Plan Review Notes
Plan Review Notes For Permit 05121223
Permit Number 05121223
Review Stop E
Sequence Number 2
Notes
Date Text
2006-03-10 00:00:00********** UNSAT *************
  
 ** PLEASE KNOW, THIS IS THE FIRST TIME
 ELECTRICAL PLANS ARE BEING SUBMITTED FOR
 REVIEW.
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITHY MECHANICAL PLANS. NEED TO
 VERFIY EQUIPMENT SIZES FOR AHU, AND CU,
 HOWEVER MECHANICAL PLANS ARE BLANK?
  
 2)NOTE: PLEASE SEE MIN OCP FOR AHU HEAT
 PER 424.3B, 125%.
 PLEASE ALSO SEE OCP LISTED FOR CU SEEMS
 HIGH, PLEASE VERIFY.
 215.5
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PLANS, AS PLANS INDICATE A MAIN
 DISCONNECT OUTSIDE AND RISER DOES NOT??
 215.5
  
 4)NOTE: PLEASE SEE A DISCONNECT SHALL BE
 REQUIRED FOR WATER HEATER. "PLUG-IN" MAY
 NOT BE USED.
 422.30,31
  
 5)NOTE: PLEASE SEE NO DISCONNECT IS
 BEING SHOWN FOR AHU?
 440.11
  
 6)NOTE: PLEASE SEE NO DISCONNECT IS
 BEING SHOWN FOR CU?
 PLEASE SEE PLANS INDICATEA 220V GFI??
 FOR DISCONNECT?? 440.11
  
 7)NOTE: PLEASE SEE BATH RM RECEPT SHALL
 BE EITHER MOVED IN BETWEEN BOTH LAV'S OR
 ADD AN ADDITIONAL GFI. PLEASE KNOW, YOU
 CAN NOT CROSS OVER A LAV TO PLUG IN AN
 APPLIANCE.
 210.52D.
  
 8)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3, THESE SHALL BE 20A,
 #12,
  
 9)NOTE: PLEASE SEE SOME WALL AREAS WHICH
 SEEM TO INDICATE MISSING RECEPTS PER
 210.52
 PLEASE SEE REDLINED LOCATIONS ON PLANS.
  
 10)NOTE: PLEASE SEE 2002 NEC FOR ARC
 FAULT PROTECTION REQUIREMENTS. PLEASE
 SEE NOTES ARE BEING REFERENCED FROM THE
 1999 NEC. PROTECTION IS REQUIRED FOR ALL
 "OUTLETS", FANS, LTS SD'S, ETC.
  
 11)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIOSN TO HAVE SD'S WIRED TO KIT/BATH
 LTS, THIS IS OK, HOWEVER THEN THOSE
 CIRCUITS WOULD ALSO REQUIRE ARC FAULT
 PROTECTION.
 THIS IS OK, HOWEVER, THIS NOT REQUIRED.
 SD'S MAY BE ON ONE OF THE BEDRM
 CIRCUITS.
 THIS IS ONLY A NOTE, HOWEVER IF NOTE
 MENTIONS THIS, THEN THIS IS WHAT WILL BE
 REQUIRED.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSET NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  