| Plan Review Notes For Permit 05121217 |
| Permit Number |
05121217 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-03-14 12:46:01 | 3/15/07 BOB FOX BROUGHT IN IMPACT FEE PAID RECEIPT AND | | | NOC. | | | | | | TEMPORARY FAILED STATUS WILL BE CHANGED TO PASS WHEN | | | PAID IN FULL RECEIPT FOR IMPACT FEES AND RECORDED NOC | | | IS SUBMITTED. | | | | | | | | | BUILDING PROVISO | | | | | | 1) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM A | | | FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED | | | ROOF CONSULTANT FOR THE ENHANCED FASTENING OF THE JOHNS | | | MANVILLE MODIFIED ROOFING SYSTEM AFTER THE REQUIRED | | | PULL TESTS ON THE LIGHTWEIGHT CONCRETE DECK HAVE BEEN | | | COMPLETED. | | | | | | 2) SUBMIT REVISED SHEETS S1, S7 AND S12 THAT REFLECT | | | THE CHANGE TO THE EAST ELEVATION ON SHEET A3.1.1 IN | | | ORDER TO COMPLY WITH FBC 704.8.1 FOR THE 25 % OF WALL | | | AREA ALLOWED AS OPENINGS. |
|