| 2006-03-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A003 PLUMBING FIXTURE CALCULATION |
| | INDICATE 3 DRINKING FOUNTAINS ARE |
| | REQUIRED ON EACH FLOOR. CALCULATIONS |
| | ALSO INDICATE THAT 4 DRINKING FOUNTAINS |
| | ARE PROVIDED ON EACH FLOOR. A HIGH/LOW |
| | DRINKING FOUNTAIN WITH ONE WASTE AND ONE |
| | WATER SUPPLY IS CONSIDERED ONE FIXTURE. |
| | ONLY 2 DRINKING FOUNTAINS ARE PROVIDED |
| | ON EACH FLOOR, AND ONE MORE DRINKING |
| | FOUNTAIN IS REQUIRED ON EACH FLOOR. |
| | TABLE 403.1. |
| | 2. SHT A105 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE FOR EACH AREA BEING |
| | DRAINED ALONG WITH 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS AS |
| | WELL AS THE AREA OF ANY ROOFS THAT DRAIN |
| | ONTO THE ROOF FROM ABOVE. SECTIONS 1106 |
| | & 1107 AND ALL SUBSECTIONS. - SHOW THE |
| | LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| | OVERFLOW SCUPPERS. OVERFLOW SCUPPERS |
| | SHALL BE SIZED PER SECTIONS 1101.7, |
| | 1107.3 AND TABLE 1106.7. SCUPPER SIZE |
| | CAN NOT BE CALCULATED WITHOUT REFERENCE |
| | TO DEFLECTION OF THE ROOF. PLEASE SHOW |
| | ON PLANS. |
| | 3. SHT A402 SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL ACCESSIBLE FIXTURES INCLUDING |
| | DRINKING FOUNTANS & UNINALS. SECTIONS |
| | 11-4.15.5(1) AND 11-4.18.3. |
| | 4. SHT P0.1 PLUMBING NOTES #13: AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| | FROM REFERENCE. SECTION 604.9. WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 SHALL BE LOCATED NEAR THE FIXTURES |
| | IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | 5. ALL NON-POTABLE WATER SYSTEMS AND |
| | PIPES SHALL BE LABELED. SECTION 608.8. |
| | 6. SHT P5.1 SANITARY RISER RISER |
| | ISOMETRIC. SHOW ALL PIPE SIZES AND |
| | INDICATE DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. SECTION 106.1.1. |
| | 7. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. SECTION |
| | 608.13.2 AND CROSS CONNECTION MANUAL |
| | SECTION 2.6. |
| | 8. SHT P6.1 FULL OPEN VALVE REQUIRED AT |
| | THE BASE OF EVERY WATER RISER PIPE. |
| | SECTION 606.1(3). |
| | 9. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR |
| | THE CONDENSATE AND THE STORM SYSTEMS. |
| | THIS SHALL INCLUDE THE VERTICAL RISERS |
| | AND THE BUILDING DRAINS. SHOW ALL PIPE |
| | SIZES FOR BOTH SYSTEMS, AND SHOW THE |
| | SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM FOR THE STORM SYSTEM. SECTION |
| | 106.3.5.1.3. |
| | 10. SUBMIT THE MANUF. SPECIFICATION |
| | SHEET FOR THE PUMPS. PUMPS SHALL BE |
| | LISTED. INDICATE MODEL NUMBER FOR EACH |
| | PUMP. SECTION 303.4. |
| | 11. SHT P7.1 CISTERN WATER RISER. MORE |
| | INFORMATION IS REQUIRED. INDICATE |
| | BUILDING SHOWN ON THE RISERS. SHOW ALL |
| | PIPE SIZES, AND SHOW THE LOCATIONS FOR |
| | THE REQUIRED BACKFLOWS WHERE THE POTABLE |
| | WATER TIES INTO THE NON-POTABLE WATER. |
| | SECTION 106.1.1. |
| | 12. SHOW THE SIZE OF ALL DOWNSPOUTS ON |
| | THE STORM DRAINAGE SYSTEM. IF COLLECTOR |
| | HEADS FOR THE PRIMARY ROOF DRAINS. |
| | SUBMIT A DETAIL SHOWING SIZE, HEIGHT & |
| | WIDTH. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |