Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop B
Sequence Number 14
Notes
Date Text
2007-10-09 15:40:52STORE FRONT SUBMITTALS
 2004 FBC
  
 DENIED BY BUILDING
  
 1) THE DESIGN PRESSURES LISTED IN NOA 02-0215.16,
 02-0215.18 AND 04-0227.02 ARE REQUIRED TO BE DIVIDED BY
 1.33 TO COMPLY WITH 2004 FBC OR BE VARIFIED BY A
 FLORIDA P.E. SEE THE FL. COVER SHEETS.
  
 2) THE MULLION LOAD CAPACITY AND THE ANCHOR LOAD
 CAPACITY FOR THE YKK LARGE MISSILE IMPACT RATED STORE
 FRONTS ARE TOO LOW FOR THE -85.3 ZONE 5 WALL PRESSURE
 WHEN REDUCED BY ONE THIRD. PLEASE CORRECT.
  
 3) THE GLASS DESIGN LOAD ON SHEET 10 OF NOA 02-0215.16
 FOR THE GLASS SPECIFIED ON THE FRONT OF THE SUBMITTALS
 IS + 65 OR - 65, WHICH IS TOO LOW FOR FOR THE REQUIRED
 COMPONENT AND CLADDING PRESSURES OFWALL ZONE 5.
 PLEASE CORRECT.
  
 4) THE NEGATIVE MULLION LOAD CAPACITY FOR THE SMALL
 MISSILE IMPACT RATED YKK STORE FRONTS ARE TOO LOW FOR
 WALL ZONE 5 WHEN REDUCED BY ONE THIRD. PLEASE CORRECT.
  
  
 5) THE GLASS TYPE SPECIFIED ON SHEET 3 OF NOA
 02-0215.18 FOR THE SMALL MISSILE IMPACT RATED YKK STORE
 FRONTS IS DIFFERENT FROM THE ONE SPECIFIED ON THE COVER
 SHEET OF THE SUBMITTAL. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]