| Plan Review Notes For Permit 05121217 |
| Permit Number |
05121217 |
|
| Review Stop |
Z |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-06-26 17:40:32 | ***REVISIONS (NEW GENERATOR SPEC & INCREASE BLD | | | SERVICE) FAILED*** | | | | | | 1) SHEET A1.1.1 SHOWS THE GENERATOR AS FUTURE | | | LOCATIONS.SITE PLAN SHALL BE MODIFIED TO SHOW THE | | | LOCATION OF THE GENERATOR THAT IS BEING PROPOSED AS | | | PART OF THIS REVISION.DIMENSIONS SHOWING THE SETBACK | | | OF THE GENERATOR FROM ADJACENT PROPERTY LINES SHALL BE | | | PROVIDED. | | | | | | 2) SCREEN WALL AROUND THE GENERATOR IS NOTED AS BEING | | | UNDER A SEPARATE PERMIT.THIS SCREEN WALL IS REQUIRED | | | AT THE TIME OF INSTALLATION OF THE GENERATOR, SO THIS | | | REVISION SHALL BE MODIFIED TO INCLUDE THE INSTALLATION | | | OF THE SCREEN WALL, OR THE NEW PERMIT SHALL BE | | | SUBMITTED CONCURRENTLY WITH THIS REVISION.UPON | | | SUBMITTAL OF THE WALL, AN ELEVATION SHALL BE PROVIDED. | | | | | | 3) PLEASE CLARIFY WHY SHEETS WERE SUBMITTED (I.E. | | | BUILDING ELEVATIONS, STRUCTURALS, ETC.) WHICH DO NOT | | | RELATE TO THE REVISIONS INDICATED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|