| Date |
Text |
| 2006-03-10 00:00:00 | ********** UNSAT ************* |
| | |
| | ** PLEASE KNOW, THIS IS THE FIRST TIME |
| | ELECTRICAL PLANS ARE BEING SUBMITTED FOR |
| | REVIEW. |
| | |
| | 1)NOTE: PLEASE CORRELATE ELECTRICAL |
| | PLANS WITHY MECHANICAL PLANS. NEED TO |
| | VERFIY EQUIPMENT SIZES FOR AHU, AND CU, |
| | HOWEVER MECHANICAL PLANS ARE BLANK? |
| | |
| | 2)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT |
| | PER 424.3B, 125%. |
| | PLEASE ALSO SEE OCP LISTED FOR CU SEEMS |
| | HIGH, PLEASE VERIFY. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PLANS, AS PLANS INDICATE A MAIN |
| | DISCONNECT OUTSIDE AND RISER DOES NOT?? |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE A DISCONNECT SHALL BE |
| | REQUIRED FOR WATER HEATER. "PLUG-IN" MAY |
| | NOT BE USED. |
| | 422.30,31 |
| | |
| | 5)NOTE: PLEASE SEE NO DISCONNECT IS |
| | BEING SHOWN FOR AHU? |
| | 440.11 |
| | |
| | 6)NOTE: PLEASE SEE NO DISCONNECT IS |
| | BEING SHOWN FOR CU? |
| | PLEASE SEE PLANS INDICATEA 220V GFI?? |
| | FOR DISCONNECT?? 440.11 |
| | |
| | 7)NOTE: PLEASE SEE BATH RM RECEPT SHALL |
| | BE EITHER MOVED IN BETWEEN BOTH LAV'S OR |
| | ADD AN ADDITIONAL GFI. PLEASE KNOW, YOU |
| | CAN NOT CROSS OVER A LAV TO PLUG IN AN |
| | APPLIANCE. |
| | 210.52D. |
| | |
| | 8)NOTE: PLEASE LIST THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER |
| | 210.52D,210.11C3, THESE SHALL BE 20A, |
| | #12, |
| | |
| | 9)NOTE: PLEASE SEE SOME WALL AREAS WHICH |
| | SEEM TO INDICATE MISSING RECEPTS PER |
| | 210.52 |
| | PLEASE SEE REDLINED LOCATIONS ON PLANS. |
| | |
| | 10)NOTE: PLEASE SEE 2002 NEC FOR ARC |
| | FAULT PROTECTION REQUIREMENTS. PLEASE |
| | SEE NOTES ARE BEING REFERENCED FROM THE |
| | 1999 NEC. PROTECTION IS REQUIRED FOR ALL |
| | "OUTLETS", FANS, LTS SD'S, ETC. |
| | |
| | 11)NOTE: PLEASE SEE NOTE ON PLANS |
| | MENTIOSN TO HAVE SD'S WIRED TO KIT/BATH |
| | LTS, THIS IS OK, HOWEVER THEN THOSE |
| | CIRCUITS WOULD ALSO REQUIRE ARC FAULT |
| | PROTECTION. |
| | THIS IS OK, HOWEVER, THIS NOT REQUIRED. |
| | SD'S MAY BE ON ONE OF THE BEDRM |
| | CIRCUITS. |
| | THIS IS ONLY A NOTE, HOWEVER IF NOTE |
| | MENTIONS THIS, THEN THIS IS WHAT WILL BE |
| | REQUIRED. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSET NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |