| 2007-06-12 14:21:52 | ***DENIED*** | | | | | | PLEASE SEE COMMENTS TAKEN FROM PREVIOUS FIRE REVIEW IN | | | ADDITION TO NEW COMMENTS: | | | | | | 1) PLEASE NOTE THAT THE RESPONSE LETTER INDICATES THAT | | | NFPA 101, SEC. 6.1.14 IS NOW SHOWN ON COVER SHEET. | | | PLEASE CLOUD THAT NOTE AS I WAS UNABLE TO LOCATE. | | | | | | 2) THE WORDING SHOULDL BE FIRE ALARM TO BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. | | | | | | 3) FIRE EXTINGUISHERS TO BE 2A-10 B,C RATED, NOT C. | | | PLEASE MAKE CORRECTION AND SHOW ON PLANS. | | | | | | NEW COMMENTS: | | | | | | 1) ADDRESS REQUIRED ON BUILDING TO BE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING TO BACKGROUND. PLEASE SHOW SIZE | | | REQUIREMENTS ON ELEVATIONS. | | | | | | 2) PLEASE SEE ELECTRICAL COMMENTS REGARDING FIRE | | | PROTECTION SYSTEMS. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|