| Date |
Text |
| 2006-07-12 00:00:00 | 1. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 2. A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 3. SUITABLE ROADS SHALL BE PROVIDED |
| | DURING CONSTRUCTION FOR FIRE AND |
| | PARAMEDICAL ACCESS. |
| | |
| | 4. ALL HANDRAILS AND GUARDRAILS SHALL |
| | COMPLY WITH ALL PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS OF THE FLORIDA FIRE |
| | PREVENTION CODE AND THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 5. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| | "IN THE EVENT OF FIRE, DO NOT USE |
| | ELEVATORS". |
| | |
| | 6. TACTILE SIGNAGE REQUIRED AT EXIT |
| | DOORS. |
| | |
| | 7. ALL TENANT SPACES SHALL BE FIRE |
| | SPRINKLER PROTECTED WHEN REQUESTING A |
| | FINAL C OF O EVEN IF THE TENANT |
| | IMPROVEMENTS IN THESE AREAS HAVE NOT |
| | STARTED YET. |
| | |
| | 8. FUTURE TENANT SPACES WILL BE REQUIRED |
| | WHEN FITTED UP TO BE EQUIPPED WITH FIRE |
| | ALARM NOTIFICATION APPLIANCES. |
| | |
| | 9. NOTE 19 ON PAGE FOA.01 IS INCORRECT. |
| | DUCT SMOKE DETECTORS SHALL CAUSE AN |
| | ALARM NOT A SUPERVISORY SIGNAL. |
| | |
| | 10. TAMPER SWITCHES, CHAINS AND LOCK |
| | WILL BE REQUIRED ON THE FIRE LINE |
| | BACKFLOW DEVICE. |
| | |
| | 11. ALL FIRE DAMPERS SHALL BE TESTED |
| | AFTER INSTALLATION TO ENSURE PROPER |
| | OPERATION. |
| | |
| | 12. BUILDING ADDRESS REQUIRED ON PROPER |
| | ELEVATION. THE ADDRESS SHALL BE A |
| | MINIMUM OF AT LEAST 6" HIGH AND 1" IN |
| | WIDTH. |
| | |
| | 13. ALL RATED DOORS MUST BE EQUIPPED |
| | WITH SELF-CLOSING DEVICES WHICH CAUSE |
| | THE DOORS TO POSITIVELY LATCH WHEN |
| | CLOSED. |
| | |
| | APPROVED PROVISO: |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |