| Notes |
| Date |
Text |
| 2006-05-01 00:00:00 | ***********DENIED******************** | | | PERMITS 05121211 AND 05121212 | | | | | | 1) THE FIRE DEPARTMENT CONNECTION (FDC) | | | SHALL BE 2 1/2 INCH CONNECTION. THE WEST | | | PALM BEACH FIRE DEPT USES 5 INCH HOSE. | | | | | | 2) EXACTLY HOW FAR IS THE NEAREST FIRE | | | HYDRANT. THE FIRE MARSHAL (AHJ) MAY | | | REQUIRE A FIRE HYDRANT INSTALLED THAT'S | | | CLOSER. | | | | | | 3) WHEN THIS PROJECT WAS REVIEWED BY | | | PLANNING & ZONING AND FIRE,THE FDC WERE | | | NOTED TO BE MINIMUM OF 150 FEET TO THE | | | NEAREST FIRE HYDRANT. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|