| Date |
Text |
| 2007-01-11 10:15:04 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | COMMENTS FROM FIRST REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT A105 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE FOR EACH AREA BEING |
| | DRAINED ALONG WITH 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS AS |
| | WELL AS THE AREA OF ANY ROOFS THAT DRAIN |
| | ONTO THE ROOF FROM ABOVE. SECTIONS 1106 |
| | & 1107 AND ALL SUBSECTIONS. - SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| | OVERFLOW SCUPPERS. OVERFLOW SCUPPERS |
| | SHALL BE SIZED PER SECTIONS 1101.7, |
| | 1107.3 AND TABLE 1106.7. SCUPPER SIZE |
| | CAN NOT BE CALCULATED WITHOUT REFERENCE |
| | TO DEFLECTION OF THE ROOF. PLEASE SHOW |
| | ON PLANS. |
| | ****RESPONSE FROM ARCHITECT, PLEASE SEE |
| | RESPONSE FROM ENGINEER. RESPONSE FROM |
| | ENGINEER, SEE ARCHITECTS RESPONSE. |
| | COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT DOING A SPOT CHECK ON AREAS |
| | 1, 5 & 8 THERE ARE INCONSISTANCIES IN THE LINEAR |
| | FOOTAGE FOR THE PARAPET WALLS FROM AREA 1 TO AREA 8. |
| | THE SQUARE FOOTAGE FOR THE VERTICAL WALL CONTRIBUTION |
| | FOR AREA 8 IS INDICATED AS LESS THAN THE AREA FOR AREA |
| | 1 AND THE WALL LINEAR FOOTAGE IS LONGER. NO VERTICAL |
| | WALL CONTRIBUTION FOR THE STAIRWELL IS INDICATED IN |
| | AREA 5 CALCULATIONS. RECHEK ALL SQUARE FOOTAGE AREAS |
| | FOR EACH AREA, EACH VERTICAL WALL/PARAPET, (HIGHER |
| | SECTIONS ON THE EAST, WEST, & SOUTH ELEVATIONS), AND |
| | TOTAL AREAS. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2 AND CROSS CONNECTION MANUAL |
| | SECTION 2.6. |
| | ****RESPONSE NOTED, BUT SHT P3.1 REFERS |
| | TO SHT P4.2 WHICH REFERS TO THE CIVIL |
| | PLANS. CIVIL DOES NOT SHOW THE METER OR |
| | BACKFLOW LOCATION. PLEASE INDICATE THE |
| | LOCATION OF METER & RPBV BACKFLOW |
| | REQUIRED ON THE WATER SERVICE. SECTION |
| | 106.1.1. |
| | ******RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED |
| | ON THE WATER SERVICE TO EACH BUILDING AS INDICATED. |
| | THIS SHALL BE INSTALLED DOWNSTREAM OF THE METER. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | |
| | 3B. SHT P5.1 FITTINGS SHALL BE INSTALLED |
| | TO GUIDE SEWAGE AND WASTE IN THE |
| | DIRECTION OF FLOW. SECTION 706.3. THE |
| | DOUBLE LAV SHOWN ON RISER SHOWS FITTING |
| | AGAINST THE FLOW. PLEASE CORRECT. |
| | ******RESPONSE NOTED, BUT THE LAVS NOW SHOW 1 LAV |
| | TRAPPED AND THEN CONNECTING TO THE TRAP OF THE ADJACENT |
| | LAV. EACH LAV SHALL BE TRAPPED SEPARATELY AND CONNECTED |
| | TO THE STACK SEPARATELY. SECTION 1002.1 |
| | |
| | *************NEW COMMENTS************* |
| | |
| | BETWEEN PLAN REVIEWS, SOME PLAN DEVELOPMENT HAS |
| | OCCURED. THIS IS GENERATING MORE COMMENTS WHICH |
| | FOLLOW. |
| | |
| | 1C. SHT P0.1 A BACKFLOW PREVENTOR IS REQUIRED ON THE |
| | WATER SERVICE. THIS HAS BEEN DELETED FROM THE DETAIL. |
| | PLEASE INDICATE THE REQUIRED B/F IN THE DETAIL WITH THE |
| | METER. SECTION 608.13.2. |
| | |
| | 2C. SHT P2.1 EMERGENCY FLOOR DRAINS INDICATED BELOW THE |
| | RAISED FLOOR ARE INDICATED AS TERMINATING ABOVE THE MOP |
| | SINK. SUBMIT A DETAIL SHOWING PIPE SIZES. INDICATE IF |
| | THERE ARE TRAPS, VENTS ETC. SHOW AN ELEVATION FOR THE |
| | PIPE TERMINATING OVER THE MOP SINK. SUBMIT A SANT. |
| | RISER DIAGRAM FOR THE EMERGENCY FLOOR DRAINS IN |
| | ISOMETRIC FORM. SECTIONS 106.1.1 & 106.3.5.1.3. |
| | |
| | 3C. SUBMIT A DETAIL FOR THE FLOOR DRAINS AT THE RAISED |
| | FLOOR LEVEL. INDICATE HOW THE FLOOR DRAINS WILL CONNECT |
| | TO THE FLOOR AND INDICATE HOW THE FLOOR WILL BE WATER |
| | PROOF AND SLOPED TO THE FLOOR DRAIN. INDICATE IF THE |
| | FLOOR DRAINS WILL HAVE A FLASHING AND INDICATE IF IT |
| | WILL EXTEND THE COMPLETE LENGTH AND WIDTH OF THE ROOM. |
| | |
| | 4C. SUBMIT A DETAIL FOR THE EMERGENCY FLOOR DRAINS ON |
| | THE FIRST FLOOR. INDICATE HOW THEY WILL DRAIN TO THE |
| | MOP SINK ABOVE THE FLOOR SLAB. SECTION 106.1.1. |
| | |
| | 5C. ACCESS IS REQUIRED FOR THE EMERGENCY FLOOR DRAINS. |
| | PLEASE INDICATE HOW THIS WILL BE ACHIEVED. SECTION |
| | 412.2. |
| | |
| | 6C. SHT P2.1 MAXIMUM 10' FROM VENT TO FLOOR DRAINS IN |
| | THE WATER PUMP ROOM. TABLE906.1. |
| | |
| | 7C. ALL FLOORS INDICATE A SANITARY RISER & FUTURE STUB |
| | OUTS ARE SHOWN. PLEASE INDICATE HOW THEY WILL BE VENTED |
| | AS NO VENT STUB OUTS ARE INDICATED ON THE FLOOR PLANS. |
| | THE SANITARY RISER DIAGRAM DOES NOT INDICATE STUB OUTS |
| | ON THE SANT. OR VENT RISERS. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 8C. SHT P6.1 DOMESTIC WATER RISER. SHUT OFF VALVES ARE |
| | REQUIRED ON THE WATER SUPPLY TO EACH HOSE BIBB. SECTION |
| | 606.2(2). |
| | |
| | 9C. SHT P5.1 THE CONDENSATE RISER ISOMETRIC DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE RISER |
| | AND FLOOR PLAN LAYOUT. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561)805-6731 |
| | E-MAIL [email protected] |