Plan Review Notes
Plan Review Notes For Permit 05121150
Permit Number 05121150
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 DIAGRAM WITH PLANS. PLEASE SEE NO POOL
 LT IS SHOWN ?
 PLEASE SEE MISSING EQUIPMENT GRND FOR
 THE "SERVICE LT"
  
  
 2)NOTE: PLEASE PROVIDE INFORMATION WHERE
 THE PANEL IS BEING FED FROM ? NEW ,
 EXISTING? ETC.
  
 215.5
  
 3)NOTE: PLEASE CORRELATE ALL ELECTRICAL
 DEVICES WHICH ARE FED FROM PANEL. PLEASE
 ADJUST LOAD CALCUALTIONS AS NEEDED.
 PLEASE ALSO INDICATE ALL CONTINUOUS
 LOADS @125%. 215.3,230.42
  
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  