| Plan Review Notes For Permit 05121217 |
| Permit Number |
05121217 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2007-07-31 16:04:20 | REV'S STAMPED, | | | REDLINED THE MDP AS THIS IS STILL BEING SHOWN AS GFCI | | | PROTECTED. THE RISER SHOWS GFP WHICH IS CORRECT. | | | 240.13, 230.95 |
|