Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop B
Sequence Number 18
Notes
Date Text
2007-11-07 10:11:192004 FBC
 SUBMITTAL FOR ROOFING (LIGHTWEIGHT CONCRETE, MODIFIED
 BITUMEN, RAS 117 CALCULATIONS)
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS FROM ATLANTIC & CARIBBEAN
 ROOF CONSULTING, LLC ARE REQUIRED TO BE SIGNED, SEALED
 AND DATED BY THE ENGINEER. THE EMBOSSED SEAL AND
 ORIGINAL SIGNATURES ARE REQUIRED. FS 741 AND FAC
 61G15-23.002
  
 2) THE ROOF COMPONENT AND CLADDING UPLIFT PRESSURES
 SPECIFIED ON THE RAS 117 CALCULATIONS DO NOT CORRESPOND
 WITH THE ROOF UPLIFT PRESSURES THAT ARE SPECIFIED ON
 STRUCTURAL SHEET S-12 OF THE PLANS (-76.9, -120.6) AND
 BOTH ARE FOR EXPOSURE CATEGORY 'C'. PLEASE CORRECT.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]