Plan Review Notes
Plan Review Notes For Permit 05121124
Permit Number 05121124
Review Stop E
Sequence Number 5
Notes
Date Text
2007-04-15 12:39:07********* UNSAT4THREVIEW ***********
  
 ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS
 REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO CHANGES IN PLANS WHICH DECREASED ON OF
 THE UNITS UPSTAIRS AND CHANGED FROM COMMERCIAL OFFICE
 USE TO RESIDENTIAL.
  
 ** IMPORTANT**
 THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS
 MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY
 ARE RESIDENTIAL OR COMMERCIAL OFFICES.
  
  
 1) NOTE:PLEASE SEE NOTE #27 FROM THE PREVIOUS THREE
 REVIEWS FOR COMPLIANCE WITH THE 2004 FBC CHAPTER 13.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH PLANS, AND FIXTURE LEGENDS FOR THE NUMBER OF
 FIXTURES, TYPES, WATTAGES ETC. THERE ARE MULTIPLE ITEMS
 WHICH DO NOT MATCH.
 PLEASE SEE THE CONTROLS ON THE CALCULATIONS INDICATE
 MANUAL ON/OFF WHEN AUTOMATED CONTROLS ARE REQUIRED FOR
 CERTAIN AREAS.
 PLEASE SEE NEW RESIDENTIAL UNITS FALL UNDER SEPARATE
 REQUIREMENTS.
 PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES.
 PLEASE SEE MULTIPLE LOCATIONS WHICH DO NOT INDICATE
 EITHER TIMER TYPE OR OCCUPANCY TYPE DEVICES?
 NOTES LOCATED ON SOME ITEMS, HOWEVER SOME OF THE NOTES
 LIKE NOTES #1 AND #2 INDICATE LIGHTING ON THE INSIDE
 BEING CONTROLLED BY A PHOTO-CELL ALONG WITH OUTSIDE
 LIGHTING?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE INPUT DATA REPORT WHICH DOES NOT SEEMS
 COORDINATE WITH TOTAL ALLOWANCE ON FRONT SECTION OF
 CALCULATIONS.
 ** PLEASE SEE NOTES FOR EGRESS STAIRS AND CORRIDORS.
  
 2) NOTE: PLEASE SEE NEW SHEET E-8 NOW SUBMITTED FOR
 FIRE ALARM SYSTEM WHICH WAS NOT ON PREVIOUS PLANS.
 PLEASE SEE ELECTRICAL PLANS INDICATE THE FAAP WITH
 NOTES BEING THE FACP? PLEASE SEE E-8 WHICH INDICATES
 THE FACP LOCATED INSIDE THE TENANT *A* WHICH IS NOT
 PERMITTED. THIS DOES NOT CORRESPOND TO THE E-8 SHEET.
 PLEASE CLARIFY THE DESIGNATED DEDICATED *SMOKE
 DETECTOR* CIRCUIT ON HP WHEN THESE DEVICES SHOULD BE ON
 THE FACP??
 PLEASE SEE NOTES ALSO MENTIONS A COMPLETE FIRE
 SPRINKLER SYSTEM WHICH IS TO BE INSTALLED HOWEVER NO
 BASE DESIGN PLANS WERE SUBMITTED. PLEASE SEE FIRE
 MARSHAL REVIEW NOTES AND SEE FBC 106.3.5.1.2 AS THE
 BASE PLANS SHALL SHOW THE REQUIRED PROPOSED SYSTEM
 ALTHOUGH THE FS WILL BE UNDER A SEPARATE PERMIT. PLEASE
 SEE THAT THE DEVICES FOR HORNS AND STROBES SHALL MEET
 FBC 11-4.28.1,.2 AND .3(4).
 PLEASE INDICATE ALL OF THE MINIMUM LEVELS IN AREAS FOR
 ADA COMPLIANCE.
 PLEASE KNOW, AS THE REQUIRED VERTICAL ACCESSIBILITY HAS
 NOT YET BEEN DETERMINED, THIS MAY REQUIRE OTHER DEVICES
 TO BE INCREASED.
  
 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE COMMON
 AREA ROOMS/CLOSETS WHICH ARE ONLY ACCESSIBLE FROM THE
 TENANT SPACE. THIS WAS BROUGHT UP IN THE PREVIOUS
 MEETING WITH THE DESIGNER. PLEASE COORDINATE WITH NOTES
 ABOVE FOR LOCATION OF *HOUSE* EQUIPMENT AND ACCESS TO
 THESE LOCATIONS.
 IF THESE ROOMS ARE PART OF HOUSE EQUIPMENT, POWER ETC,
 THEN THESE MUST BE ACCESSED FROM OTHER THAN INSIDE THE
 TENANT SPACE.
  
 4) NOTE: PLEASE SEE THE LOCATION OF THE *HP* PANEL
 WHICH IS BEING SHOWN IN THE FIRE RATED EGRESS CORRIDOR
 AND EXIT STAIRS.
 PLEASE SEE THIS WILL BE NOTED FROM BUILDING AND FIRE
 REVIEW FOR EXACT LOCATION WHICH IS NOT PERMITTED IN
 RATED STAIR/EXIT/EXIT ACCESS ETC.
 PLEASE SEE FBC CHAPTER 10 FOR ITEMS WHICH ARE PERMITTED
 IN THESE AREAS MAY ONLY BE PERTAINING TO THE ELECTRICAL
 EQUIPMENT AND DEVICES FOR THESE AREAS.
  
 5) NOTE: PLEASE SEE NOTE #8 FROM ALL PREVIOUS REVIEWS
 WHICH GAVE SECTIONS 210.52B1, 220.16 AND 210.11C1 FOR
 THE MINIMUM OF TWO OR MORE SMALL APPLIANCE CIRCUITS AND
 WHAT IS PERMITTED TO BE ON THESE CIRCUITS.
 PLEASE SEE PLANS WHICH STILL INDICATE DINING ROOM
 RECEPTACLE CIRCUITS WHICH ARE NOT FIGURED AT MINIMUM VA
 AS REQUIRED PER 210.11C1 AND 220.16.
 PLEASE SEE PLANS INDICATE SOME OF THESE AREAS WHICH
 CONTAIN SEVERAL CIRCUITS WHICH ARE BEING SHOWN AS
 GENERAL RECEPTACLE CIRCUITS.
 PLEASE SEE E-17, E-2, C-23, D-2, C-23 ETC.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO 210.52 WHICH IS
 MISSING SOME RECEPTACLES AS REQUIRED IN BREAKFAST/BAR
 AREAS FOR WALL SPACE AND ALSO MISSING DEVICES FOR WALL
 SPACES IN DINING AREAS.
 ** LOADS ON THESE CIRCUITS SHALL BE 1500VA, NO OTHER
 AREAS/DEVICE UNLESS LISTED AS AREAS OF THE LIKE AS
 STATED IN THE CODE ARE PERMITTED ON THESE CIRCUITS. * *
 PLEASE SEE RANGE HOOD J-BOXES WHICH ARE BEING SHOWN ON
 THE SMALL APPLIANCE CIRCUITS WHICH IS NOT PERMITTED. A
 RANGE HOOD IS NOT ONE OF THE PERMITTED APPLIANCES WHICH
 MAY BE ON THE SM APPL. CIRCUITS.
  
 6) NOTE:PLEASE SEE SEVERAL AREAS FOR MISSING
 RECEPTACLES PER 210.52.
 PLEASE SEE UNIT E WHICH IS MISSING DEVICES WITHIN 6FT
 OF DOORWAYS, MORE THAN 12FT OF WALL WITHOUT A DEVICE.
 PLEASE ALSO SEE UNIT *C* AND *D* DINING AREA WALL WHICH
 HAS MORE THAN 12FT OF WALL WITHOUT A DEVICE.PLEASE
 SEE LIVING ROOM AREA IN UNIT E. PLEASE SEE ONE SET OF
 PLANS ARE REDLINED WITH SOME OF THESE LOCATIONS.
  
 7) NOTE: PLEASE SEE UNIT E WHICH SHOWS A WATER HEATER
 DESIGNATION LOCATED IN THE MIDDLE OF THE KITCHEN
 COUNTER SPACE??
 PLEASE ALSO SEE THE PLANS INDICATE THE WATER HEATER IN
 A CLOSET?
 PLEASE SEE 422.17 AS THE WATER HEATER IS BEING SHOWN IN
 A STORAGE CLOSET WHICH CONTAINS EASILY IGNITABLE
 MATERIALS.* EACH ELECTRICALLY HEATED APPLIANCE THAT IS
 INTENDED BY SIZE, WEIGHT, AND SERVICE TO BE LOCATED IN
 A FIXED POSITION SHALL BE PLACED SO AS TO PROVIDE AMPLE
 PROTECTION BETWEEN THE APPLIANCE AND ADJACENT
 COMBUSTIBLE MATERIAL*.
  
 8) NOTE: PLEASE SEE 410.8 AS THE LIGHT FIXTURE IN THE
 CLOSET IN UNIT *C* DOES MEET THE MINIMUM CLEARANCES ARE
 REQUIRED.
 PLEASE RELOCATE OR REMOVE.
  
 9) NOTE: PLEASE SEE UNIT E- WHICH IS MISSING THE
 STOVE/RANGE CIRCUITING FROM PLANS.
 PLEASE ALSO SUBMIT THE MANUFACTURE INFORMATION SPECS ON
 THIS STOVE/RANGE. THE SIZE AND LOAD FOR WHAT IS BEING
 SHOWN ON PLANS AS A FULL SIZE APPLIANCE SEEMS TO BE
 VERY LOW.
 PLEASE SEE THE TABLES IN 220.19.
 ** PLEASE ALSO VERIFY PLANS AS THEY ARE INDICATING GFCI
 PROTECTION FOR THE RANGE/STOVE??
  
 10) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. MAINS, PANELS AND BREAKERS. PLEASE
 SEE PANELS DO INDICATE RATINGS AT 22K, HOWEVER IF SHOWN
 AS 22K FOR THE ENTIRE PANEL AS FULLY RATED, THEN THIS
 WOULD MEAN ALL OF THE BRANCH BREAKERS WOULD BE 22K
 RATED. IS THIS WHAT IS REALLY INTENDED?
  
 11) NOTE: PLEASE COMPLETE THE PHOTO-METRICS AS THE
 LEVELS ARE NOT READABLE ON PLANS SUBMITTED FOR WALKWAY
 AREAS AND STAIRS.
 PLEASE CLARIFY HOW THE PHOTO-METRICS INDICATE ONE TYPE
 OF FIXTURE BEING FIGURED FOR LIGHTING LEVELS, YET THE
 LIGHTING PLANS AND FIXTURE LEGEND INDICATE A DIFFERENT
 TYPE OF FIXTURE? IN FACT THE LIGHTING FIXTURES WHICH
 ARE NOTED TO BE USED ON PHOTO-METRICS ARE NOT EVEN
 LISTED ON THE FIXTURE LEGEND?
 PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR
 SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO
 EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE
 SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE
 FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM
 NFPA-101.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2)
 THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING
 SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF
 AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE
 FLOOR.
 * PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE OF
 ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY ONE
 EGRESS AREA IN TOTAL DARKNESS.
  
 12) NOTE: PLEASE COORDINATE ALL CIRCUITS. PLEASE SEE
 CIRCUITING FOR LIGHTING IN UNIT E, WHICH INDICATES E-19
 FOR BEDROOM LIGHTING AND LIGHTING IN OTHER AREAS, YET
 THE PANEL SCHEDULE SHOWS THIS CIRCUIT AS THE CIRCUIT
 FOR THE WASHER??
 PLEASE SEE 210.12 FOR AFCI PROTECTION IN THE 2002 NEC>
  
 13) NOTE: PLEASE CLARIFY THE NOTES ON THE LIGHTING
 PLANS FOR THE RESIDENTIAL UNITS ON THE SECOND FLOOR
 WHICH SEEM TO INDICATE LIGHTS FOR COMMERCIAL SPACE??
 PLEASE SEE NOTE #1 FOR E UNIT WHICH MENTIONS EMERGENCY
 LIGHTING ETC??
 FBC 106.1.2
 SEE E-6.
  
 14) NOTE: PLEASE CLARIFY RISER AS THE RISER SHOWS ONE
 LARGER GUTTER/TROUGH, YET PLANS INDICATE A DOOR LOCATED
 IN THE MIDDLE OF THE GUTTER. PLEASE KNOW IF THE WALL
 SPACE IN NOT CONTINUOUS THEN SOME THING MUST BE DONE
 WITH THE RISER AND ADJUSTED TO INCLUDE FEEDERS TO
 METERS/DISCONNECTS.
 AS SHOWN, THIS IS NOT POSSIBLE.
 PLEASE REVISE RISER, PLANS OR DOOR LOCATION FOR RISER
 TO BE COMPLETE AT ONE LOCATION.
 215.5.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 15) NOTE: PLEASE COMPLETE THE ROOM/AREA DESIGNATIONS ON
 PANEL SCHEDULE TO CORRELATE WITH THE DESIGNATIONS ON
 PLANS.
 PLEASE SEE THE FOLLOWING TEXT FROM 408.4 WHICH MENTIONS
 THE USE OF *GENERAL RECEPTACLES/GENERAL LIGHTING* IS
 NOT PERMITTED.
 SOME CIRCUITS AS SHOWN ARE NOT CLEAR.
 DESIGNATIONS ARE NOT SHOWN ON LIGHTING PLANS.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 16) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 THE FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS.
 PLEASE KNOW AT THIS TIME A FEE OF $6,600 HAS NOW BEEN
 ASSESSED AS REQUIRED UNDER THE FLORIDA STATUTES AS
 THERE HAVE BEEN SOME OF THE SAME COMMENTS REPEATED FOR
 CODE COMPLIANCE FROM PREVIOUS REVIEWS
 THIS FEE IS ASSESSED TO THE DESIGN PROFESSIONAL AS
 REQUIRED UNDER THE FLORIDA STATUTES AND MUST BE PAID
 BEFORE THE NEXT RE-SUBMISSION OF PLANS.
 ** PLEASE ALSO KNOW THAT ONE COMPLETE SET OF PLANS WILL
 BE RETAINED BY THIS OFFICE TO BE PLACED WITH PLANS FROM
 PREVIOUS REVIEWS FOR POSSIBLE REVIEW BY THE STATES
 LEGAL COUNSEL TO THE BOARD OF ARCHITECTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]