Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-26 00:00:00REVIEW COMMENCED
 ********** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED,
 HOWEVER MOST COMMENTS ARE NEW DUE TO
 MANY CHANGES IN DESIGN AND PLANS.
  
 ** PLEASE SEE THE FIRST SET OF COMMENTS
 BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW WITH THIS REVIEW RESPONSE.
  
 ***********************************
  
 ** PLEASE KNOW, PLANS AND SUBMITTIALS
 ARE NOT COMPLETE AT THIS TIME.
  
  
 1)NOTE: OK.
  
 2)NOTE: OK, HOWEVER SEE NEW COMMENTS.
  
 3)NOTE: NO, PLEASE SEE TITLE BLOCKS
 SHALL CLEARLY INDICATE THE ADDRESS FOR
 THE PROJECT. PLEASE SEE THE ADDRESS HAS
 BEEN CONFIRMED TO 1641 WORTHINGTON RD.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ADDRESS REVIEW.
 PLEASE KNOW, IF PROPERTY CHANGE LEGALLY
 TO SEPARATE PROPERTIES/ PCN. ELECTRICAL
 DESIGN MAY BE AFFECTED. PLEASE ALSO
 KNOW, LEGAL EASEMENTS MAY BE REQUIED.
  
 4)NOTE: OK, HOWEVER SEE NEW COMMENTS AS
 A COMPLETE NEW RISER IS NOW SHOWN.
  
  
 5)NOTE: OK, SEE NEW COMMENTS.
  
 6)NOTE:NO, CALCULATIONS FOR LT POLES
 WERE NOT SUBMITTED. AS ONLY TWO POLES
 ARE BEING MOVED, AND IT IS BELEIVE THESE
 POLES WERE INSTALLED UNDER THE CURRENT
 140MPH.
  
 ** PREVIOUS REVIEW **
 PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW FOR ANY
 SITE LIGHTING POLES BEING RELOCATED OR
 NEW. ALL MUST MEET 2004 FBC 140 MPH
  
 7)NOTE: OK.
  
 8)NOTE: OK.
  
 9)NOTE:NO, THIS IS UNCLEAR AS A NOTE
 IS PROVIDED ON PANEL SCHEDULES SHOWING
 AN "*" , HOWEVER THIS "*" COULD NOT BE
 LOCATED NEXT TO ANY OF THE BRANCH
 CIRCUITS, FEEDERS OR MAIN BUILDING
 SERVICE LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% 215.3,230.42 ETC
  
 10)NOTE: OK. ALSO UNDER A SEPARATE
 PERMIT
  
 11)NOTE: OK.
  
 12)NOTE: OK, HOWEVER PLEASE SEE NEW
 NOTES.
  
 14)NOTE: OK,SEE ALSO ADDED MCB'S ON ALL
 FEED THRU PANELS. THIS IS ONLY NOTED AND
 NO CODE CORRECTION EXISTS.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE INDICATE ALL PANELS WITH
 FEED-THRU LUGS FROM THE SECONDARY SIDE
 OF L1A, L2A, L3A ETC
 215.5
  
 15)NOTE:OK, SEE NOTE #9.
  
 16)NOTE: OK, HOWEVER PLEASE CLARIFY VD
 FOR FEEDER FROM GEN TO GDP.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 13,
 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP
 INFORMATION NEEDED.
  
 17)NOTE: YES/NO, PLEASE SEE REDLINED
 PLANS FOR JANS CLOSET FLRS 2-4.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE LIGHTING
 REQUIREMENTS UNDER 13-415 FOR AREAS OF
 CONTROL AND TANDEM WIRING.
 PLEASE SPECIFY THIS INFORMATION ON
 PLANS.
  
 18)NOTE:OK.
  
 19)NOTE: OK.
  
  
 *** NEW NOTES ***
  
 20) NOTE: PLEASE SEE EACH FLR COMMON
 AREAS/ HALLWAYS ARE NOW BEING CONTROLLED
 BY A LIGHTING CONTACTOR FOR ALL EM AND
 NORMAL LTS. PLEASE SEE AS THESE ARE
 BEING FED DIRECTLY FROM THE CONTACTOR??
 PLEASE SEE FBC 13-415.1.ABC.1.1, WHICH
 LIMITS EACH FLR FOR CONTROL.
 PLEASE ALSO VERIFY THAT THESE CORRIDORS
 LTS ARE BEING CONTROLLED FOR ALL LTS.
 IF THE EM FIXTURES ARE GOING TO BE FED
 FROM THE NORMAL/NON-SWITCHED SIDE OF THE
 SAME CIRCUIT, PLEASE SHOW THIS WAY.
 215.5
  
 21) NOTE: PLEASE CLARIFY STAIR TOWERS AS
 ALL LTS ARE BEING SHOWN WITH AN OCC
 SENSOR, WHICH INDICATES THAT LIGHTING
 WILL NOT BE ON AT ALL. PLEASE CLARIFY IF
 ONE OCC SEN WILL ALSO ACTIVATTE ALL
 OTHER LT FIXTURES IN STAIR TOWERS.
 PLEASE KNOW, AS THE FAILURE OF ONE OCC
 SEN COULD POSSIBLY LEAVE A STAIR LEVEL
 IN TOTAL DARKNESS UNTIL OCCUPANT
 TRAVERSES TO THE NEXT LOWER LEVEL.
 THIS SEEMS TO PROMOTE A LIFE SAFETY
 ISSUE. PLEASE KNOW, THIS IS SOMETHING
 WHICH SHALL BE GONE OVER WITH FIRE
 MARSHAL AND BUILDING OFFICAL.
 PLEASE SEE EXCEPTIONS TO 13-415 WHICH
 STATES "LIGHTING THAT IS SPECIFICALLY
 DESIGNATED AS REQUIRED BY HEALTH OR LIFE
 SAFETY STATUE,ORDINANCE, OR REGULATION.
 ** PLEASE CONTACT THIS OFFICE TO GO OVER
 POSSIBLE SCENERIOS, AS THIS OFFICE HAS
 SEEN BUILDINGS WITH STAIR TOWERS WHICH
 ARE ONLY "ON" WHEN ACTIVATED BY
 INGRESS/EGRESS BY AN OCCUPANT.
  
 22) NOTE: PLEASE PROVIDE PHOTO-METRICS
 FOR STAIRS AND EGRESS PATHS. PLEASE SEE
 THESE WERE SUBMITTED FOR A "TYPICAL" FOR
 STAIRS, HOWVER IS THIS UDNER NORMAL OR
 EM??
 NFPA-101 7.8.1.3,7.9.2.2
 ** PLEASE ALSO SEE THIS TYPICAL DETAIL
 INDICATES A FIXTURE TYPE "F1" WHICH DOES
 NOT CORRELATE WITH PLANS.
  
 23) NOTE: PLEASE SEE AREA OUTSIDE FIRST
 FLR ELEVATOR LOBBY AS IT APPEARS SOME
 LTS ARE MISSING ? "J-BOX"?
 PLEASE ALSO CLARIFY THE FIXTURE "C" AND
 "C1" AS BOTH ARE SHOWN ON PLANS WITH THE
 SAME SYMBOL.?
 106.1.2
  
 24) NOTE: PLEASE SEE FIXTURE "B" IS
 SHOWN AS BEING WALL AND CEILING MOUNTED
 ON PLANS, HOWEVER THIS FIXTURE IS NOTED
 ON SCHEDULE AS BEING CEILING
 MOUNTED/HUNG ONLY??
 106.1.2
  
 25) NOTE: PLEASE PROVIDE OCP FOR BRKR AT
 GEN FOR FEED TO THE GMDP.
 215.5
  
 26) NOTE: PLEASE SEE RISER NOW SHOWS A
 GMDP AND ATS-1 HOWEVER THESE ARE NOT
 LOCATED ON PLANS. PLEASE SEE THESE SEEM
 TO BE MISSING FROM THE MAIN ELECTRICAL
 RM WHERE THEY ARE REQUIRED.
 225.34, 230.72
  
 27) NOTE:PLEASE SEE "GMDP" SHALL
 INDICATE A SIGN AS EM MAIN.
 PLEASE SEE 702.7 FOR SIGNALS REQUIRED.
 702.8,701.8,701.9, 230.2E
  
 28) NOTE: PLEASE PROVIDE A GROUNDING
 ELECTRODE RISER FOR ALL TRANSFORMERS AND
 ATTACHMENT AT MAIN GROUNDIGN ELECTRODE
 SYSTEM.
 250.50,250.30, 250.58
  
 29) NOTE: PLEASE SEE RISER DIAGRAM AS A
 "GMDP-2" IS LOCATED IN AN AREA NOT
 DESIGNATED TO ANYTHING? PLEASE SEE
 REDLINED PLANS.
 215.5,
  
 30) NOTE: NOTE REMOVED.
  
 ** PLEASE SEE THE FOLLOWING NOTE IS NOT
 FOR KAMM CONSULTING ENG'S.
  
 31) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION IN TITLE BLOCK FOR LANDSCAPE
 ARCHITECT AND FIRM.
 PLEASE SEE 61G1-16.004, FS 481.219
 MISSING CERTIFICATE OF AUTHORIZATION #.
  
  
 ** IMPORTANT**
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ON.Y INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONLY SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER2WPB.ORG
  
  