| Date |
Text |
| 2006-08-11 00:00:00 | DENIED BY BUILDING |
| | |
| | 2004 FLORIDA BUILDING CODE |
| | 4 STORY OFFICE BUILDING (SHELL) |
| | TYPE II-B (SPRINKLERED) |
| | BUSINESS OCCUPANCY |
| | FLOOD ZONE A9 BFE 13' (+6" CITY REQ) |
| | REQUIRED SOIL BEARING CAPACITY 2500 AND |
| | 8000 PSF |
| | |
| | 1) STRUCTURE IS LOCATED IN AN A9 FLOOD |
| | ZONE. AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 2) SUBMIT A SIGNED AND SEALED SURVEY OR |
| | SITE PLAN INDICATING THE LOCATION OF THE |
| | STRUCTURE AND THE DISTANCE TO THE |
| | PROPERTY LINES (CONDO BOUNDARY LINES). |
| | THIS IS REQUIRED TO DETERMINE THE FIRE |
| | SEPARATION DISTANCE, AS WELL AS, |
| | EXTERIOR WALL FIRE RATINGS AND OPENING RESTRICTIONS. |
| | |
| | 3) FBC* 1804.2.2 AREA OF QUESTIONABLE |
| | SOIL. SUBMIT A GEOTECHNICAL REPORT TO |
| | VERIFY THE SAFE BEARING CAPACITY OF THE |
| | SOIL. |
| | |
| | 4) FBC 13-400.2.A.2 SHELL BUILDINGS. |
| | SHELL BUILDINGS SHALL COMPLY WITH THIS |
| | CODE BY METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED |
| | DESIGN PARAMETERS ARE |
| | KNOWN, A METHOD A CALCULATION MAY BE |
| | RESUBMITTED. |
| | 13-400.3.ABC.2 CODE COMPLIANCE |
| | CERTIFICATION. |
| | THE BUILDING?S OWNER, THE OWNER?S |
| | ARCHITECT, OR OTHER AUTHORIZED AGENT |
| | LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY TO THE BUILDING OFFICIAL THAT |
| | THE BUILDING IS IN COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 13 OF THIS CODE |
| | PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | IF, DURING THE BUILDING?S CONSTRUCTION |
| | OR RENOVATION, ALTERATIONS ARE MADE IN |
| | THE BUILDING?S DESIGN OR IN MATERIALS OR |
| | EQUIPMENT INSTALLED IN THE BUILDING |
| | WHICH WOULD DIMINISH IT?S ENERGY |
| | PERFORMANCE, AN AMENDED COPY OF THE |
| | COMPLIANCE CERTIFICATION SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL ON OR |
| | BEFORE THE DATE OF FINAL INSPECTION BY |
| | THE BUILDING OWNER OR HIS OR HER LEGALLY AUTHORIZED |
| | AGENT. |
| | THE CERTIFIED FLA/COM CALCULATION |
| | PRINTOUT OR FORM 400C SHALL BE A PART OF |
| | THE PLANS AND SPECIFICATIONS SUBMITTED |
| | FOR PERMITTING. |
| | THE PARTY RESPONSIBLE UNDER SUBSECTIONS |
| | 471.003 AND 481.228 AND CHAPTER 489, |
| | FLORIDA STATUTES , FOR THE DESIGN AND SPECIFICATION OF |
| | EACH BUILDING SYSTEM |
| | SHALL CERTIFY THAT THE PLANS AND |
| | SPECIFICATIONS FOR THAT SYSTEM COMPLY |
| | WITH THE REQUIREMENTS OF CHAPTER 13 OF |
| | THIS CODE (SEE ALSO SECTION 13-103.2 ). |
| | PLEASE SUBMIT THE APPROPRIATE FORMS |
| | SIGNED AND SEALED BY THE DOR FOR EACH |
| | SYSTEM. ALSO SEE SECTION 13-101.1.6. |
| | |
| | 5) FBC* 105.13.1SPECIAL INSPECTOR.A |
| | STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING.A THRESHOLD |
| | BUILDING IS ANY BUILDING WHICH IS |
| | GREATER THAN THREE STORIES OR 50 FEET IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY WITH 5,000 SQFT AREA AND |
| | GREATER THAN 500 OCCUPANTS.THREE |
| | COPIES OF THE PLANS AND OTHER DOCUMENTS |
| | WILL BE REQUIRED FOR PERMITTING PURPOSES |
| | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| | SERVICES MANAGER - TEL: |
| | 561 805 6711), A MEETING INVOLVING THE |
| | OWNER, THRESHOLD INSPECTOR, JOB |
| | INSPECTOR, CONTRACTOR AND ENGINEER. |
| | |
| | 6) SEVERAL OF THE SECTION TAGS ARE |
| | INCORRECT ON SHEET S-5. |
| | - THERE IS A TAG FOR SECTION 11 ON S-10, |
| | BUT 11 ON S-10 IS BLANK. |
| | - THERE IS A TAG FOR SECTION 7 ON S-10, |
| | BUT 7 ON S-10 SAYS NOT USED. |
| | - TWO OF THE SECTION 9 ON S-10 TAGS ARE |
| | NOT IN THE CORRECT LOCATIONS ON S-5. |
| | |
| | 7) THE WIND PRESSURES FOR THE WINDOW |
| | SCHEDULE ON SHEET A8.1.1 DO NOT CONCUR |
| | WITH THE OPENING PRESSURES ON S11. |
| | |
| | 8) THE RAMP HEIGHT ON DRAWING 2 ON |
| | A1.2.1 IS 16" AND THE HEIGHT OF THE |
| | STEPS IS 18". PLEASE CORRECT. |
| | |
| | 9) FBC 11-4.8.4 REQUIRES 72 INCHES OF |
| | STRAIGHT AND LEVEL CLEARANCE AT THE |
| | BOTTOM OF RAMPS. DRAWING 2 ON A1.2.1 HAS |
| | ONLY 60 INCHES OF CLEARANCE. PLEASE |
| | CORRECT. |
| | |
| | 10) FBC 3002.4 ELEVATOR CAR TO |
| | ACCOMMODATE AMBULANCE STRETCHER. |
| | IN BUILDINGS FOUR STORIES IN HEIGHT OR |
| | MORE, AT LEAST ONE ELEVATOR SHALL BE |
| | PROVIDED FOR FIRE DEPARTMENT EMERGENCY |
| | ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR |
| | SHALL BE OF SUCH A SIZE AND ARRANGEMENT |
| | TO ACCOMMODATE A 24-INCH BY 76-INCH (610 |
| | MM BY 1930 MM) AMBULANCE STRETCHER IN |
| | THE HORIZONTAL, OPEN POSITION AND SHALL |
| | BE IDENTIFIED BY THE INTERNATIONAL |
| | SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). THE SYMBOL SHALL NOT BE |
| | LESS THAN 3 INCHES (76 MM) HIGH AND |
| | SHALL BE PLACED INSIDE ON BOTH SIDES OF |
| | THE HOISTWAY DOOR FRAME. PROVIDE NOTE ON |
| | PLAN SPECIFYING THIS AND WHICH ELEVATOR |
| | COMPLIES. |
| | |
| | 11) ELEVATORS SHALL COMPLY WITH |
| | ACCESSIBILITY REQUIRES OF FBC 3007 AND |
| | 11-4.10. PROVIDE NOTE ON PLAN SPECIFYING |
| | SIGNAGE AND HEIGHT. |
| | |
| | 12) SHOW THE CURB RAMPS REQUIRED BY FBC |
| | 11-4.7 FROM THE ACCESSIBLE PARKING |
| | SPACES TO THE ACCESSIBLE SIDEWALK ON THE |
| | PLANS. |
| | |
| | 13)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | PRODUCT APPROVAL COVERSHEETS WITH THE |
| | STATE FL # FOR ALL ITEMS REQUIRED BY |
| | RULE 9B-72. THIS IS REQUIRED IN ADDITION |
| | TO THE NOA OR OTHER EVALUATION |
| | REPORT/INSTALLATION INSTRUCTIONS. |
| | |
| | 14) FBC*109.3.6 REQUIRES ALL PRODUCT |
| | APPROVALS SUBMITTED TO BE REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE |
| | FOLLOWING: |
| | - STEEL DOOR TO THE ROOF (RO1) |
| | - FIRE CORRIDOR EXIT DOOR (107) |
| | |
| | 16)TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | 17) ALSO SEE HANDWRITTEN NOTES AND |
| | CORRECTIONS ON THE PLANS (SET #3). |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |