2006-11-27 11:37:41*****DENIED*****
  
  
  
  
 1. THE SUBMITTED PLANS INDICATE THAT THE DISTANCE FROM
 THE FIRE DEPARTMENT CONNECTION (FDC) TO THE NEAREST
 FIRE HYDRANT IS GREATER THAN 150 FEET.AS PER THE FIRE
 MARSHAL, THE FDC SHALL BE NO GREATER THAN 150 FEET TO
 THE NEAREST HYDRANT.
  
 2.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
  
  
  
  