| 2006-02-17 00:00:00 | DENIED: |
| | 1.PLAN SHEET M.01 MECHANICAL NOTE #1, |
| | REFERENCE STANDARDS ARE NOT THE CURRENT |
| | STANDARDS AS ADOPTED WITH THE 2004 FBC. |
| | (EXAMPLE - ASHRAE 62-01, 15-01, 34-01, |
| | NFPA 90A-02, 90B-02, ETC).PLEASE |
| | VERIFY ALL REFERENCED STANDARDS. |
| | |
| | 2.PLAN SHEET M0.2 O.A. CALCS & EXHAUST |
| | CALCS. REFERENCE THE WRONG ASHRAE |
| | STANDARD. |
| | |
| | 3.PLAN SHEET M2.1.1, PLEASE INDICATE |
| | RETURN AIR.PLEASE NOTE, NO |
| | COMBUSTIBLES ALLOWED IN THE PLENUM PER |
| | 2004 FMC 602.2.1 |
| | |
| | 4.PLAN SHEET M2.1.1, NOTES REFERENCE |
| | PLAN SHEET M7.3 FOR DETAIL OF THE |
| | UNDERFLOOR AIR HIGHWAY LOOP & THE FUTURE |
| | "YORK FLEXSYS VAV MIT TERMINAL |
| | DIFFUSER".DETAILS ON PLAN SHEET M7.3 |
| | DO NOT SHOW THIS APPLICATION.ALL |
| | DETAILS INDICATE DUCT SYSTEM IN THE |
| | CEILING.PLEASE INDICATE HOW THE DUCT |
| | WILL BE SUPPORTED UNDER THE FLOOR. |
| | |
| | 5.PLAN SHEET M2.1.1, 2.1.2, & 2.2.2 |
| | MECHANICAL ROOMS ARE OPEN RETURN WITH |
| | FLOOR DRAINS INDICATED IN THE MECHANICAL |
| | ROOM.PLANS DO NOT PROVIDE A LAYOUT OF |
| | THE CONDENSATE FROM THE AHU.IS THE |
| | INTENT TO TERMINATE INTO THE FLOOR |
| | DRAIN? WHAT WILL BE THE PRESSURE |
| | DIFFERENTAL IN THE RETURN AIR PLENUM. |
| | PLEASE REFERENCE 2004 FPC SECTION 901.2. |
| | |
| | 6.PLEASE INDICATE PIPING MATERIAL FOR |
| | THE CONDENSER WATER.2004 FMC CHAPTER |
| | 12. |
| | |