PALM BEACH, AMENDMENTS TO FBC-2004, |
| | CHAPTER 1, ADMINISRATION: |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATION REQUIRED FOR PLAN REVIEW: |
| | |
| | 1. UTL-SINK SHOWN ON PLUMBING ISOMETRIC |
| | DRAWING ON SHEET E-1 CAN NOT DISCHARGE |
| | INTO A BATHROOM GROUP. MUST BE |
| | DOWNSTREAM OF BATHROOM GROUP, PER |
| | FBC-2004 PLUMBING SEC. 909.1. PLEASE |
| | CORRECT. |
| | 2. TUB SHOWN ON PLUMBING ISOMETRIC DRAW- |
| | ING ON SHEET E-1 IS NOT VENTED, SHOULD |
| | BE PART OF BATHROOM GROUP. PLEASE |
| | CORRECT. |
| | 3. ITEM #14 PLUMBING NOTES ON E-1. AIR |
| | CHAMBERS ARE NOT TO CODE, MUST BE WATER |
| | HAMMER ARRESTERS TO BE INSTALLED PER |
| | FBC-2004 PLUMBING SEC. 604.9. PLEASE |
| | CHANGE NOTES TO REFLECT THIS. |
| | 4. PER 708.3.4, A CLEANOUT SHALL BE |
| | PROVIDED AT THE BASE OF EACH WASTE OR |
| | SOIL STACK. THE PLUMBING ISOMETRIC |
| | DRAWING ON SHEET E-1 DOES NOT INDICATE |
| | THIS, PLEASE CORRECT. |
| | 5. PLUMBING ISOMETRIC SHOWN ON E-1 |
| | INDICATES BUILDING SEWER INSTALLED |
| | PARALLEL TO THE OUTSIDE OF THE BUILDING |
| | WITH BRANCHES TO THE FIXTURES ON INSIDE |
| | OF BUILDING. NOTE: PER 708.3.5 BUILDING |
| | DRAIN AND BUILDING SEWER JUNCTION, THERE |
| | SHALL BE A CLEANOUT NEAR THE JUNCTION OF |
| | THE BUILDING DRAIN AND THE BUILDING |
| | SEWER. PLEASE CORRECT DRAWING TO REFLECT |
| | THIS. |
| | 6. PER CHAPTER 1, SEC. 106 , SHEET E-1 |
| | DRAWING NEEDS TO BE SIGNED BY DESIGNER. |
| | 7. NOTE: CHANGES TO BE IDENTIFIED BY |
| | TRIANGLES, CLOUDS OR OTHER AND NOTE ON |
| | REVISIONS ON DRAWING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |