| 2006-02-10 00:00:00 | IN ELEC FOR REVIEW. |
| | ********** UNSAT ********** |
| | |
| | ** PLEASE KNOW, PLANS AND SUBMITTIALS |
| | ARE NOT COMPLETE AT THIS TIME. |
| | |
| | |
| | 1)NOTE: PLEASE SEE ALL CURRENT CODES |
| | SHALL BE REFERENCED TO THE CURRENT CODES |
| | IN EFFECT. PLEASE SEE PLANS CALL FOR |
| | 2001 FLORIDA BUILDING CODE. PLEASE KNOW, |
| | AS OF OCT 1ST, 2005 THE NEW FBC IS THE |
| | 2004 EDITION. PLEASE SEE THE FOLLOWING |
| | SHALL BE REFERENCED. 2003 NFPA-101, 2002 |
| | NFPA-70, AND 2002 NFPA-72 |
| | |
| | 2)NOTE: PLANS WILL REQUIRED BATTERY BACK |
| | UP LT FIXTURES IN MAIN ELECTRICAL RM, |
| | ELEVATOR RMS. |
| | PLEASE ALSO KNOW BATTERY BACK UP |
| | FIXTURES WILL BE REQUIRED IN STAIRWAY |
| | AND EGRESS PATHS TO PROVIDE A MIN OF 1FT |
| | CANDLE OF LIGHT BY SOME SORT OF BATTEY |
| | BACK UP FIXTURE. PLEASE SEE NFPA-101 |
| | 7.9.2.2, TRIPPING OR SHUTTING OFF ANY |
| | SINGLE DEVICE OR MEANS OF OVERCURRENT |
| | PROTECTION SHALL NOT LEAVE ANY ONE |
| | EGRESS PATH IN TOTAL DARKNESS. |
| | PLEASE PROVIDE PHOTOMETRICS FOR |
| | STAIRWAYS, AS THE 2003 LS 101 7.8.1.3 |
| | REQUIRES A MIN OF 10FT CANDLES(108LUX) |
| | IN STAIRWAYS UNDER NORMAL LIGHTING |
| | CONDITIONS AND 7.9.2.2 PERMITS THE |
| | DERATING TO A MIN OF 1FT CANDLE UNDER |
| | EMERGENCY CONDITIONS. |
| | 700.16.,700.12E ETC |
| | |
| | 3)NOTE: PLEASE SEE ADDRESS REVIEW. |
| | PLEASE KNOW, IF PROPERTY CHANGE LEGALLY |
| | TO SEPARATE PROPERTIES/ PCN. ELECTRICAL |
| | DESIGN MAY BE AFFECTED. PLEASE ALSO |
| | KNOW, LEGAL EASEMENTS MAY BE REQUIED. |
| | |
| | 4)NOTE: PLEASE SEE REQUIREMENTS OF |
| | 225.31-225.39 FOR FEEDERS COMING FROM |
| | GARAGE BLDG. |
| | PLEASE SEE MEAANS OF DISCONNECT FOR ALL |
| | FEEDERS FROM GARAGE IS REQUIRED, ALL |
| | MUST BE GROUPED AND RATED FOR THE LOAD |
| | SERVED , IN CLUDING ALL AS NOTED IN |
| | ABOVE CODES. |
| | PLEASE SEE ELECTRICAL RISER WILL BE |
| | AFFECTED WITH CHANGES AND A MORE |
| | COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| | BE DONE THAT TIME. |
| | |
| | 5)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEMS AT SEPARATE BLDGS. |
| | PLEASE ALSO PROVIDE A ONE-LINE DIAGRAM |
| | OF THE ENTIRE GROUNDING ELECTRODE |
| | CONDUCTOR AND GROUNDING ELECTRODE SYSTEM |
| | PER 250.58,250.30 |
| | |
| | 6)NOTE: PLEASE PROVIDE WIND LOAD |
| | CALCUALTIONS FOR BLDG REVIEW FOR ANY |
| | SITE LIGHTING POLES BEING RELOCATED OR |
| | NEW. ALL MUST MEET 2004 FBC 140 MPH |
| | |
| | 7)NOTE: PLEASE SEE E-1.2 WHICH SHOWS A |
| | PANEL HP AND DISCONNECT, HOWEVER THESE |
| | ARE NOT LOCATED ON RISER FOR REVIEW? |
| | PLEASE ALSO SEE A NOTE #2 IS SHOWN ON |
| | PLANS, HOWEVER A NOTE #2 IS NOT ON SHEET |
| | FOR EXPLANATION OF NOTE?? |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE 620.23,620.24 FOR |
| | REQUIRED DEDICATED CIRCUITS IN ALL |
| | ELEVATOR EQUIPMENT RMS. PLEASE ALSO SEE |
| | ELEVATOR PITS, LTS, GFI ARE ALSO |
| | REQUIRED TO BE DEDICATED. |
| | |
| | 9)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125% 215.3,230.42 ETC |
| | |
| | 10)NOTE: PLEASE PLACE NOTE ON "LIGHTNING |
| | PROTECTION PLANS". ANY PROPOSED |
| | LIGHTNING PROTECTION SYSTEM SHALL MEET |
| | NFPA-780. OR WORDS TO THAT AFFECT. |
| | IT WAS NOTED THE LIGHTNING PROTECTION |
| | WILL BE UNDER A SEPARATE PERMIT. |
| | |
| | 11)NOTE: PLEASE SEE ALL PANELS ON THE |
| | LOAD SIDE OF TRANSFORMERS SHALL CONTAIN |
| | MCB'S AS REQUIRED PER 408.16 |
| | |
| | 12)NOTE: PLEASE SEE RISER AS SHOWN UNDER |
| | THIS PERMIT SHALL BE COMPLETE WITH ALL |
| | FEEDERS, CONDUITS ETC. |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE INDICATE ALL PANELS WITH |
| | FEED-THRU LUGS FROMTHE SECONDARY SIDE OF |
| | |
| | L1A, L2A, L3A ETC |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE COMPLETE AND SUBMIT MIN |
| | LOAD CALCUALTIONS AS REQUIRED PER |
| | NEC.220 |
| | |
| | 16)NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| | 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP |
| | INFORMATION NEEDED. |
| | |
| | 17)NOTE: PLEASE SEE LIGHTING |
| | REQUIREMENTS UNDER 13-415 FOR AREAS OF |
| | CONTROL AND TANDEM WIRING. |
| | PLEASE SPECIFY THIS INFORMATION ON |
| | PLANS. |
| | |
| | 18)NOTE: PLEASE SEE MANY OF THE |
| | ENGINEER'S SEALS ARE NOT |
| | "RAISED/EMBOSSED" ENOUGH TO CLEARLY SHOW |
| | ALL INFORMATION AS REQUIRED UNDER FS |
| | 471.025 |
| | PLEASE KNOW, ALL SEALS MUST CONTAIN THE |
| | WORD "LICENSE" INSTEAD OF THE OLD |
| | "CERTIFICATE", IF SEAL IS NEWER AND |
| | MENTIONS "LICENSE PLEASE DISREGARD. |
| | PLEASE SEE THE FBPE'S HAD EXTENDED THE |
| | DATE TO JAN 1ST,2006 FOR ALL SEALS TO BE |
| | CHANGED. |
| | |
| | 19)NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| | SEALED "PHOTO-COPIES" OF ARCHITECT'S |
| | SIGNATURE. PLEASE SEE FS 481.221 WHICH |
| | REQUIRES THE SIGNATURE TO BE AN ORIGINAL |
| | SIGNATURE. |
| | |
| | ** PLEASE KNOW, REVIEW FOR MAIN BLDG HAS |
| | NOT COMMENCED AT THIS TIME. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ON.Y INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONLY SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |