| Plan Review Notes For Permit 05121223 |
| Permit Number |
05121223 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-23 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- GENERAL CONTRACTOR LICENSE CGC008463 | | | IS SUSPENDED. CONTRACTOR NEEDS TO | | | CONTACT DBPR TO RESOLVE LICENSE ISSUES. | | | PERMIT CAN'T BE USED IF CONTRACTOR'S | | | LICENSE IS SUSPENDED. | | | | | | 2- A) SCOPE OF WORK STATES REPLACING | | | BROKEN WINDOWS. PROVIDE FLORIDA OR LOCAL | | | PRODUCT APPROVAL FOR WINDOWS TO BE | | | INSTALLED. | | | | | | B) SPECIFY SIZES OF WINDOWS TO BE | | | REPLACED TO VERIFY COMPLIANCE WITH | | | EGRESS REQUIREMENTS FROM BEDROOMS. SEC. | | | 505.1 OF FBC 2004 EXISTING BUILDINGS. | | | | | | C) IF TOTAL NUMBER OF WINDOWS TO BE | | | REPLACED AMOUNT TO MORE THAN 25% OF | | | GLAZED AREA IN THE HOUSE, THEN STORM | | | SHUTTERS ARE REQUIRED. SEC. 507.3 FBC | | | 2004 EXISTING BUILDINGS. | | | | | | D) PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR STORM SHUTTERS IF THEY ARE | | | REQUIRED. SEE ITEM C) ABOVE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|