Plan Review Notes
Plan Review Notes For Permit 05121211
Permit Number 05121211
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-05-01 00:00:00***********DENIED********************
 PERMITS 05121211 AND 05121212
  
 1) THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE 2 1/2 INCH CONNECTION. THE WEST
 PALM BEACH FIRE DEPT USES 5 INCH HOSE.
  
 2) EXACTLY HOW FAR IS THE NEAREST FIRE
 HYDRANT. THE FIRE MARSHAL (AHJ) MAY
 REQUIRE A FIRE HYDRANT INSTALLED THAT'S
 CLOSER.
  
 3) WHEN THIS PROJECT WAS REVIEWED BY
 PLANNING & ZONING AND FIRE,THE FDC WERE
 NOTED TO BE MINIMUM OF 150 FEET TO THE
 NEAREST FIRE HYDRANT.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754