| Plan Review Notes For Permit 05121124 |
| Permit Number |
05121124 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-04-10 19:03:50 | PLAN DENIED | | | 1) PLEASE MARK FLEX SIZES ON THE PLANS . | | | 2) PAGE M-3 GROUND FLOOR GRILL D AT 300 CFM DOES NOT | | | MATCH AIR DEVICE SCHEDULE . | | | 3) PAGE M-3 UPPER FLOOR MECHANICAL SHAFT PLEASE REFER | | | TO SECTION 607.5.5.1 FBC (M) 2004 | | | 4) PLEASE PROVIDE A DTAIL FOR CURB TIE DOWN TO ROOF . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|