| Date |
Text |
| 2006-06-26 00:00:00 | REVIEW COMMENCED |
| | ********** UNSAT 2ND REVIEW *********** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED, |
| | HOWEVER MOST COMMENTS ARE NEW DUE TO |
| | MANY CHANGES IN DESIGN AND PLANS. |
| | |
| | ** PLEASE SEE THE FIRST SET OF COMMENTS |
| | BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW WITH THIS REVIEW RESPONSE. |
| | |
| | *********************************** |
| | |
| | ** PLEASE KNOW, PLANS AND SUBMITTIALS |
| | ARE NOT COMPLETE AT THIS TIME. |
| | |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK, HOWEVER SEE NEW COMMENTS. |
| | |
| | 3)NOTE: NO, PLEASE SEE TITLE BLOCKS |
| | SHALL CLEARLY INDICATE THE ADDRESS FOR |
| | THE PROJECT. PLEASE SEE THE ADDRESS HAS |
| | BEEN CONFIRMED TO 1641 WORTHINGTON RD. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE ADDRESS REVIEW. |
| | PLEASE KNOW, IF PROPERTY CHANGE LEGALLY |
| | TO SEPARATE PROPERTIES/ PCN. ELECTRICAL |
| | DESIGN MAY BE AFFECTED. PLEASE ALSO |
| | KNOW, LEGAL EASEMENTS MAY BE REQUIED. |
| | |
| | 4)NOTE: OK, HOWEVER SEE NEW COMMENTS AS |
| | A COMPLETE NEW RISER IS NOW SHOWN. |
| | |
| | |
| | 5)NOTE: OK, SEE NEW COMMENTS. |
| | |
| | 6)NOTE:NO, CALCULATIONS FOR LT POLES |
| | WERE NOT SUBMITTED. AS ONLY TWO POLES |
| | ARE BEING MOVED, AND IT IS BELEIVE THESE |
| | POLES WERE INSTALLED UNDER THE CURRENT |
| | 140MPH. |
| | |
| | ** PREVIOUS REVIEW ** |
| | PLEASE PROVIDE WIND LOAD |
| | CALCUALTIONS FOR BLDG REVIEW FOR ANY |
| | SITE LIGHTING POLES BEING RELOCATED OR |
| | NEW. ALL MUST MEET 2004 FBC 140 MPH |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE:NO, THIS IS UNCLEAR AS A NOTE |
| | IS PROVIDED ON PANEL SCHEDULES SHOWING |
| | AN "*" , HOWEVER THIS "*" COULD NOT BE |
| | LOCATED NEXT TO ANY OF THE BRANCH |
| | CIRCUITS, FEEDERS OR MAIN BUILDING |
| | SERVICE LOAD CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125% 215.3,230.42 ETC |
| | |
| | 10)NOTE: OK. ALSO UNDER A SEPARATE |
| | PERMIT |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK, HOWEVER PLEASE SEE NEW |
| | NOTES. |
| | |
| | 14)NOTE: OK,SEE ALSO ADDED MCB'S ON ALL |
| | FEED THRU PANELS. THIS IS ONLY NOTED AND |
| | NO CODE CORRECTION EXISTS. |
| | |
| | **PREVIOUS REVIEW NOTE** |
| | PLEASE INDICATE ALL PANELS WITH |
| | FEED-THRU LUGS FROM THE SECONDARY SIDE |
| | OF L1A, L2A, L3A ETC |
| | 215.5 |
| | |
| | 15)NOTE:OK, SEE NOTE #9. |
| | |
| | 16)NOTE: OK, HOWEVER PLEASE CLARIFY VD |
| | FOR FEEDER FROM GEN TO GDP. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 CHAPTER 13, |
| | 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP |
| | INFORMATION NEEDED. |
| | |
| | 17)NOTE: YES/NO, PLEASE SEE REDLINED |
| | PLANS FOR JANS CLOSET FLRS 2-4. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE LIGHTING |
| | REQUIREMENTS UNDER 13-415 FOR AREAS OF |
| | CONTROL AND TANDEM WIRING. |
| | PLEASE SPECIFY THIS INFORMATION ON |
| | PLANS. |
| | |
| | 18)NOTE:OK. |
| | |
| | 19)NOTE: OK. |
| | |
| | |
| | *** NEW NOTES *** |
| | |
| | 20) NOTE: PLEASE SEE EACH FLR COMMON |
| | AREAS/ HALLWAYS ARE NOW BEING CONTROLLED |
| | BY A LIGHTING CONTACTOR FOR ALL EM AND |
| | NORMAL LTS. PLEASE SEE AS THESE ARE |
| | BEING FED DIRECTLY FROM THE CONTACTOR?? |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, WHICH |
| | LIMITS EACH FLR FOR CONTROL. |
| | PLEASE ALSO VERIFY THAT THESE CORRIDORS |
| | LTS ARE BEING CONTROLLED FOR ALL LTS. |
| | IF THE EM FIXTURES ARE GOING TO BE FED |
| | FROM THE NORMAL/NON-SWITCHED SIDE OF THE |
| | SAME CIRCUIT, PLEASE SHOW THIS WAY. |
| | 215.5 |
| | |
| | 21) NOTE: PLEASE CLARIFY STAIR TOWERS AS |
| | ALL LTS ARE BEING SHOWN WITH AN OCC |
| | SENSOR, WHICH INDICATES THAT LIGHTING |
| | WILL NOT BE ON AT ALL. PLEASE CLARIFY IF |
| | ONE OCC SEN WILL ALSO ACTIVATTE ALL |
| | OTHER LT FIXTURES IN STAIR TOWERS. |
| | PLEASE KNOW, AS THE FAILURE OF ONE OCC |
| | SEN COULD POSSIBLY LEAVE A STAIR LEVEL |
| | IN TOTAL DARKNESS UNTIL OCCUPANT |
| | TRAVERSES TO THE NEXT LOWER LEVEL. |
| | THIS SEEMS TO PROMOTE A LIFE SAFETY |
| | ISSUE. PLEASE KNOW, THIS IS SOMETHING |
| | WHICH SHALL BE GONE OVER WITH FIRE |
| | MARSHAL AND BUILDING OFFICAL. |
| | PLEASE SEE EXCEPTIONS TO 13-415 WHICH |
| | STATES "LIGHTING THAT IS SPECIFICALLY |
| | DESIGNATED AS REQUIRED BY HEALTH OR LIFE |
| | SAFETY STATUE,ORDINANCE, OR REGULATION. |
| | ** PLEASE CONTACT THIS OFFICE TO GO OVER |
| | POSSIBLE SCENERIOS, AS THIS OFFICE HAS |
| | SEEN BUILDINGS WITH STAIR TOWERS WHICH |
| | ARE ONLY "ON" WHEN ACTIVATED BY |
| | INGRESS/EGRESS BY AN OCCUPANT. |
| | |
| | 22) NOTE: PLEASE PROVIDE PHOTO-METRICS |
| | FOR STAIRS AND EGRESS PATHS. PLEASE SEE |
| | THESE WERE SUBMITTED FOR A "TYPICAL" FOR |
| | STAIRS, HOWVER IS THIS UDNER NORMAL OR |
| | EM?? |
| | NFPA-101 7.8.1.3,7.9.2.2 |
| | ** PLEASE ALSO SEE THIS TYPICAL DETAIL |
| | INDICATES A FIXTURE TYPE "F1" WHICH DOES |
| | NOT CORRELATE WITH PLANS. |
| | |
| | 23) NOTE: PLEASE SEE AREA OUTSIDE FIRST |
| | FLR ELEVATOR LOBBY AS IT APPEARS SOME |
| | LTS ARE MISSING ? "J-BOX"? |
| | PLEASE ALSO CLARIFY THE FIXTURE "C" AND |
| | "C1" AS BOTH ARE SHOWN ON PLANS WITH THE |
| | SAME SYMBOL.? |
| | 106.1.2 |
| | |
| | 24) NOTE: PLEASE SEE FIXTURE "B" IS |
| | SHOWN AS BEING WALL AND CEILING MOUNTED |
| | ON PLANS, HOWEVER THIS FIXTURE IS NOTED |
| | ON SCHEDULE AS BEING CEILING |
| | MOUNTED/HUNG ONLY?? |
| | 106.1.2 |
| | |
| | 25) NOTE: PLEASE PROVIDE OCP FOR BRKR AT |
| | GEN FOR FEED TO THE GMDP. |
| | 215.5 |
| | |
| | 26) NOTE: PLEASE SEE RISER NOW SHOWS A |
| | GMDP AND ATS-1 HOWEVER THESE ARE NOT |
| | LOCATED ON PLANS. PLEASE SEE THESE SEEM |
| | TO BE MISSING FROM THE MAIN ELECTRICAL |
| | RM WHERE THEY ARE REQUIRED. |
| | 225.34, 230.72 |
| | |
| | 27) NOTE:PLEASE SEE "GMDP" SHALL |
| | INDICATE A SIGN AS EM MAIN. |
| | PLEASE SEE 702.7 FOR SIGNALS REQUIRED. |
| | 702.8,701.8,701.9, 230.2E |
| | |
| | 28) NOTE: PLEASE PROVIDE A GROUNDING |
| | ELECTRODE RISER FOR ALL TRANSFORMERS AND |
| | ATTACHMENT AT MAIN GROUNDIGN ELECTRODE |
| | SYSTEM. |
| | 250.50,250.30, 250.58 |
| | |
| | 29) NOTE: PLEASE SEE RISER DIAGRAM AS A |
| | "GMDP-2" IS LOCATED IN AN AREA NOT |
| | DESIGNATED TO ANYTHING? PLEASE SEE |
| | REDLINED PLANS. |
| | 215.5, |
| | |
| | 30) NOTE: NOTE REMOVED. |
| | |
| | ** PLEASE SEE THE FOLLOWING NOTE IS NOT |
| | FOR KAMM CONSULTING ENG'S. |
| | |
| | 31) NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION IN TITLE BLOCK FOR LANDSCAPE |
| | ARCHITECT AND FIRM. |
| | PLEASE SEE 61G1-16.004, FS 481.219 |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | |
| | |
| | ** IMPORTANT** |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ON.Y INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONLY SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | DPALMER2WPB.ORG |
| | |
| | |
| 2006-06-25 00:00:00 | PLANS IN ELEC FOR REVIEW. |