| Notes |
| Date |
Text |
| 2008-01-24 11:35:52 | DENIED BY BUILDING | | | | | | THE LETTER FROM FRANK L. BENNARDO, THE WINDOW SHOP | | | DRAWING ENGINEER, TO ALLOW LARGER SHIM SPACE THAN THE | | | PRODUCT APPROVALS FOR THE MGI-50 AND YHS50 STOREFRONT | | | FRAMING SYSTEMS IS DENIED. THE ENGINEER IS REQUIRED TO | | | PROVIDE SIGNED AND SEALED CALCULATIONS AND RATIONAL | | | ANALYSIS IN ORDER TO DEVIATE FROM THE REQUIREMENTS OF | | | THE PRODUCT APPROVAL WHICH ARE BASED ON TESTING OF THE | | | PRODUCT. SEE FBC 1714.5.4.2 AND 1714.7. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|