| 2007-01-05 09:42:33 | DENIED BY BUILDING |
| | |
| | 2004 FLORIDA BUILDING CODE |
| | 4 STORY OFFICE BUILDING (SHELL) |
| | TYPE II-B (SPRINKLERED) |
| | BUSINESS OCCUPANCY |
| | FLOOD ZONE A9 BFE 13' (+6" CITY REQ) |
| | REQUIRED SOIL BEARING CAPACITY 2500 AND |
| | 8000 PSF |
| | |
| | 1) STRUCTURE IS LOCATED IN AN A9 FLOOD |
| | ZONE. AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 4) PRIOR TO PERMIT ISSUANCE, PLEASE ARRANGE WITH HAROLD |
| | PISKURA (INSPECTION SERVICES MANAGER - TEL : |
| | 561-805-6711), A MEETING INVOLVING THE OWNER, THRESHOLD |
| | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. |
| | |
| | 5) ON SHEET A2.0.1 UNDER CODE ANALYSIS/ APPLICABLE |
| | CODES, THE HIGH VELOCITY HURRICANE ZONES IS INCORRECTLY |
| | SPECIFIED. THIS PROJECT IS NOT LOCATED WITHIN THE HIGH |
| | VELOCITY HURRICANE ZONE. |
| | |
| | 6) ON SHEET A1.1.1, THE DETAIL TAGS SPECIFY THE WRONG |
| | PAGES. IT SHOULD BE PAGE A1.2.4. |
| | |
| | 7) THE MAXIMUM DESIGN PRESSURE FROM THE MODIFIED |
| | ROOFING PRODUCT APPROVAL IS TOO LOW BASED ON THE ROOF |
| | PRESSURES ON PAGE S12 OF PLANS. THE PRODUCT APPROVAL |
| | ALLOWS FOR INCREASED PRESSURES THROUGH ENHANCED |
| | FASTENING (SEE LIMITATION #7 ON NOA) WITH SIGNED AND |
| | SEALED RAS 117 CALCULATIONS.PLEASE SUBMIT THE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS. |
| | |
| | 8)THE FIRE WINDOWS IN WATER PUMP ROOM ARE NOT CODE |
| | COMPLIANT. FBC 715.4 REQUIRES FIRE-PROTECTION-RATED |
| | GLAZING IN INTERIOR ONE HOUR RATED WALLS TO HAVE A 45 |
| | MINUTE RATING. THE FIRE GLASS 20 SPECIFIED IN DETAIL 1 |
| | ON A8.1.1 HAS A TWENTY MINUTE FIRE RATING. FBC |
| | 715.4.7.2LIMITS THE TOTAL AREA OF INTERIOR FIRE |
| | WINDOW ASSEMBLIES TO NOT EXCEED 25 PERCENT OF THE AREA |
| | OF A COMMON WALL WITHIN ANY ROOM. THE ALLOWABLE AREA |
| | FOR FIRE WINDOWS IS EXCEEDED. |
| | |
| | 9) THE STATE PRODUCT APPROVAL COVERSHEET FOR THE |
| | WINDSOR REPUBLIC DOOR DOES NOT CORRESPOND THE THE |
| | ATTACHED NOA FOR THE SERIES DM 418 STEEL DOOR. PLEASE |
| | CORRECT. |
| | |
| | 10) THE OTHER PRODUCT APPROVALS SUBMITTED DO NOT HAVE |
| | THE STATE PRODUCT APPROVAL COVERSHEETS WITH THEFL# |
| | ATTACHED. NOTE: FBC* 109.3.6 REQUIRES THE PRODUCT |
| | APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 11)FBC 1406.2.2REQUIRES ARCHITECTURAL TRIM THAT |
| | EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE |
| | SHALL BE CONSTRUCTED OF APPROVED NONCOMBUSTIBLE |
| | MATERIALS AND SHALL BE SECURED TO THE WALL WITH METAL |
| | OR OTHER APPROVED NONCOMBUSTIBLE BRACKETS. FOAM BANDING |
| | AT PARAPET AND MEDALLIONS AS SHOWN ON A3.1.1 ARE |
| | NON-COMPLIANT. |
| | |
| | 12)A SEPARATE PERMIT WILL BE REQUIRED FOR THE FENCE |
| | WALL AT THE GENERATOR AREA AS SHOWN ON SHEET S-13. THE |
| | HEIGHT OF THE WALL IS SPECIFIED AS 15', HOWEVER THE |
| | SITE PLANS SPECIFY 6'. PLEASE CORRECT. THE TAG FOR THE |
| | ELEVATION SHOULD REFERENCE 7 ON A1.2.3. |
| | |
| | 13)ON THE COVERED WALKWAY PLAN ON S13, SPECIFY THE |
| | COLUMN TYPE AND REINFORCING FOR THE L ANGLE COLUMN |
| | BETWEEN SPANDREL PANELS 73 AND 74.ALSO SPECIFY THE |
| | FOUNDATION TYPE AND REINFORCEMENT FOR THE LARGE L ANGLE |
| | FOOTING AT THIS LOCATION. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE ROOF OF THE |
| | COVERED WALKWAY. |
| | |
| | 15) THE SECTION OF EXTERIOR WALL ON THE EAST ELEVATION |
| | THAT IS LESS THAN 10 FEET FROM THE CONDO PROPERTY LINE |
| | (FIRE SEPARATION DISTANCE) IS REQUIRED BY FBC TABLE 602 |
| | TO HAVE A ONE HOUR FIRE RATING FOR TYPE II-B |
| | CONSTRUCTION. IN ADDITION, FBC TABLE 704.8 LIMITS THE |
| | ALLOWABLE AREA OF UNPROTECTED OPENINGS TO 10% OF THE |
| | WALL AREA. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |