2008-01-24 11:35:52DENIED BY BUILDING
  
 THE LETTER FROM FRANK L. BENNARDO, THE WINDOW SHOP
 DRAWING ENGINEER, TO ALLOW LARGER SHIM SPACE THAN THE
 PRODUCT APPROVALS FOR THE MGI-50 AND YHS50 STOREFRONT
 FRAMING SYSTEMS IS DENIED. THE ENGINEER IS REQUIRED TO
 PROVIDE SIGNED AND SEALED CALCULATIONS AND RATIONAL
 ANALYSIS IN ORDER TO DEVIATE FROM THE REQUIREMENTS OF
 THE PRODUCT APPROVAL WHICH ARE BASED ON TESTING OF THE
 PRODUCT. SEE FBC 1714.5.4.2 AND 1714.7.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]