| Plan Review Notes For Permit 05121150 |
| Permit Number |
05121150 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-31 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL | | | DIAGRAM WITH PLANS. PLEASE SEE NO POOL | | | LT IS SHOWN ? | | | PLEASE SEE MISSING EQUIPMENT GRND FOR | | | THE "SERVICE LT" | | | | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION WHERE | | | THE PANEL IS BEING FED FROM ? NEW , | | | EXISTING? ETC. | | | | | | 215.5 | | | | | | 3)NOTE: PLEASE CORRELATE ALL ELECTRICAL | | | DEVICES WHICH ARE FED FROM PANEL. PLEASE | | | ADJUST LOAD CALCUALTIONS AS NEEDED. | | | PLEASE ALSO INDICATE ALL CONTINUOUS | | | LOADS @125%. 215.3,230.42 | | | | | | | | | **PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|