| Date |
Text |
| 2006-08-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | COMMENTS FROM FIRST REVIEW: |
| | |
| | 1. SHT A003 PLUMBING FIXTURE CALCULATION |
| | INDICATE 3 DRINKING FOUNTAINS ARE |
| | REQUIRED ON EACH FLOOR. CALCULATIONS |
| | ALSO INDICATE THAT 4 DRINKING FOUNTAINS |
| | ARE PROVIDED ON EACH FLOOR. A HIGH/LOW |
| | DRINKING FOUNTAIN WITH ONE WASTE AND ONE |
| | WATER SUPPLY IS CONSIDERED ONE FIXTURE. |
| | ONLY 2 DRINKING FOUNTAINS ARE PROVIDED |
| | ON EACH FLOOR, AND ONE MORE DRINKING |
| | FOUNTAIN IS REQUIRED ON EACH FLOOR. |
| | TABLE 403.1. |
| | ****RESPONSE FROM ARCHITECT, PLEASE SEE |
| | RESPONSE FROM ENGINEER. RESPONSE FROM |
| | ENGINEER, SEE ARCHITECTS RESPONSE. |
| | COMMENT NOT ADDRESSED. |
| | |
| | 2. SHT A105 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE FOR EACH AREA BEING |
| | DRAINED ALONG WITH 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS AS |
| | WELL AS THE AREA OF ANY ROOFS THAT DRAIN |
| | ONTO THE ROOF FROM ABOVE. SECTIONS 1106 |
| | & 1107 AND ALL SUBSECTIONS. - SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| | OVERFLOW SCUPPERS. OVERFLOW SCUPPERS |
| | SHALL BE SIZED PER SECTIONS 1101.7, |
| | 1107.3 AND TABLE 1106.7. SCUPPER SIZE |
| | CAN NOT BE CALCULATED WITHOUT REFERENCE |
| | TO DEFLECTION OF THE ROOF. PLEASE SHOW |
| | ON PLANS. |
| | ****RESPONSE FROM ARCHITECT, PLEASE SEE |
| | RESPONSE FROM ENGINEER. RESPONSE FROM |
| | ENGINEER, SEE ARCHITECTS RESPONSE. |
| | COMMENT NOT ADDRESSED. |
| | |
| | 3. SHT A402 SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL ACCESSIBLE FIXTURES INCLUDING |
| | DRINKING FOUNTANS & UNINALS. SECTIONS |
| | 11-4.15.5(1) AND 11-4.18.3. |
| | ****RESPONSE NOTED, BUT CLEAR FLOOR |
| | SPACE FOR THE DRINKING FOUNTAINS SHALL |
| | BE FORWARD APPROACH. SECTION |
| | 11-4.15.5(1). |
| | |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT P5.1 SANITARY RISER RISER |
| | ISOMETRIC. SHOW ALL PIPE SIZES AND |
| | INDICATE DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SOME PIPE SIZES |
| | ARE STILL MISSING, AND DFU'S NEED TO BE RECHECKED. |
| | |
| | 7. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2 AND CROSS CONNECTION MANUAL |
| | SECTION 2.6. |
| | ****RESPONSE NOTED, BUT SHT P3.1 REFERS |
| | TO SHT P4.2 WHICH REFERS TO THE CIVIL |
| | PLANS. CIVIL DOES NOT SHOW THE METER OR |
| | BACKFLOW LOCATION. PLEASE INDICATE THE |
| | LOCATION OF METER & RPBV BACKFLOW |
| | REQUIRED ON THE WATER SERVICE. SECTION |
| | 106.1.1. |
| | |
| | 8. OK |
| | 9. OK |
| | |
| | 10. SUBMIT THE MANUF. SPECIFICATION |
| | SHEET FOR THE PUMPS. PUMPS SHALL BE |
| | LISTED. INDICATE MODEL NUMBER FOR EACH |
| | PUMP. SECTION 303.4. |
| | ****RESPONSE NOTED, BUT LISTING FOR |
| | PUMPS ARE NOT SHOWN ON SHT P8.2. |
| | |
| | 11. SHT P7.1 CISTERN WATER RISER. MORE |
| | INFORMATION IS REQUIRED. INDICATE |
| | BUILDING SHOWN ON THE RISERS. SHOW ALL |
| | PIPE SIZES, AND SHOW THE LOCATIONS FOR |
| | THE REQUIRED BACKFLOWS WHERE THE POTABLE |
| | WATER TIES INTO THE NON-POTABLE WATER. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE BUILDING |
| | INDICATION IS NOT SHOWN, AND THE |
| | REQUIRED BACKFLOW IS NOT SHOWN. |
| | |
| | 12. OK |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHT 0000 (BOTH), INDEX OF DRAWINGS |
| | DOES NOT REFLECT SHEETS SUBMITTED. SOME |
| | SHEETS HAVE NOT BEEN SUBMITTED, SOME |
| | SHEETS SUBMITTED, BUT ARE NOT INDICATED |
| | ON THE INDEX, AND SOME SHEETS ARE |
| | MISNUMBERED. PLEASE CORRELATE INDEX AND |
| | SHEETS FOR PLANS. SECTION 106.1.1. |
| | |
| | 2B. SHT P0.1 PLUMBING SHEET INDEX SHOWS |
| | SHT P1.1. THIS SHEET HAS NOT BEEN |
| | SUBMITTED. CORRELATE INDEX AND SHEETS. |
| | SECTION 106.1.1. |
| | |
| | 3B. SHT P5.1 FITTINGS SHALL BE INSTALLED |
| | TO GUIDE SEWAGE AND WASTE IN THE |
| | DIRECTION OF FLOW. SECTION 706.3. THE |
| | DOUBLE LAV SHOWN ON RISER SHOWS FITTING |
| | AGAINST THE FLOW. PLEASE CORRECT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561)805-6731 |
| | E-MAIL [email protected] |