| Plan Review Notes For Permit 05121211 |
| Permit Number |
05121211 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-27 11:37:41 | *****DENIED***** | | | | | | | | | | | | | | | 1. THE SUBMITTED PLANS INDICATE THAT THE DISTANCE FROM | | | THE FIRE DEPARTMENT CONNECTION (FDC) TO THE NEAREST | | | FIRE HYDRANT IS GREATER THAN 150 FEET.AS PER THE FIRE | | | MARSHAL, THE FDC SHALL BE NO GREATER THAN 150 FEET TO | | | THE NEAREST HYDRANT. | | | | | | 2.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|